Sample Record for 2020-04-22-2
Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project Information
Project ID: 214923 DEA: 081L7104 EFIS: 0820000141
QA Service Level: 1
DIST-CO-RTE-PM: 08-RIV-91-10.29
Work Description: Bridge Repair
Location Description:
Contractor Name: Luis Negrete
Contractor Address: 1820 ALHAMBRA BLVD., SACRAMENTO, CA 95816
Resident Engineer: Xavier Avila Structure Rep.: Luis Negrete
Sample Information
DIME Sample ID: 2020-04-22-2
TL Number from the TL Form:
Sample Submitted By Organization: CT HQ - QASI Los Angeles Field Office
Sample Organization Contact: (858) 285-5797
Type of Sample: Quality Assurance
Type of Material: SMTL TM5 - Couplers
Sample Taken Date: 04/22/2020
Date that the sample was received by the laboratory/organization performing the testing: 04/23/2020
The quantity of what the sample constitutes: Lot 1
A brief description of the sample: Mechanical Couplers
From where was the sample collected: Fabricator
Laboratory sample identification:
Structure unique identifier:
Structure name: Buchanan St OC
The fabricator/manufacturer/facility name: Integrity Rebar
Material Information
Production or Authorization Testing: Authorization Testing
Service or Ultimate: Service
Material Standard Code: ASTM A706
Material Grade: 60
Rebar Manufacturer: Casacade
Coupler Manufacturer: BarSplice
Intermediate Assembler or Fabricator: Integrity Rebar
Rebar Size: #5
Coupler Model: Zap Screwlok Type 2
Coating Standards: Uncoated
Shape of Rebar: Straight
Rebar Hoop Diameter: NA
Rebar Hoop Fabricator: NA
Coupler Component Heat/Lot Number(s): A143646 Code EE
Rebar Heat Number(s): 124819
Rebar Size 2 : 5
Coupler Unique ID:
Test Results
Test 1 of 3
DIME Test ID: 2020-04-22-2-1
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Cyclical/Fatique Tensile with Slip)
Verified Date: 04/23/2020
Date Tested: 04/23/2020
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Service Splice
Test Result Compliance:
Additional Comments When Verified:
|
Number of Samples Tested
|
1
|
| Sample | Number of Cycles | Size | Mfg. Lot Number(s) | Slip (inch) | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | | 1 | | No. 5/16mm | 1 | -0.0024 | 0.31 | 27508 | 88735 | Service Splice | bewing |
| |
|
UTM
|
400kip
|
|
Temperature
|
72.00 f
|
|
Halo ID
|
Small
|
Test 2 of 3
DIME Test ID: 2020-04-22-2-2
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Cyclical/Fatique Tensile with Slip)
Verified Date: 04/23/2020
Date Tested: 04/23/2020
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Service Splice
Test Result Compliance:
Additional Comments When Verified:
|
Number of Samples Tested
|
1
|
| Sample | Number of Cycles | Size | Mfg. Lot Number(s) | Slip (inch) | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | | 2 | | No. 5/16mm | 1 | 0 | 0.31 | 29251 | 94357 | Service Splice | bewing |
| |
|
UTM
|
400kip
|
|
Temperature
|
72.00 f
|
|
Halo ID
|
|
Test 3 of 3
DIME Test ID: 2020-04-22-2-3
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Cyclical/Fatique Tensile with Slip)
Verified Date: 04/23/2020
Date Tested: 04/23/2020
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Service Splice
Test Result Compliance:
Additional Comments When Verified:
|
Number of Samples Tested
|
1
|
| Sample | Number of Cycles | Size | Mfg. Lot Number(s) | Slip (inch) | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | | 3 | | No. 5/16mm | 1 | 0 | 0.31 | 29104 | 93884 | Service Splice | bewing |
| |
|
UTM
|
400kip
|
|
Temperature
|
72.00 f
|
|
Halo ID
|
|