Project Information

Project ID: 215063 DEA: 032F5704 EFIS: 0300020615 QA Service Level: 1
DIST-CO-RTE-PM: 03-PLA-80-46.3/63.5
Work Description: Replace 4 Bridges (OC) on Highway 80 from Crystal Springs to Cisco Grove (Baxter, Drum Forebay)
Location Description:
Contractor Name: Walsh Construction Company II, LLC (Walsh)
Contractor Address: 1390 Willow Pass Road Suite 950, Concord, CA 94520
Resident Engineer: Tad Sampson Structure Rep.: Jimmer Ross

Sample Information

DIME Sample ID: 2021-10-14-22
TL Number from the TL Form:
Sample Submitted By Organization: Kie-Con, Incorporated - Antioch
Sample Organization Contact: (925) 331-7122
Type of Sample: Quality Control
Type of Material: Concrete
Sample Taken Date: 10/14/2021
Date that the sample was received by the laboratory/organization performing the testing: 10/15/2021
The quantity of what the sample constitutes: 25 CY
A brief description of the sample: 4x8 concrete cylinders
From where was the sample collected: Fabricator
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: KIE-CON, INC

Material Information

The concrete mix design number: K5670-100 CPA R4
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: 112340
Concrete batch plant:
The fabricator/manufacturer designation for the sample: 20-111C 10/14/2021
A detailed description of where the material sample was collected: Concrete sample from wheelbarrow
Where the material sample would have been placed if not sampled: Voided Slab
From Lot No.:
Bag Lot No.:

Test Results

Test 1 of 6

DIME Test ID: 2021-10-14-22-1
Test Method: ASTM C1064-17: Standard Test Method for Temperature of Freshly Mixed Hydraulic-Cement Concrete
Verified Date: 10/20/2021
Date Tested: 10/14/2021
Submitted By Organization: Kie-Con, Incorporated - Antioch
Organization Address: 3551 Wilbur Avenue,
Organization City: Antioch
Organization State: CA
Organization Zipcode: 94509
Organization Email: cesar.rodriguez3@kiewit.com
Organization Phone: (925) 302-3654
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Temperature 74 F

Test 2 of 6

DIME Test ID: 2021-10-14-22-2
Test Method: ASTM C143-20: Standard Test Method for Slump of Hydraulic-Cement Concrete
Verified Date: 10/20/2021
Date Tested: 10/14/2021
Submitted By Organization: Kie-Con, Incorporated - Antioch
Organization Address: 3551 Wilbur Avenue,
Organization City: Antioch
Organization State: CA
Organization Zipcode: 94509
Organization Email: cesar.rodriguez3@kiewit.com
Organization Phone: (925) 302-3654
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Slump 9.75 inch

Test 3 of 6

DIME Test ID: 2021-10-14-22-3
Test Method: ASTM C231-17a: Standard Test Method for Air Content of Freshly Mixed Concrete by the Pressure Method
Verified Date: 10/20/2021
Date Tested: 10/14/2021
Submitted By Organization: Kie-Con, Incorporated - Antioch
Organization Address: 3551 Wilbur Avenue,
Organization City: Antioch
Organization State: CA
Organization Zipcode: 94509
Organization Email: cesar.rodriguez3@kiewit.com
Organization Phone: (925) 302-3654
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Air content 6 %

Test 4 of 6

DIME Test ID: 2021-10-14-22-4
Test Method: ASTM C138-17a: Standard Test Method for Density (Unit Weight), Yield, and Air Content (Gravimetric) of Concrete
Verified Date: 10/20/2021
Date Tested: 10/14/2021
Submitted By Organization: Kie-Con, Incorporated - Antioch
Organization Address: 3551 Wilbur Avenue,
Organization City: Antioch
Organization State: CA
Organization Zipcode: 94509
Organization Email: cesar.rodriguez3@kiewit.com
Organization Phone: (925) 302-3654
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Identification of concrete represented by the sample 112340
Volume of the measure 0.25 ft^3
Density of concrete 140.8 lb/ft^3
Yield of concrete no data
Relative yield of the batch no data
Cement content no data
Air content no data

Test 5 of 6

DIME Test ID: 2021-10-14-22-5
Test Method: ASTM C39-18: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 10/20/2021
Date Tested: 10/16/2021
Submitted By Organization: Kie-Con, Incorporated - Antioch
Organization Address: 3551 Wilbur Avenue,
Organization City: Antioch
Organization State: CA
Organization Zipcode: 94509
Organization Email: cesar.rodriguez3@kiewit.com
Organization Phone: (925) 302-3654
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 3
Test performed With no density determined
Average diameter of cylinder 1 4.00 in
Average diameter of cylinder 2 4.00 in
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Average diameter of cylinder 3 4.00 in
Cross sectional area of cylinder 1 12.57 in^2
Cross sectional area of cylinder 2 12.57 in^2
Cross sectional area of cylinder 3 12.57 in^2
Compressive strength (to nearest 10 psi) 5280 psi
Maximum load on cylinder 1 66420 lb
Maximum load on cylinder 2 65850 lb
Maximum load on cylinder 3 66930 lb
Type of fracture pattern of cylinder 1 1
Type of fracture pattern of cylinder 2 1
Type of fracture pattern of cylinder 3 1
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Correction factor for cylinder 3 1
Age of specimen 2 days
Age of specimen in hours no data0 hours

Test 6 of 6

DIME Test ID: 2021-10-14-22-6
Test Method: ASTM C39-18: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 10/20/2021
Date Tested: 10/20/2021
Submitted By Organization: Kie-Con, Incorporated - Antioch
Organization Address: 3551 Wilbur Avenue,
Organization City: Antioch
Organization State: CA
Organization Zipcode: 94509
Organization Email: cesar.rodriguez3@kiewit.com
Organization Phone: (925) 302-3654
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 3
Test performed With no density determined
Average diameter of cylinder 1 4.00 in
Average diameter of cylinder 2 4.00 in
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Average diameter of cylinder 3 4.00 in
Cross sectional area of cylinder 1 12.57 in^2
Cross sectional area of cylinder 2 12.57 in^2
Cross sectional area of cylinder 3 12.57 in^2
Compressive strength (to nearest 10 psi) 5980 psi
Maximum load on cylinder 1 73730 lb
Maximum load on cylinder 2 74070 lb
Maximum load on cylinder 3 77540 lb
Type of fracture pattern of cylinder 1 1
Type of fracture pattern of cylinder 2 1
Type of fracture pattern of cylinder 3 1
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Correction factor for cylinder 3 1
Age of specimen 6 days
Age of specimen in hours no data0 hours