Project Information

Project ID: 88888 DEA: SMTL-STOCK EFIS: SMTL-STOCK QA Service Level:
DIST-CO-RTE-PM: 59---
Work Description: Special project for SMTL stock material. Object Code: 1025. J2 DEA: 912680.
Location Description:
Contractor Name: Unknown
Contractor Address: Unknown
Resident Engineer: Unknown Structure Rep.: Unknown

Sample Information

DIME Sample ID: 2018-07-12-4
TL Number from the TL Form: Unknown
Sample Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Sample Organization Contact: (916) 227-7071
Type of Sample: Proficiency
Type of Material: Cementitious
Sample Taken Date: 07/12/2018
Date that the sample was received by the laboratory/organization performing the testing: 07/12/2018
The quantity of what the sample constitutes: 1 Bucket
A brief description of the sample: CCRL 209
From where was the sample collected: Source
Laboratory sample identification: CM188209
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: CCRL

Material Information

Brand: CCRL
Mill: CCRL
Type of Cementitious Material: Type II Cement

Test Results

Test 1 of 12

DIME Test ID: 2018-07-12-4-2
Test Method: ASTM C109-11: Compressive Strength of Hydraulic Cement Mortars (Using 2-in. or [50mm] Cube Specimens)
Verified Date: 02/13/2019
Date Tested: 07/19/2018
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test: 3 Day Break
Test Result Compliance:
Additional Comments When Verified:
Will control cubes be used per ASTM C311? no
Compressive strength of 1st specimen (psi) 3218 psi
Compressive strength of 2nd specimen (psi) 3053 psi
Compressive strength of 3rd specimen (psi) 3133 psi
Average Compressive strength (to nearest 10 psi) 3130 psi

Test 2 of 12

DIME Test ID: 2018-07-12-4-3
Test Method: ASTM C109-11: Compressive Strength of Hydraulic Cement Mortars (Using 2-in. or [50mm] Cube Specimens)
Verified Date: 02/13/2019
Date Tested: 07/23/2018
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test:
Test Result Compliance: not applicable
Additional Comments When Verified:
Will control cubes be used per ASTM C311? no
Compressive strength of 1st specimen (psi) 3773.5 psi
Compressive strength of 2nd specimen (psi) 4020 psi
Compressive strength of 3rd specimen (psi) 4144.75 psi
Average Compressive strength (to nearest 10 psi) 3980 psi

Test 3 of 12

DIME Test ID: 2018-07-12-4-4
Test Method: ASTM C109-11: Compressive Strength of Hydraulic Cement Mortars (Using 2-in. or [50mm] Cube Specimens)
Verified Date: 02/13/2019
Date Tested: 08/13/2018
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test: 28 Day Break
Test Result Compliance:
Additional Comments When Verified:
Will control cubes be used per ASTM C311? no
Compressive strength of 1st specimen (psi) 5233 psi
Compressive strength of 2nd specimen (psi) 5331 psi
Compressive strength of 3rd specimen (psi) 5145 psi
Average Compressive strength (to nearest 10 psi) 5240 psi

Test 4 of 12

DIME Test ID: 2018-07-12-4-5
Test Method: ASTM C151-15: Standard Test Method for Autoclave Expansion of Hydraulic Cement
Verified Date: 02/13/2019
Date Tested: 07/31/2018
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Change in length of specimen(In percent) -0.22 %

Test 5 of 12

DIME Test ID: 2018-07-12-4-6
Test Method: ASTM C185-15a: Standard Test Method for Air Content of Hydraulic Cement Mortar
Verified Date: 02/13/2019
Date Tested: 07/24/2018
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Specific gravity 3.15
Water Content 236
The amount of flow (In percent) 93 %
The amount of water used (In percent) 67.4 %
Net Weight of Sample 834.2 grams
Air Content 8.07 %

Test 6 of 12

DIME Test ID: 2018-07-12-4-7
Test Method: ASTM C187-16: Standard Test Method for Amount of Water Required for Normal Consistency of Hydraulic Cement Paste (Water Normal Consistency)
Verified Date: 02/13/2019
Date Tested: 07/30/2018
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Mass of Water 162 g
Mass of Dry Cement 650 g
Water required for normal consistency 24.9 %

Test 7 of 12

DIME Test ID: 2018-07-12-4-8
Test Method: ASTM C191-13: Standard Test Methods for Time of Setting of Hydraulic Cement by Vicat Needle
Verified Date: 02/13/2019
Date Tested: 07/30/2018
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Type of Water Used Type IV grade reagent water
Initial time of setting 169 min
Final time of setting 240 min

Test 8 of 12

DIME Test ID: 2018-07-12-4-9
Test Method: ASTM C204-11: Standard Test Methods for Fineness of Hydraulic Cement by Air-Permeability Apparatus
Verified Date: 02/13/2019
Date Tested: 07/25/2018
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Method Used Test Method A
Test Time 98 seconds
Fineness 3985 cm^2/g

Test 9 of 12

DIME Test ID: 2018-07-12-4-10
Test Method: ASTM C266-15: Standard Test Method for Time of Setting of Hydraulic-Cement Paste by Gillmore Needles
Verified Date: 02/13/2019
Date Tested: 07/30/2018
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Initial time of setting 195 min
Final time of setting 285 min

Test 10 of 12

DIME Test ID: 2018-07-12-4-11
Test Method: ASTM C430-8: Standard Test Method for Fineness of Hydraulic Cement by the 45-μm (No. 325) Sieve
Verified Date: 02/13/2019
Date Tested: 07/19/2018
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Corrected residue, % (Rc) 3.13 %
Fineness of the cement as the corrected percentage passing the 45 micrometers sieve (No. 325) 96.87 %

Test 11 of 12

DIME Test ID: 2018-07-12-4-12
Test Method: ASTM C451-13: Standard Test Method for Early Stiffening of Hydraulic Cement (Paste Method)
Verified Date: 02/13/2019
Date Tested: 07/26/2018
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Percent final penetration 69 %

Test 12 of 12

DIME Test ID: 2018-07-12-4-13
Test Method: ASTM C1038-14b: Standard Test Method for Expansion of Hydraulic Cement Mortar Bars Stored in Water (Cement Mortar Bars)
Verified Date: 02/13/2019
Date Tested: 07/23/2018
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Specimen A Initial measurement at 24 hours 0.2737 in
Specimen B Initial measurement at 24 hours 0.2662 in
Specimen C Initial measurement at 24 hours 0.2812 in
Specimen D Initial measurement at 24 hours 0.2671 in
Specimen A Final measurement at 14 days 0.2737 in
Specimen B Final measurement at 14 days 0.2662 in
Specimen C Final measurement at 14 days 0.2814 in
Specimen D Final measurement at 14 days 0.2671 in
The average length of change of the four specimens no data0 %