Project ID: 1002668 DEA: 080R42A4 EFIS: 0812000076
QA Service Level: 1
DIST-CO-RTE-PM: 08-SBD--unknown
Work Description: BUILDING MAINTENANCE FACILITY IN THE CITY OF FONTANA ON SE QUADRANT OF SR 210 & I-15 IC
Location Description: 0R42A BUILD MAINTENANCE FACILITY ADJACENT TO SOUTHERN REGIONAL LAB (DESIGN BUILD)
Contractor Name: Exbon Development
Contractor Address: 13831 Newhope St., Garden Grove, CA
Resident Engineer: Alfonso Gonzales Structure Rep.: Oluwatayo Ogeyemi
DIME Sample ID: 2026-10-28-36
TL Number from the TL Form:
Sample Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Sample Organization Contact: 213-792-4794
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 10/28/2026
Date that the sample was received by the laboratory/organization performing the testing: 05/22/2026
The quantity of what the sample constitutes: 9
A brief description of the sample: 4x8 cylinders
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Exbon Development Inc.
The concrete mix design number: 3H40L024
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: 10604874
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Maintenance Facility Adjacent to SRL
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
DIME Test ID: 2026-10-28-36-1
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 11/04/2026
Date Tested: 11/04/2026
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (213) 792-4797
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C1231 - Unbonded Elastomeric Pad Cap
|
|
Apparent mass of submerged cylinder 1
|
no data0 lb
|
|
Average diameter of cylinder 1
|
4.00 in
|
|
Average diameter of cylinder 2
|
4.00 in
|
|
Average diameter of cylinder 3
|
4.00 in
|
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
|
Compressive strength (to nearest 10 psi)
|
2770 psi
|
|
Maximum load on cylinder 1
|
32270 lb
|
|
Maximum load on cylinder 2
|
34320 lb
|
|
Maximum load on cylinder 3
|
37730 lb
|
|
Compressive strength of cylinder 1
|
2570.0 psi
|
|
Type of fracture pattern of cylinder 1
|
3
|
|
Compressive strength of cylinder 2
|
2730.0 psi
|
|
Compressive strength of cylinder 3
|
3000 psi
|
|
Type of fracture pattern of cylinder 2
|
2
|
|
Type of fracture pattern of cylinder 3
|
2
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
7 days
|
|
Age of specimen in hours
|
no data0 hours
|
|
Serial number of delivery ticket, if available
|
no data
|