Project Information

Project ID: 214337 DEA: 080E33U4 EFIS: 0817000075 QA Service Level: 1
DIST-CO-RTE-PM: 08-SBD-115-R7.3/R10.0
Work Description: ADD WB AUX & EB DECEL LANES, WIDEN I15 SW CONNECT,RAMPS/BRDG
Location Description: SAN BERNARDINO COUNTY IN ONTARIO FROM 0.2 MILE WEST OF CUCAMONGA CREEK BRIDGE TO MILLIKEN AVENUE
Contractor Name: Ames Construction
Contractor Address: 391 North Main Street, Suite 302, Corona, CA 92880
Resident Engineer: Denise Sostrom Structure Rep.: Matt Bruce

Sample Information

DIME Sample ID: 2022-05-02-37
TL Number from the TL Form: 1040-52
Sample Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Sample Organization Contact: 213-792-4794
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 05/02/2022
Date that the sample was received by the laboratory/organization performing the testing: 05/27/2022
The quantity of what the sample constitutes: 6 cylinder
A brief description of the sample: 4x8 cylinder
From where was the sample collected: Job Site
Laboratory sample identification: 1040-52
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Boral

Material Information

The concrete mix design number: RRM18161
The truck number from where the sample was collected: 2237
The batch plant ticket number from where the sample was collected: 6387865
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Abutments and Wingwalls
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:

Test Results

Test 1 of 2

DIME Test ID: 2022-05-02-37-1
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617 - Sulfur Mortar Cap
Cured in accordance with ASTM C511
Verified Date: 05/31/2022
Date Tested: 05/31/2022
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Cross sectional area of cylinder 1 12.69 in^2
Cross sectional area of cylinder 2 12.69 in^2
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Compressive strength (to nearest 10 psi) 4610 psi
Average diameter of cylinder 1 4.02 in
Average diameter of cylinder 2 4.02 in
Compressive strength of cylinder 1 4593.4 psi
Compressive strength of cylinder 2 4624.5 psi
Maximum load on cylinder 1 58290 lb
Maximum load on cylinder 2 58685 lb
Type of fracture pattern of cylinder 1 2
Type of fracture pattern of cylinder 2 2
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Age of specimen 28 days

Test 2 of 2

DIME Test ID: 2022-05-02-37-2
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617 - Sulfur Mortar Cap
Cured in accordance with ASTM C511
Verified Date: 06/13/2022
Date Tested: 06/13/2022
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Cross sectional area of cylinder 1 12.63 in^2
Cross sectional area of cylinder 2 12.69 in^2
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Compressive strength (to nearest 10 psi) 4730 psi
Average diameter of cylinder 1 4.01 in
Average diameter of cylinder 2 4.02 in
Compressive strength of cylinder 1 4740.3 psi
Compressive strength of cylinder 2 4728.9 psi
Maximum load on cylinder 1 59870 lb
Maximum load on cylinder 2 60010 lb
Type of fracture pattern of cylinder 1 3
Type of fracture pattern of cylinder 2 1
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Age of specimen 42 days