Project ID: 1001360 DEA: 09374804 EFIS: 0918000020
QA Service Level: 1
DIST-CO-RTE-PM: 09-INY-395-115.0
Work Description: BUILDING WORK AND PLACE HMA (TYPE A).
Location Description: INYO COUNTY IN BISHOP AT THE DISTRICT OFFICE AT 500 SOUTH MAIN STREET
Contractor Name: BOWE CONTRACTORS INC.
Contractor Address: 609 Bailey Ct, Tehachapi, CA 93561
Resident Engineer: David Carruba Structure Rep.: Alejandrino Naime
DIME Sample ID: 2026-09-04-22
TL Number from the TL Form:
Sample Submitted By Organization: CT D09 - Bishop Field Laboratory
Sample Organization Contact: (760) 872-5211
Type of Sample: Quality Control
Type of Material: Concrete
Sample Taken Date: 09/04/2026
Date that the sample was received by the laboratory/organization performing the testing: 09/07/2026
The quantity of what the sample constitutes: 6 cy
A brief description of the sample: 6 PCC Cylinders 4x8
From where was the sample collected: Job Site
Laboratory sample identification: PCC-06
Structure unique identifier:
Structure name: Lab Slab on Grade
The fabricator/manufacturer/facility name: 7/11 Bishop
The concrete mix design number: 718216A6
The truck number from where the sample was collected: 83989
The batch plant ticket number from where the sample was collected: 984460
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: 6 cy into Truck
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
DIME Test ID: 2026-09-04-22-1
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 10/06/2026
Date Tested: 10/05/2026
Submitted By Organization: CT D09 - Bishop Field Laboratory
Organization Address: 500 South Main Street,
Organization City: Bishop
Organization State: CA
Organization Zipcode: 93514
Organization Email: chris.talbot@dot.ca.gov
Organization Phone: (760) 872-0794
General Comments for this Test: PCC-06
Test Result Compliance: complies
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C1231 - Unbonded Elastomeric Pad Cap
|
|
Average diameter of cylinder 1
|
4.00 in
|
|
Average diameter of cylinder 2
|
4.00 in
|
|
Average diameter of cylinder 3
|
4.00 in
|
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
|
Compressive strength (to nearest 10 psi)
|
4360 psi
|
|
Maximum load on cylinder 1
|
53390 lb
|
|
Maximum load on cylinder 2
|
55710 lb
|
|
Maximum load on cylinder 3
|
55260 lb
|
|
Compressive strength of cylinder 1
|
4247.4 psi
|
|
Type of fracture pattern of cylinder 1
|
1
|
|
Compressive strength of cylinder 2
|
4432.0 psi
|
|
Compressive strength of cylinder 3
|
4396.2 psi
|
|
Type of fracture pattern of cylinder 2
|
1
|
|
Type of fracture pattern of cylinder 3
|
1
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
31 days
|
|
Age of specimen in hours
|
no data0 hours
|