Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project ID: 209175 DEA: 030F2204 EFIS: 0300000072
QA Service Level: 1
DIST-CO-RTE-PM: 03-ED-50-R30.7/R31.7
Work Description: REPLACE BRIDGE.
Location Description: SLY PARK UNDERCROSSING
Contractor Name: VIKING CONSTRUCTION COMPANY, INC.
Contractor Address: P.O. Box 1508 , Rancho Cordova, CA 95741
Resident Engineer: Jarrett Woodruff Structure Rep.: Brandon Miller
DIME Sample ID: 2014-07-09-10309354
TL Number from the TL Form:
Sample Submitted By Organization: CT D03 - Sacramento Sanders Structures Construction Field Office
Sample Organization Contact: (916) 505-6839
Type of Sample: Verification
Type of Material: Concrete
Sample Taken Date: 07/09/2014
Date that the sample was received by the laboratory/organization performing the testing:
The quantity of what the sample constitutes: Concrete in wheelbarrow
A brief description of the sample: Concrete in wheelbarrow
From where was the sample collected: Other
Laboratory sample identification:
Structure unique identifier: 25-0042
Structure name: Sly Park Rd UC
The fabricator/manufacturer/facility name: Jobsite
The concrete mix design number: SF718AFST0
The truck number from where the sample was collected: 47
The batch plant ticket number from where the sample was collected: 1045890
Concrete batch plant: 1B
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Discharge from concrete truck into wheelbarrow
Where the material sample would have been placed if not sampled: Stage 1 Abutment 2 Retaining Wall
From Lot No.:
Bag Lot No.:
DIME Test ID: 2014-07-09-10309354-1
Test Method: ASTM C1064-08: Standard Test Method for Temperature of Freshly Mixed Hydraulic-Cement Concrete
Verified Date: 07/23/2014
Date Tested: 07/09/2014
Submitted By Organization: CT D03 - Sacramento Sanders Structures Construction Field Office
Organization Address: 3976 Durock Road, Suite 102,
Organization City: Shingle Springs
Organization State: CA
Organization Zipcode: 95686
Organization Email: brandon.miller@dot.ca.gov
Organization Phone: (530) 821-8266
General Comments for this Test: Last 2 cy were rejected
Test Result Compliance: does not comply
Additional Comments When Verified:
DIME Test ID: 2014-07-09-10309354-2
Test Method: ASTM C231-10: Standard Test Method for Air Content of Freshly Mixed Concrete by the Pressure Method
Verified Date: 07/23/2014
Date Tested: 07/09/2014
Submitted By Organization: CT D03 - Sacramento Sanders Structures Construction Field Office
Organization Address: 3976 Durock Road, Suite 102,
Organization City: Shingle Springs
Organization State: CA
Organization Zipcode: 95686
Organization Email: brandon.miller@dot.ca.gov
Organization Phone: (530) 821-8266
General Comments for this Test:
Test Result Compliance: comply
Additional Comments When Verified:
DIME Test ID: 2014-07-09-10309354-3
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521 Cured in accordance with ASTM C511
Verified Date: 07/23/2014
Date Tested: 07/14/2014
Submitted By Organization: CT D03 - Sacramento Sanders Structures Construction Field Office
Organization Address: 3976 Durock Road, Suite 102,
Organization City: Shingle Springs
Organization State: CA
Organization Zipcode: 95686
Organization Email: brandon.miller@dot.ca.gov
Organization Phone: (530) 821-8266
General Comments for this Test:
Test Result Compliance: does not comply
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
2
|
|
Test performed
|
With no density determined
|
|
Cross sectional area of cylinder 1
|
28.46 in^2
|
|
Cross sectional area of cylinder 2
|
28.46 in^2
|
|
Capped in accordance with?
|
ASTM C617/CTM521
|
|
Compressive strength (to nearest 10 psi)
|
2780 psi
|
|
Average diameter of cylinder 1
|
6.02 in
|
|
Average diameter of cylinder 2
|
6.02 in
|
|
Compressive strength of cylinder 1
|
2815.0 psi
|
|
Compressive strength of cylinder 2
|
2754.1 psi
|
|
Maximum load on cylinder 1
|
80116 lb
|
|
Maximum load on cylinder 2
|
78383 lb
|
|
Type of fracture pattern of cylinder 1
|
1
|
|
Type of fracture pattern of cylinder 2
|
1
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
no data
|
|
Age of specimen
|
5 days
|
DIME Test ID: 2014-07-09-10309354-4
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521 Cured in accordance with ASTM C511
Verified Date: 08/11/2014
Date Tested: 08/06/2014
Submitted By Organization: CT D03 - Sacramento Sanders Structures Construction Field Office
Organization Address: 3976 Durock Road, Suite 102,
Organization City: Shingle Springs
Organization State: CA
Organization Zipcode: 95686
Organization Email: brandon.miller@dot.ca.gov
Organization Phone: (530) 821-8266
General Comments for this Test:
Test Result Compliance: comply
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
2
|
|
Test performed
|
With no density determined
|
|
Cross sectional area of cylinder 1
|
28.46 in^2
|
|
Cross sectional area of cylinder 2
|
28.37 in^2
|
|
Capped in accordance with?
|
ASTM C617/CTM521
|
|
Compressive strength (to nearest 10 psi)
|
5060 psi
|
|
Average diameter of cylinder 1
|
6.02 in
|
|
Average diameter of cylinder 2
|
6.01 in
|
|
Compressive strength of cylinder 1
|
5034.3 psi
|
|
Compressive strength of cylinder 2
|
5083.0 psi
|
|
Maximum load on cylinder 1
|
143275 lb
|
|
Maximum load on cylinder 2
|
144206 lb
|
|
Type of fracture pattern of cylinder 1
|
1
|
|
Type of fracture pattern of cylinder 2
|
1
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
no data
|
|
Age of specimen
|
28 days
|