Project ID: 44444 DEA: ASCP EFIS: ASCP
QA Service Level:
DIST-CO-RTE-PM: 59---
Work Description: Special project for submitting Sample information for Asphalt Supplier Certification Program.
Location Description:
Contractor Name: Unknown
Contractor Address: Unknown
Resident Engineer: Unknown Structure Rep.: Unknown
DIME Sample ID: 2020-11-02-17
TL Number from the TL Form: 20-269
Sample Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Sample Organization Contact: (916) 227-7302
Type of Sample: Verification
Type of Material: Asphalt Binder
Sample Taken Date: 11/02/2020
Date that the sample was received by the laboratory/organization performing the testing: 11/11/2020
The quantity of what the sample constitutes: 1 can
A brief description of the sample: received 1 can of PG 70-10
From where was the sample collected: Source
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Holly Frontier Glendale
Performance Grade: PG 70-10
Modified: No
Lot number:
Sublot number:
Tank number:
Time of sample:
HMA Supplier:
Certified Asphalt Supplier:
Multigrade:
Multigrade Type:
Asphalt Binder Mix Number:
DIME Test ID: 2020-11-02-17-1
Test Method: AASHTO T315-16: Standard Method of Test for Determining the Rheological Properties of Asphalt Binder Using a Dynamic Shear Rheometer (DSR) (Dynamic Shear)
Verified Date: 11/13/2020
Date Tested: 11/13/2020
Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Organization Address: 5900 Folsom Boulevard, Room 225,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: guadalupe.magana@dot.ca.gov
Organization Phone: (916) 227-7302
General Comments for this Test: Per 2018 Standards and Specifications
Test Result Compliance: complies
Additional Comments When Verified:
Phase
|
RTFO residue
|
Test Plate Diameter
|
25 mm
|
Test Gap
|
1 mm
|
Test Frequency
|
10.0 rad/s
|
Strain Amplitude
|
10.00 %
|
Stress Amplitude
|
0.362 kPa
|
Phase Angle (δ) (for the 10 cycles)
|
85.8 degree
|
Complex Modulus (G*) (for the 10 measurements)
|
3.618 kPa
|
Test Temperature (Specimen 1)
|
70.0 C
|
Dynamic Shear, G*/sin(δ)
|
3.63 kPa
|
DIME Test ID: 2020-11-02-17-2
Test Method: AASHTO T315-16: Standard Method of Test for Determining the Rheological Properties of Asphalt Binder Using a Dynamic Shear Rheometer (DSR) (Dynamic Shear)
Verified Date: 11/18/2020
Date Tested: 11/18/2020
Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Organization Address: 5900 Folsom Boulevard, Room 225,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: guadalupe.magana@dot.ca.gov
Organization Phone: (916) 227-7302
General Comments for this Test: Per 2018 Standards and Specifications
Test Result Compliance: complies
Additional Comments When Verified:
Phase
|
PAV residue
|
Test Plate Diameter
|
8 mm
|
Test Gap
|
2 mm
|
Test Frequency
|
10.0 rad/s
|
Strain Amplitude
|
1.00 %
|
Stress Amplitude
|
37.400 kPa
|
Phase Angle (δ) (for the 10 cycles)
|
50.2 degree
|
Complex Modulus (G*) (for the 10 measurements)
|
3740.021 kPa
|
Test Temperature (Specimen 1)
|
34.0 C
|
(G*) x sin(δ)=
|
2873 kPa
|
DIME Test ID: 2020-11-02-17-3
Test Method: AASHTO T315-16: Standard Method of Test for Determining the Rheological Properties of Asphalt Binder Using a Dynamic Shear Rheometer (DSR) (Dynamic Shear)
Verified Date: 11/13/2020
Date Tested: 11/13/2020
Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Organization Address: 5900 Folsom Boulevard, Room 225,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: guadalupe.magana@dot.ca.gov
Organization Phone: (916) 227-7302
