Sample Record for 2022-08-05-24
Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project Information
Project ID: 214663 DEA: 081F7304 EFIS: 0815000034
QA Service Level: 1
DIST-CO-RTE-PM: 08-SBD-215-2.7
Work Description: REPLACE CONCRETE BRIDGE, PLACE CONCRETE PCPS GIRDERS AND HMA.
Location Description: SAN BERNARDINO COUNTY IN COLTON AT WASHINGTON STREET OVERCROSSING
Contractor Name: SECURITY PAVING COMPANY, INC.
Contractor Address: 13170 TELFAIR AVE, SYLMAR, CA, 91342
Resident Engineer: Shaine Shahidi Structure Rep.: Unknown
Sample Information
DIME Sample ID: 2022-08-05-24
TL Number from the TL Form:
Sample Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Sample Organization Contact: 213-792-4794
Type of Sample: Quality Control
Type of Material: Concrete
Sample Taken Date: 08/05/2022
Date that the sample was received by the laboratory/organization performing the testing: 08/09/2022
The quantity of what the sample constitutes: 2
A brief description of the sample: 4x8
From where was the sample collected: Job Site
Laboratory sample identification: 1037-805
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Robertsons
Material Information
The concrete mix design number: 1610974
The truck number from where the sample was collected: 10067274
The batch plant ticket number from where the sample was collected: 42029593
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Abutment 1and 3 end diaphrams
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
Test Results
Test 1 of 1
DIME Test ID: 2022-08-05-24-1
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617 - Sulfur Mortar Cap Cured in accordance with ASTM C511
Verified Date: 09/02/2022
Date Tested: 09/02/2022
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Cross sectional area of cylinder 1
|
12.69 in^2
|
Cross sectional area of cylinder 2
|
12.63 in^2
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
Compressive strength (to nearest 10 psi)
|
5440 psi
|
Average diameter of cylinder 1
|
4.02 in
|
Average diameter of cylinder 2
|
4.01 in
|
Compressive strength of cylinder 1
|
5528.0 psi
|
Compressive strength of cylinder 2
|
5356.3 psi
|
Maximum load on cylinder 1
|
70150 lb
|
Maximum load on cylinder 2
|
67650 lb
|
Type of fracture pattern of cylinder 1
|
1
|
Type of fracture pattern of cylinder 2
|
1
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Age of specimen
|
28 days
|