Project Information

Project ID: 209175 DEA: 030F2204 EFIS: 0300000072 QA Service Level: 1
DIST-CO-RTE-PM: 03-ED-50-R30.7/R31.7
Work Description: REPLACE BRIDGE.
Location Description: SLY PARK UNDERCROSSING
Contractor Name: VIKING CONSTRUCTION COMPANY, INC.
Contractor Address: P.O. Box 1508 , Rancho Cordova, CA 95741
Resident Engineer: Jarrett Woodruff Structure Rep.: Brandon Miller

Sample Information

DIME Sample ID: 2014-08-30-3
TL Number from the TL Form:
Sample Submitted By Organization: Viking Construction Company, Incorporated - Rancho Cordova
Sample Organization Contact: (916) 852-5530
Type of Sample: Quality Control
Type of Material: Concrete
Sample Taken Date: 08/30/2014
Date that the sample was received by the laboratory/organization performing the testing: 08/30/2014
The quantity of what the sample constitutes: 1 bag
A brief description of the sample: Unknown
From where was the sample collected: Source
Laboratory sample identification: Unknown
Structure unique identifier: Unknown
Structure name: Unknown
The fabricator/manufacturer/facility name: Folsom Ready Mix

Material Information

The concrete mix design number: SF718AFST0
The truck number from where the sample was collected: Unknown
The batch plant ticket number from where the sample was collected: 1049084
Concrete batch plant: Unknown
The fabricator/manufacturer designation for the sample: Unknown
A detailed description of where the material sample was collected: Folsom Ready Mix Stockpile
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:

Test Results

Test 1 of 6

DIME Test ID: 2014-08-30-3-1
Test Method: ASTM C138-10b: Standard Test Method for Density (Unit Weight), Yield, and Air Content (Gravimetric) of Concrete
Verified Date: 09/17/2014
Date Tested: 08/30/2014
Submitted By Organization: Viking Construction Company, Incorporated - Rancho Cordova
Organization Address: 11315 Sunrise Gold Circle, Suite A,
Organization City: Rancho Cordova
Organization State: CA
Organization Zipcode: 95742
Organization Email: dfishback@vikingbridges.com
Organization Phone: (916) 852-5530
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Identification of concrete represented by the sample Stage 2 Abutment 2 Footing
Volume of the measure 4.015 ft^3
Density of concrete 149.2 lb/ft^3
Yield of concrete no data
Relative yield of the batch no data
Cement content no data
Air content no data

Test 2 of 6

DIME Test ID: 2014-08-30-3-2
Test Method: ASTM C1064-08: Standard Test Method for Temperature of Freshly Mixed Hydraulic-Cement Concrete
Verified Date: 09/17/2014
Date Tested: 08/30/2014
Submitted By Organization: Viking Construction Company, Incorporated - Rancho Cordova
Organization Address: 11315 Sunrise Gold Circle, Suite A,
Organization City: Rancho Cordova
Organization State: CA
Organization Zipcode: 95742
Organization Email: dfishback@vikingbridges.com
Organization Phone: (916) 852-5530
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Temperature 74 F

Test 3 of 6

DIME Test ID: 2014-08-30-3-3
Test Method: ASTM C143-10a: Standard Test Method for Slump of Hydraulic-Cement Concrete
Verified Date: 09/17/2014
Date Tested: 08/30/2014
Submitted By Organization: Viking Construction Company, Incorporated - Rancho Cordova
Organization Address: 11315 Sunrise Gold Circle, Suite A,
Organization City: Rancho Cordova
Organization State: CA
Organization Zipcode: 95742
Organization Email: dfishback@vikingbridges.com
Organization Phone: (916) 852-5530
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Slump 5 inch

Test 4 of 6

DIME Test ID: 2014-08-30-3-4
Test Method: ASTM C231-10: Standard Test Method for Air Content of Freshly Mixed Concrete by the Pressure Method
Verified Date: 09/17/2014
Date Tested: 08/30/2014
Submitted By Organization: Viking Construction Company, Incorporated - Rancho Cordova
Organization Address: 11315 Sunrise Gold Circle, Suite A,
Organization City: Rancho Cordova
Organization State: CA
Organization Zipcode: 95742
Organization Email: dfishback@vikingbridges.com
Organization Phone: (916) 852-5530
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Air content 1.7 %

Test 5 of 6

DIME Test ID: 2014-08-30-3-5
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Cured in accordance with ASTM C511
Verified Date: 09/17/2014
Date Tested: 09/06/2014
Submitted By Organization: Viking Construction Company, Incorporated - Rancho Cordova
Organization Address: 11315 Sunrise Gold Circle, Suite A,
Organization City: Rancho Cordova
Organization State: CA
Organization Zipcode: 95742
Organization Email: dfishback@vikingbridges.com
Organization Phone: (916) 852-5530
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 1
Test performed With no density determined
Capped in accordance with? ASTM C617/CTM521
Compressive strength of cylinder (to nearest 10 psi) 2740 psi
Average diameter of cylinder 1 5.99 in
Maximum load on cylinder 1 77170 lb
Type of fracture pattern of cylinder 1 1
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Age of specimen 7 days

Test 6 of 6

DIME Test ID: 2014-08-30-3-6
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Cured in accordance with ASTM C511
Verified Date: 10/13/2014
Date Tested: 09/27/2014
Submitted By Organization: Viking Construction Company, Incorporated - Rancho Cordova
Organization Address: 11315 Sunrise Gold Circle, Suite A,
Organization City: Rancho Cordova
Organization State: CA
Organization Zipcode: 95742
Organization Email: dfishback@vikingbridges.com
Organization Phone: (916) 852-5530
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 4
Test performed With no density determined
Cross sectional area of cylinder 1 28.17 in^2
Cross sectional area of cylinder 2 28.26 in^2
Cross sectional area of cylinder 3 28.26 in^2
Capped in accordance with? ASTM C617/CTM521
Cross sectional area of cylinder 4 28.07 in^2
Average diameter of cylinder 1 5.99 in
Compressive strength (to nearest 10 psi) 4360 psi
Average diameter of cylinder 2 6.00 in
Average diameter of cylinder 3 6.00 in
Average diameter of cylinder 4 5.98 in
Maximum load on cylinder 1 121940 lb
Maximum load on cylinder 2 121210 lb
Maximum load on cylinder 3 129020 lb
Maximum load on cylinder 4 118870 lb
Type of fracture pattern of cylinder 1 1
Type of fracture pattern of cylinder 2 1
Type of fracture pattern of cylinder 3 1
Type of fracture pattern of cylinder 4 1
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 no data
Correction factor for cylinder 3 no data
Correction factor for cylinder 4 no data
Age of specimen 28 days