Project ID: 211924 DEA: 040G6424 EFIS: 0413000350
QA Service Level: 1
DIST-CO-RTE-PM: 04-MRN-1-001-28.51
Work Description:
Location Description:
Contractor Name: MYERS-DISNEY JV
Contractor Address: 9033 Washington BLVD, Pico Rivera, CA 90660
Resident Engineer: Unknown Structure Rep.: Anthony Tierra
DIME Sample ID: 2026-10-02-25
TL Number from the TL Form:
Sample Submitted By Organization: CT D04 - Petaluma Field Laboratory
Sample Organization Contact: 510-385-7413
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 10/02/2026
Date that the sample was received by the laboratory/organization performing the testing: 10/06/2026
The quantity of what the sample constitutes: 18.50
A brief description of the sample: 9 4x8 concrete cylinders
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier: 27-0024
Structure name: Lagunitas Creek Overflow Bridge
The fabricator/manufacturer/facility name: Bauman Landscape Construction Redi-Mix Concrete
The concrete mix design number: 85350SCC
The truck number from where the sample was collected: BAUMAN_M23
The batch plant ticket number from where the sample was collected: NA
Concrete batch plant:
The fabricator/manufacturer designation for the sample: Bauman Landscape Construction Redi-Mix Concrete
A detailed description of where the material sample was collected: Back of Truck
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
DIME Test ID: 2026-10-02-25-1
Test Method: ASTM C1064-17: Standard Test Method for Temperature of Freshly Mixed Hydraulic-Cement Concrete
Submitted By Organization: CT D04 - Petaluma Field Laboratory
Organization Address: 3401 Regatta Blvd.,
Organization City: Richmond
Organization State: CA
Organization Zipcode: 94804
Organization Email: ignacio.arechiga@dot.ca.gov
Organization Phone: (510) 385-7413
Data has not been verified.
DIME Test ID: 2026-10-02-25-2
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 10/07/2026
Date Tested: 10/07/2026
Submitted By Organization: CT HQ - Vallejo Field Laboratory
Organization Address: 690 Walnut,
Organization City: vallejo
Organization State: CA
Organization Zipcode: 94592
Organization Email: yannick.aranas@dot.ca.gov
Organization Phone: (916) 639-4315
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C1231 - Unbonded Elastomeric Pad Cap
|
|
Average diameter of cylinder 1
|
4.00 in
|
|
Average diameter of cylinder 2
|
4.00 in
|
|
Average diameter of cylinder 3
|
4.00 in
|
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
|
Compressive strength (to nearest 10 psi)
|
4090 psi
|
|
Maximum load on cylinder 1
|
53020 lb
|
|
Maximum load on cylinder 2
|
49768 lb
|
|
Maximum load on cylinder 3
|
51280 lb
|
|
Compressive strength of cylinder 1
|
4218.0 psi
|
|
Type of fracture pattern of cylinder 1
|
3
|
|
Compressive strength of cylinder 2
|
3959.3 psi
|
|
Compressive strength of cylinder 3
|
4079.6 psi
|
|
Type of fracture pattern of cylinder 2
|
2
|
|
Type of fracture pattern of cylinder 3
|
3
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
5 days
|
|
Age of specimen in hours
|
no data0 hours
|
DIME Test ID: 2026-10-02-25-3
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 10/09/2026
Date Tested: 10/09/2026
Submitted By Organization: CT HQ - Vallejo Field Laboratory
Organization Address: 690 Walnut,
Organization City: vallejo
Organization State: CA
Organization Zipcode: 94592
Organization Email: yannick.aranas@dot.ca.gov
Organization Phone: (916) 639-4315
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C1231 - Unbonded Elastomeric Pad Cap
|
|
Average diameter of cylinder 1
|
4.00 in
|
|
Average diameter of cylinder 2
|
4.00 in
|
|
Average diameter of cylinder 3
|
4.00 in
|
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
|
Compressive strength (to nearest 10 psi)
|
4470 psi
|
|
Maximum load on cylinder 1
|
56820 lb
|
|
Maximum load on cylinder 2
|
56300 lb
|
|
Maximum load on cylinder 3
|
55550 lb
|
|
Compressive strength of cylinder 1
|
4520.3 psi
|
|
Type of fracture pattern of cylinder 1
|
3
|
|
Compressive strength of cylinder 2
|
4478.9 psi
|
|
Compressive strength of cylinder 3
|
4419.3 psi
|
|
Type of fracture pattern of cylinder 2
|
3
|
|
Type of fracture pattern of cylinder 3
|
2
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
7 days
|
|
Age of specimen in hours
|
no data0 hours
|