Project Information

Project ID: 212112 DEA: 080C2514 EFIS: 0816000076 COOP: 081645 QA Service Level: 1
DIST-CO-RTE-PM: 08-SBD-10-0.0/13.2
Work Description: Design-Build of I-10 Corridor Contract 1 - Adding 2 new Express Lanes
Location Description: LA/SBD County Line to PM 13.2 near I-15
Contractor Name: Lane-Security Paving Joint Venture
Contractor Address: 3450 Centre Lake Drive, 1st Floor, Ontario, CA 91761
Resident Engineer: Jose Corona Structure Rep.: Luis Negrete

Sample Information

DIME Sample ID: 2021-02-22-8
TL Number from the TL Form:
Sample Submitted By Organization: Con-Fab California Corporation - Lathrop
Sample Organization Contact: (209) 249-4700
Type of Sample: Quality Control
Type of Material: Concrete
Sample Taken Date: 02/22/2021
Date that the sample was received by the laboratory/organization performing the testing: 02/23/2021
The quantity of what the sample constitutes: 2 6x12 concrete cylinders
A brief description of the sample: 6x12 concrete cylinders
From where was the sample collected: Manufacturer
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Con-Fab California, LLC

Material Information

The concrete mix design number: VER-98LV
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: 3024
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Bed 7, 3rd Truck
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:

Test Results

Test 1 of 1

DIME Test ID: 2021-02-22-8-1
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C1231
Cured in accordance with ASTM C511
Verified Date: 02/23/2021
Date Tested: 02/23/2021
Submitted By Organization: Con-Fab California Corporation - Lathrop
Organization Address: 1910 Lathrop Road,
Organization City: Lathrop
Organization State: CA
Organization Zipcode: 95330
Organization Email: dannyc@confabca.com
Organization Phone: (209) 249-4717
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Cross sectional area of cylinder 1 28.27 in^2
Cross sectional area of cylinder 2 28.27 in^2
Capped in accordance with? ASTM C1231
Compressive strength (to nearest 10 psi) 7240 psi
Average diameter of cylinder 1 6.00 in
Average diameter of cylinder 2 6.00 in
Maximum load on cylinder 1 203400 lb
Maximum load on cylinder 2 206100 lb
Type of fracture pattern of cylinder 1 2
Type of fracture pattern of cylinder 2 2
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Age of specimen 1 days