Project ID: 993771 DEA: 07325204 EFIS: 0716000082
QA Service Level: 1
DIST-CO-RTE-PM: 07-LA-210-R36.7/R37.1
Work Description: San Gabriel River Bridge - CM/GC Project - Hinge And Diaphragm Repairs
Location Description: Los Angeles County - LOS ANGELES COUNTY IN IRWINDALE FROM 0.2 MILE EAST OF 0.7 MILE WEST OF IRWINDALE AVENUE OVECROSSING
Contractor Name: FLATIRON WEST INC
Contractor Address: 14726 Ramona Avenue, Suite 300, Chino, CA 91710
Resident Engineer: Moe Izadpanah Structure Rep.: Quynh Nguyen
DIME Sample ID: 2022-08-21-1
TL Number from the TL Form: Set 2
Sample Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Sample Organization Contact: 213-792-4794
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 08/21/2022
Date that the sample was received by the laboratory/organization performing the testing: 08/23/2022
The quantity of what the sample constitutes: 10
A brief description of the sample: Concrete Cylinders
From where was the sample collected: Job Site
Laboratory sample identification: 1044-2
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Flatiron
The concrete mix design number: Not Provided
The truck number from where the sample was collected: Not Provided
The batch plant ticket number from where the sample was collected: Not Provided
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Site
Where the material sample would have been placed if not sampled: Hinge and Deck
From Lot No.:
Bag Lot No.:
DIME Test ID: 2022-08-21-1-1
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617 - Sulfur Mortar Cap
Verified Date: 08/23/2022
Date Tested: 08/23/2022
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Cross sectional area of cylinder 1
|
28.37 in^2
|
Cross sectional area of cylinder 2
|
28.37 in^2
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
Compressive strength (to nearest 10 psi)
|
5270 psi
|
Average diameter of cylinder 1
|
6.01 in
|
Average diameter of cylinder 2
|
6.01 in
|
Compressive strength of cylinder 1
|
5315.7 psi
|
Compressive strength of cylinder 2
|
5226.3 psi
|
Maximum load on cylinder 1
|
150805 lb
|
Maximum load on cylinder 2
|
148270 lb
|
Type of fracture pattern of cylinder 1
|
3
|
Type of fracture pattern of cylinder 2
|
3
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Age of specimen
|
2 days
|
DIME Test ID: 2022-08-21-1-2
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617 - Sulfur Mortar Cap
Verified Date: 08/28/2022
Date Tested: 08/28/2022
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Cross sectional area of cylinder 1
|
28.27 in^2
|
Cross sectional area of cylinder 2
|
28.27 in^2
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
Compressive strength (to nearest 10 psi)
|
6010 psi
|
Average diameter of cylinder 1
|
6.00 in
|
Average diameter of cylinder 2
|
6.00 in
|
Compressive strength of cylinder 1
|
6065.3 psi
|
Compressive strength of cylinder 2
|
5963.9 psi
|
Maximum load on cylinder 1
|
171465 lb
|
Maximum load on cylinder 2
|
168600 lb
|
Type of fracture pattern of cylinder 1
|
2
|
Type of fracture pattern of cylinder 2
|
2
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Age of specimen
|
7 days
|
DIME Test ID: 2022-08-21-1-3
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617 - Sulfur Mortar Cap
Verified Date: 09/08/2022
Date Tested: 09/04/2022
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Cross sectional area of cylinder 1
|
28.18 in^2
|
Cross sectional area of cylinder 2
|
28.27 in^2
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
Compressive strength (to nearest 10 psi)
|
7960 psi
|
Average diameter of cylinder 1
|
5.99 in
|
Average diameter of cylinder 2
|
6.00 in
|
Compressive strength of cylinder 1
|
7992.9 psi
|
Compressive strength of cylinder 2
|
7933.7 psi
|
Maximum load on cylinder 1
|
225240 lb
|
Maximum load on cylinder 2
|
224285 lb
|
Type of fracture pattern of cylinder 1
|
1
|
Type of fracture pattern of cylinder 2
|
1
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Age of specimen
|
14 days
|
DIME Test ID: 2022-08-21-1-4
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617 - Sulfur Mortar Cap
Verified Date: 09/11/2022
Date Tested: 09/11/2022
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Cross sectional area of cylinder 1
|
28.27 in^2
|
Cross sectional area of cylinder 2
|
28.37 in^2
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
Compressive strength (to nearest 10 psi)
|
8380 psi
|
Average diameter of cylinder 1
|
6.00 in
|
Average diameter of cylinder 2
|
6.01 in
|
Compressive strength of cylinder 1
|
8448.5 psi
|
Compressive strength of cylinder 2
|
8301.6 psi
|
Maximum load on cylinder 1
|
238840 lb
|
Maximum load on cylinder 2
|
235515 lb
|
Type of fracture pattern of cylinder 1
|
1
|
Type of fracture pattern of cylinder 2
|
1
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Age of specimen
|
21 days
|
DIME Test ID: 2022-08-21-1-5
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617 - Sulfur Mortar Cap
Verified Date: 09/22/2022
Date Tested: 09/17/2022
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test: Tested 9/17/22@800PM
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Cross sectional area of cylinder 1
|
28.27 in^2
|
Cross sectional area of cylinder 2
|
28.27 in^2
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
Compressive strength (to nearest 10 psi)
|
8930 psi
|
Average diameter of cylinder 1
|
6.00 in
|
Average diameter of cylinder 2
|
6.00 in
|
Compressive strength of cylinder 1
|
9053.1 psi
|
Compressive strength of cylinder 2
|
8803.9 psi
|
Maximum load on cylinder 1
|
255930 lb
|
Maximum load on cylinder 2
|
248885 lb
|
Type of fracture pattern of cylinder 1
|
1
|
Type of fracture pattern of cylinder 2
|
2
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Age of specimen
|
28 days
|