Sample Record for 2022-07-26-2
Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project Information
Project ID: 215456 DEA: 07293604 EFIS: 0713000238
QA Service Level: 1
DIST-CO-RTE-PM: 07-LA-405-14.3/15.8
Work Description: CONSTRUCT AUXILIARY LANE AND WIDEN ON AND OFF RAMPS.
Location Description: LOS ANGELES COUNTY IN TORRANCE BETWEEN WESTERN AVENUE UNDERCROSSING AND WEST 182ND STREET
Contractor Name: ORTIZ ENTERPRISES, INC.
Contractor Address: 6 CUSHING SUITE 200, IRVINE CA 92618
Resident Engineer: Samuel Gallardo Structure Rep.: James Holloway
Sample Information
DIME Sample ID: 2022-07-26-2
TL Number from the TL Form:
Sample Submitted By Organization: CT HQ - QASI Los Angeles Field Office
Sample Organization Contact: (858) 285-5797
Type of Sample: Quality Assurance
Type of Material: SMTL TM5 - Couplers
Sample Taken Date: 07/26/2022
Date that the sample was received by the laboratory/organization performing the testing: 08/01/2022
The quantity of what the sample constitutes: 80
A brief description of the sample: #10 Grip-Twist Couplers
From where was the sample collected: Fabricator
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Ortiz Enterprises Inc.
Material Information
Production or Authorization Testing: Production Testing
Service or Ultimate: Ultimate
Material Standard Code: ASTM A706
Material Grade: 60
Rebar Manufacturer: Cascade Steel
Coupler Manufacturer: BarSplice
Intermediate Assembler or Fabricator:
Rebar Size: #10
Coupler Model: Taper GripTwist
Coating Standards: Uncoated
Shape of Rebar: Straight
Rebar Hoop Diameter:
Rebar Hoop Fabricator:
Coupler Component Heat/Lot Number(s): A214593
Rebar Heat Number(s): 255521
Rebar Size 2 :
Coupler Unique ID:
Test Results
Test 1 of 3
DIME Test ID: 2022-07-26-2-1
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Cyclical/Fatique Tensile with Slip)
Verified Date: 08/02/2022
Date Tested: 08/02/2022
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
|
Number of Samples Tested
|
1
|
| Sample | Number of Cycles | Size | Mfg. Lot Number(s) | Slip (inch) | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | | 1 | | No. 10/32mm | 1 | 0.0003 | 1.27 | 111720 | 87968 | Ok Necking | bewing |
| |
|
UTM
|
2000kip
|
|
Temperature
|
72.00 f
|
|
Halo ID
|
Small
|
Test 2 of 3
DIME Test ID: 2022-07-26-2-2
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Cyclical/Fatique Tensile with Slip)
Verified Date: 08/02/2022
Date Tested: 08/02/2022
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
|
Number of Samples Tested
|
1
|
| Sample | Number of Cycles | Size | Mfg. Lot Number(s) | Slip (inch) | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | | 2 | | No. 10/32mm | 1 | 0 | 1.27 | 113436 | 89319 | Ok Necking | bewing |
| |
|
UTM
|
2000kip
|
|
Temperature
|
72.00 f
|
|
Halo ID
|
|
Test 3 of 3
DIME Test ID: 2022-07-26-2-3
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Cyclical/Fatique Tensile with Slip)
Verified Date: 08/02/2022
Date Tested: 08/02/2022
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
|
Number of Samples Tested
|
1
|
| Sample | Number of Cycles | Size | Mfg. Lot Number(s) | Slip (inch) | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | | 3 | | No. 10/32mm | 1 | 0 | 1.27 | 111221 | 87575 | Ok Necking | bewing |
| |
|
UTM
|
2000kip
|
|
Temperature
|
72.00 f
|
|
Halo ID
|
|