Print Report | Back to Sample Detail

Sample Record for 2022-06-06-20

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 215349 DEA: 081C0824 EFIS: 0816000087 QA Service Level: 1
DIST-CO-RTE-PM: 08-RIV-10-R104.9/R134.2
Work Description: PLACE HMA (TYPE A), JPCP AND IMPORTED BORROW.
Location Description: RIVERSIDE COUNTY FROM ROUTE 10/177 SEPARATION TO 1.1 MILES WEST OF WILEY'S WELL RD OC
Contractor Name: FISHER SAND & GRAVEL CO.
Contractor Address: 1302 W DRIVERS WAY, TEMPE, AZ. 85284
Resident Engineer: Khoi Vu Structure Rep.: Shukri Abouazra

Sample Information

DIME Sample ID: 2022-06-06-20
TL Number from the TL Form: 1
Sample Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Sample Organization Contact: 213-792-4794
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 06/06/2022
Date that the sample was received by the laboratory/organization performing the testing: 06/07/2022
The quantity of what the sample constitutes: 8
A brief description of the sample: 6X12
From where was the sample collected: Job Site
Laboratory sample identification: 1041-06A
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: COFFMAN

Material Information

The concrete mix design number: 2102-2
The truck number from where the sample was collected: 61
The batch plant ticket number from where the sample was collected: 4763
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: CHUTE
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:

Test Results

Test 1 of 4

DIME Test ID: 2022-06-06-20-1
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617 - Sulfur Mortar Cap
Cured in accordance with ASTM C511
Verified Date: 06/13/2022
Date Tested: 06/13/2022
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Cross sectional area of cylinder 1 28.18 in^2
Cross sectional area of cylinder 2 28.18 in^2
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Compressive strength (to nearest 10 psi) 3600 psi
Average diameter of cylinder 1 5.99 in
Average diameter of cylinder 2 5.99 in
Compressive strength of cylinder 1 3496.5 psi
Compressive strength of cylinder 2 3705.3 psi
Maximum load on cylinder 1 98530 lb
Maximum load on cylinder 2 104415 lb
Type of fracture pattern of cylinder 1 2
Type of fracture pattern of cylinder 2 3
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Age of specimen 7 days

Test 2 of 4

DIME Test ID: 2022-06-06-20-2
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617 - Sulfur Mortar Cap
Cured in accordance with ASTM C511
Verified Date: 06/21/2022
Date Tested: 06/20/2022
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Cross sectional area of cylinder 1 28.18 in^2
Cross sectional area of cylinder 2 28.09 in^2
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Compressive strength (to nearest 10 psi) 4500 psi
Average diameter of cylinder 1 5.99 in
Average diameter of cylinder 2 5.98 in
Compressive strength of cylinder 1 4562.5 psi
Compressive strength of cylinder 2 4428.4 psi
Maximum load on cylinder 1 128570 lb
Maximum load on cylinder 2 124395 lb
Type of fracture pattern of cylinder 1 2
Type of fracture pattern of cylinder 2 1
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Age of specimen 14 days

Test 3 of 4

DIME Test ID: 2022-06-06-20-3
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617 - Sulfur Mortar Cap
Cured in accordance with ASTM C511
Verified Date: 07/04/2022
Date Tested: 07/04/2022
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Cross sectional area of cylinder 1 28.18 in^2
Cross sectional area of cylinder 2 28.18 in^2
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Compressive strength (to nearest 10 psi) 4830 psi
Average diameter of cylinder 1 5.99 in
Average diameter of cylinder 2 5.99 in
Compressive strength of cylinder 1 4890.2 psi
Compressive strength of cylinder 2 4760.8 psi
Maximum load on cylinder 1 137805 lb
Maximum load on cylinder 2 134160 lb
Type of fracture pattern of cylinder 1 1
Type of fracture pattern of cylinder 2 1
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Age of specimen 28 days

Test 4 of 4

DIME Test ID: 2022-06-06-20-4
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617 - Sulfur Mortar Cap
Cured in accordance with ASTM C511
Verified Date: 08/29/2022
Date Tested: 07/18/2022
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Cross sectional area of cylinder 1 27.99 in^2
Cross sectional area of cylinder 2 28.09 in^2
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Compressive strength (to nearest 10 psi) 5630 psi
Average diameter of cylinder 1 5.97 in
Average diameter of cylinder 2 5.98 in
Compressive strength of cylinder 1 5467.0 psi
Compressive strength of cylinder 2 5798.9 psi
Maximum load on cylinder 1 153020 lb
Maximum load on cylinder 2 162890 lb
Type of fracture pattern of cylinder 1 1
Type of fracture pattern of cylinder 2 1
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Age of specimen 42 days