REPORT OF LABORATORY TESTING |
||||
Resident Engineer: |
Syd Valeh |
Date Reported: |
12/07/2020 |
|
Address: |
TL Number: |
161445 |
||
City: |
||||
Project Name: |
||||
Prime Contractor: Granite North Coast Area Office |
||||
Sample Taken Date: |
11/09/2020 |
Mix Design: |
NWC708SC |
|
Contractor: Unknown |
Location : |
|||
Structure unique identifier: |
||||
Structure name: |
||||
Location of Pour: |
The following testing has been tested in accordance with:
ASTM C39-17a : Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Cured in accordance with ASTM C511
Specimen | Average diameter of cylinder (in) | Cross sectional area of cylinder (in^2) | Maximum load on cylinder (lb) | Compressive strength of cylinder (psi) | Type of fracture pattern of cylinder |
---|---|---|---|---|---|
1 | 5.98 | 28.09 | 176846 | 6297.0 | 1 |
2 | 5.97 | 27.99 | 172101 | 6148.0 | 1 |
DIME Test ID: 2020-11-09-28-1
Number of specimens: 2
Compressive strength (to nearest 10 psi): 6220
Age of specimen: 28 days
Certified By: Mike Mullins
*Subject to final inspection by the Resident Engineer. |
TL- Report of Laboratory Testing