Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project ID: 1001645 DEA: 051R1004 EFIS: 0523000125
QA Service Level: 1
DIST-CO-RTE-PM: 05-SLO, -1-32.6
Work Description: BRIDGE REPLACEMENT, HMA, AND RSP PROTECTION.
Location Description: SAN LUIS OBISPO COUNTY NEAR MORRO BAY AT TORO CREEK BRIDGE
Contractor Name: SOUZA CONSTRUCTION
Contractor Address: 4027 Santa Fe Road, San Luis Obispo, CA 93403
Resident Engineer: Dean Russu Structure Rep.: Dave Lewis
DIME Sample ID: 2026-09-11-82
TL Number from the TL Form:
Sample Submitted By Organization: CT D05 - Paso Robles Field Laboratory
Sample Organization Contact: 1 (209) 610-9363
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 09/11/2026
Date that the sample was received by the laboratory/organization performing the testing: 09/11/2026
The quantity of what the sample constitutes: 9/11/26 Pour - 752RN1810
A brief description of the sample: 4x8 Cylinders 752RN1810
From where was the sample collected: Job Site
Laboratory sample identification: 260911-1 752RN1810
Structure unique identifier:
Structure name: 9/11/26 Pour
The fabricator/manufacturer/facility name: CalPortland - San Luis Obispo
The concrete mix design number: 752RN1810
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: NA
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Concrete Truck
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
DIME Test ID: 2026-09-11-82-1
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 10/12/2026
Date Tested: 09/18/2026
Submitted By Organization: CT D05 - Paso Robles Field Laboratory
Organization Address: CA,
Organization City: ,
Organization State: CA
Organization Zipcode: 93422
Organization Email: isaac.larey.chezem@dot.ca.gov
Organization Phone: (805) 234-6493
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
1
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C1231 - Unbonded Elastomeric Pad Cap
|
|
Average diameter of cylinder 1
|
4.02 in
|
|
Cross sectional area of cylinder 1
|
12.69 in^2
|
|
Compressive strength of cylinder (to nearest 10 psi)
|
4400 psi
|
|
Maximum load on cylinder 1
|
55821 lb
|
|
Type of fracture pattern of cylinder 1
|
4
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Age of specimen
|
7 days
|
|
Age of specimen in hours
|
no data0 hours
|
DIME Test ID: 2026-09-11-82-2
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 10/12/2026
Date Tested: 09/21/2026
Submitted By Organization: CT D05 - Paso Robles Field Laboratory
Organization Address: CA,
Organization City: ,
Organization State: CA
Organization Zipcode: 93422
Organization Email: isaac.larey.chezem@dot.ca.gov
Organization Phone: (805) 234-6493
General Comments for this Test: 10 Day
Test Result Compliance:
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
1
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C1231 - Unbonded Elastomeric Pad Cap
|
|
Average diameter of cylinder 1
|
4.02 in
|
|
Cross sectional area of cylinder 1
|
12.69 in^2
|
|
Compressive strength of cylinder (to nearest 10 psi)
|
4520 psi
|
|
Maximum load on cylinder 1
|
57376 lb
|
|
Type of fracture pattern of cylinder 1
|
2
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Age of specimen
|
10 days
|
|
Age of specimen in hours
|
no data0 hours
|
DIME Test ID: 2026-09-11-82-3
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 10/12/2026
Date Tested: 10/09/2026
Submitted By Organization: CT D05 - Paso Robles Field Laboratory
Organization Address: CA,
Organization City: ,
Organization State: CA
Organization Zipcode: 93422
Organization Email: isaac.larey.chezem@dot.ca.gov
Organization Phone: (805) 234-6493
General Comments for this Test: 28 Day
Test Result Compliance: complies
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C1231 - Unbonded Elastomeric Pad Cap
|
|
Average diameter of cylinder 1
|
4.00 in
|
|
Average diameter of cylinder 2
|
4.00 in
|
|
Average diameter of cylinder 3
|
4.00 in
|
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
|
Compressive strength (to nearest 10 psi)
|
5550 psi
|
|
Maximum load on cylinder 1
|
68472 lb
|
|
Maximum load on cylinder 2
|
70312 lb
|
|
Maximum load on cylinder 3
|
70423 lb
|
|
Compressive strength of cylinder 1
|
5447.3 psi
|
|
Type of fracture pattern of cylinder 1
|
4
|
|
Compressive strength of cylinder 2
|
5593.6 psi
|
|
Compressive strength of cylinder 3
|
5602.5 psi
|
|
Type of fracture pattern of cylinder 2
|
4
|
|
Type of fracture pattern of cylinder 3
|
4
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
28 days
|
|
Age of specimen in hours
|
no data0 hours
|