Print Report | Back to Sample Detail

Sample Record for 2022-04-14-7

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 214579 DEA: 010B0904 EFIS: 0100020444 QA Service Level: 1
DIST-CO-RTE-PM: 01-DN-101-8.2/8.7
Work Description: Panther Creek & Hunter Creek Bridges
Location Description: DEL NORTE COUNTY NEAR KLAMATH AT PANTHER CREEK BRIDGE AND AT HUNTER CREEK BRIDGE
Contractor Name: Golden State Bridge, Inc
Contractor Address: 3701 Mallard Dr., Benicia, CA 94510
Resident Engineer: Ryan Dunne Structure Rep.: Brian Cinkutis

Sample Information

DIME Sample ID: 2022-04-14-7
TL Number from the TL Form:
Sample Submitted By Organization: CT HQ - QASI Bay Area Field Office
Sample Organization Contact: (916) 284-6784
Type of Sample: Quality Assurance
Type of Material: SMTL TM5 - Couplers
Sample Taken Date: 04/14/2022
Date that the sample was received by the laboratory/organization performing the testing: 04/18/2022
The quantity of what the sample constitutes: 30 pieces
A brief description of the sample: #6 dayton 101/101A couplers
From where was the sample collected: Fabricator
Laboratory sample identification:
Structure unique identifier:
Structure name: Panther Creek
The fabricator/manufacturer/facility name: PJ's rebar

Material Information

Production or Authorization Testing: Production Testing
Service or Ultimate: Service
Material Standard Code: ASTM A706
Material Grade: 60
Rebar Manufacturer: Nucor
Coupler Manufacturer: Dayton
Intermediate Assembler or Fabricator: PJs Rebar
Rebar Size: #6
Coupler Model: D101/101A
Coating Standards: Uncoated
Shape of Rebar: Straight
Rebar Hoop Diameter:
Rebar Hoop Fabricator:
Coupler Component Heat/Lot Number(s): N/aNucor
Rebar Heat Number(s): 3500022246
Rebar Size 2 : 6
Coupler Unique ID:

Test Results

Test 1 of 3

DIME Test ID: 2022-04-14-7-1
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Cyclical/Fatique Tensile with Slip)
Verified Date: 04/21/2022
Date Tested: 04/21/2022
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
Number of Samples Tested 1
SampleNumber of CyclesSizeMfg. Lot Number(s)Slip (inch)Area (sqin)Peak Load (lbf)Peak Stress (psi)CommentsTested By
1No. 6/19mm10.00030.443934889427Ok Neckingbewing
UTM 400kip
Temperature 72.00 f
Halo ID Small

Test 2 of 3

DIME Test ID: 2022-04-14-7-2
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Cyclical/Fatique Tensile with Slip)
Verified Date: 04/21/2022
Date Tested: 04/21/2022
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
Number of Samples Tested 1
SampleNumber of CyclesSizeMfg. Lot Number(s)Slip (inch)Area (sqin)Peak Load (lbf)Peak Stress (psi)CommentsTested By
2No. 6/19mm100.443938489510Ok Neckingbewing
UTM 400kip
Temperature 72.00 f
Halo ID

Test 3 of 3

DIME Test ID: 2022-04-14-7-3
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Cyclical/Fatique Tensile with Slip)
Verified Date: 04/21/2022
Date Tested: 04/21/2022
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
Number of Samples Tested 1
SampleNumber of CyclesSizeMfg. Lot Number(s)Slip (inch)Area (sqin)Peak Load (lbf)Peak Stress (psi)CommentsTested By
3No. 6/19mm100.443922189138Ok Neckingbewing
UTM 400kip
Temperature 72.00 f
Halo ID