Project ID: 995494 DEA: 081K4904 EFIS: 0819000050
QA Service Level: 1
DIST-CO-RTE-PM: 08-SBD-40-R105.1/R105.9
Work Description: BUILDING WORK, HMA, AND TEMPORARY PORTABLE SANITARY FACILITIES.
Location Description: SAN BERNARDINO COUNTY ABOUT 36 MILES WEST OF NEEDLES FROM 2.1 MILES TO 1.3 MILES WEST OF GOFFS ROAD UNDERCROSSING
Contractor Name: GRANITE CONSTRUCTION COMPANY
Contractor Address: 38000 Monroe Street, Indio, CA 92203
Resident Engineer: Anthony Doan Structure Rep.: Alejandrino Naime
DIME Sample ID: 2026-09-21-37
TL Number from the TL Form:
Sample Submitted By Organization: CT D08 - Barstow Field Laboratory 1
Sample Organization Contact: (760) 252-9216
Type of Sample: Acceptance
Type of Material: Hot Mix Asphalt
Sample Taken Date: 09/21/2026
Date that the sample was received by the laboratory/organization performing the testing: 09/21/2026
The quantity of what the sample constitutes: 363.19
A brief description of the sample: 3/4" RWMA
From where was the sample collected: Manufacturer
Laboratory sample identification: 0572G-26
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Granite Construction
DIME Test ID: 2026-09-21-37-1
Test Method: AASHTO T308-25: Standard Method of Test for Determining the Asphalt Binder Content of Hot Mix Asphalt (HMA) by the Ignition Method (Method A) (Asphalt Binder Content)
Verified Date: 09/28/2026
Date Tested: 09/24/2026
Submitted By Organization: CT D08 - Barstow Field Laboratory 1
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: kaushalkumar.talati@dot.ca.gov
Organization Phone: (951) 840-8328
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
|
What temperature unit is used?
|
Celsius
|
|
Test procedure used?
|
Method A
|
|
Corrected Asphalt Binder Content
|
7.16 %
|
|
Mass of HMA Sample prior to ignition
|
2159 g
|
|
Mass Loss
|
155.9 g
|
|
Correction Factor (Percent by mass of HMA Specimen)
|
-0.01 %
|
|
Moisture Content
|
no data0 %
|
|
Temperature Compensation Factor
|
0.06 %
|
|
Test Temperature
|
538 C
|