Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project ID: 215029 DEA: 120Q8504 EFIS: 1217000116
QA Service Level: 1
DIST-CO-RTE-PM: 12-ORA-5-34.5/37.4
Work Description: PLACE POLYESTER CONCRETE ON 3 BRIDGES & REPLACE CONCRETE BARRIERS.
Location Description: ORANGE COUNTY IN ORANGE AND ANAHEIM FROM 0.1 MILE NORTH OF SANTA ANA RIVER BRIDGE TO HARBOR BOULEVARD OVERCROSSING
Contractor Name: PETERSON-CHASE GENERAL ENGINEERING CONSTRUCTION, INC.
Contractor Address: 16351 CONSTRUCTION CIR W, IRVINE CA 92606
Resident Engineer: Kifah Ramadan Structure Rep.: Bijan Ronagh-Langroodi
DIME Sample ID: 2020-10-28-2
TL Number from the TL Form: Sacramento Caltrans lab
Sample Submitted By Organization: Kwik Bond Polymers
Sample Organization Contact: (760) 518-6064
Type of Sample: Quality Control
Type of Material: Polyester
Sample Taken Date: 10/28/2020
Date that the sample was received by the laboratory/organization performing the testing: 10/28/2020
The quantity of what the sample constitutes: 8 tankers
A brief description of the sample: 1 gallon can
From where was the sample collected: Source
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Kwik Bond Polymers and Polynt
DIME Test ID: 2020-10-28-2-1
Test Method: ASTM D2196-Feb15: Standard Test Methods for Rheological Properties of Non-Newtonian Materials by Rotational Viscometer
Verified Date: 11/18/2020
Date Tested: 11/18/2020
Submitted By Organization: CT HQ - Sacramento Concrete Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: spencer.adams@dot.ca.gov
Organization Phone: (916) 227-5716
General Comments for this Test: Accepted Based on Supplier Results.
Test Result Compliance: complies
Additional Comments When Verified:
DIME Test ID: 2020-10-28-2-2
Test Method: ASTM D1475-Nov13: Standard Test Method For Density of Liquid Coatings, Inks, and Related Products
Verified Date: 11/18/2020
Date Tested: 11/18/2020
Submitted By Organization: CT HQ - Sacramento Concrete Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: spencer.adams@dot.ca.gov
Organization Phone: (916) 227-5716
General Comments for this Test: Accepted Based on Supplier Results.
Test Result Compliance: complies
Additional Comments When Verified:
Density Units
|
pounds/gallons
|
Liquid Density (pounds per gallon)
|
9
|
DIME Test ID: 2020-10-28-2-3
Test Method: ASTM D638-Dec14: Standard Test Method for Tensile Properties of Plastics
Verified Date: 11/18/2020
Date Tested: 11/18/2020
Submitted By Organization: CT HQ - Sacramento Concrete Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: spencer.adams@dot.ca.gov
Organization Phone: (916) 227-5716
General Comments for this Test: Accepted Based on Supplier Results.
Test Result Compliance: complies
Additional Comments When Verified:
Number of specimens tested
|
6
|
Conditioning procedure
|
18/25/50+5/70
|
Speed of testing
|
0.45 in/min
|
Sample 1 Width
|
0.487 in
|
Sample 1 Ultimate strength
|
2957 psi
|
Sample 1 Thickness
|
0.253 in
|
Sample 1 Area
|
0.1232 in^2
|
Sample 1 Ultimate Strength Actual
|
364.3 lbs
|
Sample 1 percent elongation
|
58.32 %
|
Sample 1 Time
|
no data0 MM:SS
|
Sample 2 Width
|
0.487 in
|
Sample 2 Thickness
|
0.253 in
|
Sample 2 Area
|
0.1232 in^2
|
Sample 2 Ultimate strength
|
3030.8 psi
|
Sample 2 Ultimate Strength Actual
|
373.4 lbs
|
Sample 2 percent elongation
|
63.53 %
|
Sample 2 Time
|
no data0 MM:SS
|
Sample 3 Width
|
0.487 in
|
Sample 3 Thickness
|
0.254 in
|
Sample 3 Area
|
0.1237 in^2
|
Sample 3 Ultimate strength
|
3017.8 psi
|
Sample 3 Ultimate Strength Actual
|
373.3 lbs
|
Sample 3 percent elongation
|
61.69 %
|
Sample 3 Time
|
no data0 MM:SS
|
Sample 4 Width
|
0.488 in
|