General Comments for this Test: Per 2018 Standards and Specifications
Test Result Compliance: complies
Additional Comments When Verified:
Phase
|
Original binder
|
Test Plate Diameter
|
25 mm
|
Test Gap
|
1 mm
|
Test Frequency
|
10.0 rad/s
|
Strain Amplitude
|
12.00 %
|
Stress Amplitude
|
0.137 kPa
|
Phase Angle (δ) (for the 10 cycles)
|
88.4 degree
|
Complex Modulus (G*) (for the 10 measurements)
|
1.141 kPa
|
Test Temperature (Specimen 1)
|
70.0 C
|
Dynamic Shear, G*/sin(δ)
|
1.14 kPa
|
DIME Test ID: 2020-11-02-17-4
Test Method: AASHTO T240-17: Standard Method of Test for Effect of Heat and Air on a Moving Film of Asphalt Binder (Rolling Thin-Film Oven Test)
Verified Date: 11/19/2020
Date Tested: 11/13/2020
Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Organization Address: 5900 Folsom Boulevard, Room 225,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: guadalupe.magana@dot.ca.gov
Organization Phone: (916) 227-7302
General Comments for this Test: as per 2018 standard specs
Test Result Compliance: complies
Additional Comments When Verified:
Is mass change based on one or two containers?
|
One
|
Any material loss from containers during heating process/testing?
|
No
|
Mass of empty container #1
|
172.365 grams
|
Mass of container #1 before test (m1i)
|
207.723 grams
|
Mass of container #1 after test (m1f)
|
207.646 grams
|
Average mass change
|
-0.218 percent
|
DIME Test ID: 2020-11-02-17-5
Test Method: AASHTO T51-13: Standard Method of Test for Ductility of Asphalt Materials (Asphalt Binder)
Verified Date: 11/19/2020
Date Tested: 11/13/2020
Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Organization Address: 5900 Folsom Boulevard, Room 225,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: guadalupe.magana@dot.ca.gov
Organization Phone: (916) 227-7302
General Comments for this Test: as per 2018 standard specs
Test Result Compliance: complies
Additional Comments When Verified:
Is a normal test obtainable?
|
Yes
|
Number of replicates tested
|
One
|
Ductility of test #1 (D1)
|
75 cm
|
Ductility of sample
|
75 cm
|
DIME Test ID: 2020-11-02-17-6
Test Method: AASHTO T313-19: Standard Method of Test for Determining the Flexural Creep Stiffness of Asphalt Binder Using the Bending Beam Rheometer (BBR)
Verified Date: 11/20/2020
Date Tested: 11/19/2020
Submitted By Organization: CT HQ - Sacramento Asphalt Binder Laboratory
Organization Address: 5900 Folsom Boulevard, Room 225,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: guadalupe.magana@dot.ca.gov
Organization Phone: (916) 227-7302
General Comments for this Test: Per 2018 Standards and Specifications
Test Result Compliance: complies
Additional Comments When Verified:
Minimum test bath temperature at 240 s
|
no data
|
Maximum test bath temperature at 240 s
|
no data
|
Time of test load application
|
no data HH:MM:SS
|
File name of test data
|
no data
|
Time beam in bath
|
no data
|
Time test started
|
no data HH:MM:SS
|
Flags issued by software during test
|
no data
|
Correlation coefficient (R²)
|
no data0
|
Regression coefficient a
|
no data
|
Regression coefficient b
|
no data
|
Regression coefficient c
|
no data
|
Load at time 0.0
|
no data0 mN
|
Deflection at time 0.0 s
|
no data0 µm
|
Load at time 0.5 s
|
no data0 mN
|
Deflection at time 0.5 s
|
no data0 µm
|
Load at 60.0 s
|
no data0 mN
|
Beam deflection 60.0 s
|
no data0 µm
|
Measured Stiffness Modulus 60.0 s
|
74.2 mPa
|
Estimated Stiffness Modulus 60.0 s
|
no data
|
Difference between stiffness moduli 60.0 s
|
no data
|
Estimated m-value 60.0 s
|
0.369
|