Print Report | Back to Sample Detail

Sample Record for 2019-04-29-9

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 210837 DEA: 080J0804 EFIS: 0800000283 COOP: 081625 QA Service Level: 1
DIST-CO-RTE-PM: 08-RIV-15-34.7/51.6
Work Description: (Alternative Delivery) DESIGN-BUILD OF THE INTERSTATE 15 EXPRESS LANES PROJECT
Location Description: Riverside County and SBD-15-0.0/1.3
Contractor Name: Skanska-Ames, Joint Venture
Contractor Address: 1801 California Avenue, Corona, CA 92881
Resident Engineer: Roy Fisher (reports) Structure Rep.: Roy Fisher

Sample Information

DIME Sample ID: 2019-04-29-9
TL Number from the TL Form: 53
Sample Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Sample Organization Contact: 213-792-4794
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 04/29/2019
Date that the sample was received by the laboratory/organization performing the testing: 05/01/2019
The quantity of what the sample constitutes: 6
A brief description of the sample: 6x12 concrete cylinders
From where was the sample collected: Job Site
Laboratory sample identification: 974-53
Structure unique identifier: SARD PIER WALL OF PIER 8
Structure name: SARD PIER WALL OF PIER 8
The fabricator/manufacturer/facility name: ROBERTSON CORONA

Material Information

The concrete mix design number: SC675B38
The truck number from where the sample was collected: 2072
The batch plant ticket number from where the sample was collected: 4455785
Concrete batch plant: Unknown
The fabricator/manufacturer designation for the sample: SKANSKA AMES
A detailed description of where the material sample was collected: 6 cy
Where the material sample would have been placed if not sampled: SARD PIER WALL OF PIER 8
From Lot No.: Unknown
Bag Lot No.: Unknown

Test Results

Test 1 of 2

DIME Test ID: 2019-04-29-9-1
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Cured in accordance with ASTM C511
Verified Date: 05/08/2019
Date Tested: 05/06/2019
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Cross sectional area of cylinder 1 28.37 in^2
Cross sectional area of cylinder 2 28.37 in^2
Capped in accordance with? ASTM C617/CTM521
Compressive strength (to nearest 10 psi) 2920 psi
Average diameter of cylinder 1 6.01 in
Average diameter of cylinder 2 6.01 in
Compressive strength of cylinder 1 2911.5 psi
Compressive strength of cylinder 2 2931.6 psi
Maximum load on cylinder 1 82600 lb
Maximum load on cylinder 2 83170 lb
Type of fracture pattern of cylinder 1 1
Type of fracture pattern of cylinder 2 1
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Age of specimen 7 days

Test 2 of 2

DIME Test ID: 2019-04-29-9-2
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Cured in accordance with ASTM C511
Verified Date: 05/29/2019
Date Tested: 05/28/2019
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Cross sectional area of cylinder 1 28.37 in^2
Cross sectional area of cylinder 2 28.37 in^2
Capped in accordance with? ASTM C617/CTM521
Compressive strength (to nearest 10 psi) 4550 psi
Average diameter of cylinder 1 6.01 in
Average diameter of cylinder 2 6.01 in
Compressive strength of cylinder 1 4631.3 psi
Compressive strength of cylinder 2 4459.6 psi
Maximum load on cylinder 1 131390 lb
Maximum load on cylinder 2 126520 lb
Type of fracture pattern of cylinder 1 1
Type of fracture pattern of cylinder 2 4
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Age of specimen 29 days