Sample 4 Thickness
|
0.26 in
|
Sample 4 Area
|
0.1269 in^2
|
Sample 4 Ultimate strength
|
3274.2 psi
|
Sample 4 Ultimate Strength Actual
|
415.5 lbs
|
Sample 4 percent elongation
|
69.1 %
|
Sample 4 Time
|
no data0 MM:SS
|
Sample 5 Width
|
0.488 in
|
Sample 5 Thickness
|
0.26 in
|
Sample 5 Area
|
0.1269 in^2
|
Sample 5 Ultimate strength
|
3057.5 psi
|
Sample 5 Ultimate Strength Actual
|
388 lbs
|
Sample 5 percent elongation
|
63.61 %
|
Sample 5 Time
|
no data0 MM:SS
|
Sample 6 Width
|
0.487 in
|
Sample 6 Thickness
|
0.26 in
|
Sample 6 Area
|
0.1266 in^2
|
Sample 6 Ultimate strength
|
3142.2 psi
|
Sample 6 Ultimate Strength Actual
|
397.8 lbs
|
Sample 6 percent elongation
|
67.59 %
|
Sample 6 Time
|
no data0 MM:SS
|
Ultimate Strength Average
|
3080 psi
|
Percent Elongation Average
|
64 %
|
DIME Test ID: 2020-10-28-2-4
Test Method: ASTM D2369-Jul10: Standard Test Method for Volatile Content of Coatings
Verified Date: 11/18/2020
Date Tested: 11/18/2020
Submitted By Organization: CT HQ - Sacramento Concrete Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: spencer.adams@dot.ca.gov
Organization Phone: (916) 227-5716
General Comments for this Test: Accepted Based on Supplier Results.
Test Result Compliance: complies
Additional Comments When Verified:
Mean of two volatile content determination
|
45.9
|
DIME Test ID: 2020-10-28-2-5
Test Method: CTM 551-August 2012: Method of Test for Determining Suitability of Materials for Overlayment and Repair of Portland Cement Concrete Pavements and Structures
Verified Date: 11/18/2020
Date Tested: 11/18/2020
Submitted By Organization: CT HQ - Sacramento Concrete Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: spencer.adams@dot.ca.gov
Organization Phone: (916) 227-5716
General Comments for this Test: Accepted Based on Supplier Results.
Test Result Compliance: complies
Additional Comments When Verified:
Curing history for Sample 1
|
24hr
|
Maximum applied load (P) for Sample 1
|
1058.13 lb
|
Span length for Sample 1
|
9 in
|
Break location for Sample 1
|
bond
|
Specimen defects/notes for Sample 1
|
no data
|
Surface type for Sample 1
|
SSD
|
Modulus of rupture (R) for Sample 1
|
529.065 psi
|
Curing history for Sample 2
|
24hr
|
Maximum applied load (P) for Sample 2
|
1429.13 lb
|
Span length for Sample 2
|
9 in
|
Break location for Sample 2
|
bond
|
Specimen defects/notes for Sample 2
|
no data
|
Surface type for Sample 2
|
SSD
|
Modulus of rupture (R) for Sample 2
|
714.565 psi
|
Curing history for Sample 3
|
24hr
|
Maximum applied load (P) for Sample 3
|
1065.67 lb
|
Span length for Sample 3
|
9 in
|
Break location for Sample 3
|
bond
|
Specimen defects/notes for Sample 3
|
no data
|
Surface type for Sample 3
|
SSD
|
Modulus of rupture (R) for Sample 3
|
532.835 psi
|
DIME Test ID: 2020-10-28-2-6
Test Method: SCAQMD 309-91-Feb93: Determination of Static Volatile Emissions
Verified Date: 11/18/2020
Date Tested: 11/18/2020
Submitted By Organization: CT HQ - Sacramento Concrete Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: spencer.adams@dot.ca.gov
Organization Phone: (916) 227-5716
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Diameter of lid
|
155 mm
|
Room Temperature
|
68.1 f
|
Tare weight
|
no data0 grams
|
Initial weight
|
100 grams
|
Weight at 5 minutes
|
99.9 grams
|
Weight at 10 minutes
|
99.8 grams
|
Weight at 15 minutes
|
99.6 grams
|
Weight at 20 minutes
|
99.6 grams
|
Weight at 25 minutes
|
99.5 grams
|
Weight at 30 minutes
|
99.5 grams
|
Final weight
|
99.5 grams
|
Total weight loss
|
0.5 grams
|
Calculated radius of gallon can lid in cm
|
7.75 cm
|
Lid Factor
|
52.996 m^2
|
Volatile emission
|
26.498 grams/m^2
|