Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project ID: 1001687 DEA: 11430344 EFIS: 1118000104
QA Service Level: 1
DIST-CO-RTE-PM: 11-SD-5,54,94,125-Var
Work Description: CULVERTS RESTORATION, RHMA, JPCP, ISR, BARRIER, LANDSCAPE, ELECTRICAL.
Location Description: SAN DIEGO COUNTY AT VARIOUS LOCATIONS
Contractor Name: GRIFFITH COMPANY
Contractor Address: 13520 Evening Creek Drive, Suite 400, San Diego, CA 92128
Resident Engineer: Sultan Ghazialam Structure Rep.: Unknown
DIME Sample ID: 2026-08-19-64
TL Number from the TL Form:
Sample Submitted By Organization: CT D11 - District 11 Materials Laboratory
Sample Organization Contact: (858) 518-8709
Type of Sample: Quality Assurance
Type of Material: Hot Mix Asphalt
Sample Taken Date: 08/19/2026
Date that the sample was received by the laboratory/organization performing the testing: 07/16/2026
The quantity of what the sample constitutes: 4 boxes
A brief description of the sample: Plant Sample
From where was the sample collected: Supplier
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: MM Lakeside
DIME Test ID: 2026-08-19-64-2
Test Method: AASHTO T308-10: Standard Method of Test for Determining the Asphalt Binder Content of Hot Mix Asphalt (HMA) by the Ignition Method (Method A) (Asphalt Binder Content)
Verified Date: 09/15/2026
Date Tested: 09/10/2026
Submitted By Organization: CT D11 - District 11 Materials Laboratory
Organization Address: 4050 Taylor Street,
Organization City: San Diego
Organization State: CA
Organization Zipcode: 92110
Organization Email: benjamin.haney@dot.ca.gov
Organization Phone: (858) 688-1595
General Comments for this Test: Complies
Test Result Compliance: complies
Additional Comments When Verified:
|
What temperature unit is used?
|
Celsius
|
|
Test procedure used?
|
Method A
|
|
Mass of the specimen basket assembly
|
4027.2 g
|
|
Mass of the specimen and specimen basket assembly prior to ignition
|
6080.7 g
|
|
Mass of HMA Sample prior to ignition
|
2053.5 g
|
|
Corrected Asphalt Binder Content
|
7.23 %
|
|
Mass Loss
|
149.8 g
|
|
Mass of aggregate remaining after ignition
|
1903.7 g
|
|
Correction Factor (Percent by mass of HMA Specimen)
|
0.06 %
|
|
Moisture Content
|
no data0 %
|
|
Temperature Compensation Factor
|
no data0 %
|
|
Test Temperature
|
538 C
|
DIME Test ID: 2026-08-19-64-3
Test Method: AASHTO T209-25: Standard Method of Test for Theoretical Maximum Specific Gravity (Gmm) and Density of Asphalt Mixtures (Maximum Specific Gravity)
Verified Date: 09/11/2026
Date Tested: 09/10/2026
Submitted By Organization: CT D11 - District 11 Materials Laboratory
Organization Address: 4050 Taylor Street,
Organization City: San Diego
Organization State: CA
Organization Zipcode: 92110
Organization Email: benjamin.haney@dot.ca.gov
Organization Phone: (858) 688-1595
General Comments for this Test: N/A - Complies Target 2.449 - Tested 2.431 . Within 0.019
Test Result Compliance: not applicable
Additional Comments When Verified:
|
Number of Samples
|
1
|
|
What is the unit of measurement for theoretical density?
|
US Units
|
|
Mass Determination
|
Air
|
|
Method Performed
|
Mechanical Agitation - Method A
|
|
Mass of container filled with water 1
|
7475.6 grams
|
|
Mass of oven-dry sample in air for Sample 1
|
2555.8 grams
|
|
Mass of container filled with the sample and water for Sample 1
|
8979.9 grams
|
|
Temperature of Water
|
77 °F
|
|
Specific Gravity for Sample 1
|
2.431
|
|
Theoretical maximum density at 25°C (77°F)
|
151.3 lb/ft^3
|
DIME Test ID: 2026-08-19-64-4
Test Method: AASHTO T275-07r12: Standard Method of Test for Bulk Specific Gravity (Gmb) of Compacted Asphalt Mixtures Using Paraffin-Coated Specimens (Bulk Specific Gravity)
Verified Date: 09/11/2026
Date Tested: 09/10/2026
Submitted By Organization: CT D11 - District 11 Materials Laboratory
Organization Address: 4050 Taylor Street,
Organization City: San Diego
Organization State: CA
Organization Zipcode: 92110
Organization Email: benjamin.haney@dot.ca.gov
Organization Phone: (858) 688-1595
General Comments for this Test: Complies Target Gmb from low to high between 0.024 Gmb
Tested Low-2.340 Gmb and High-2.357 Gmb
Test Result Compliance: not applicable
Additional Comments When Verified:
|
Bulk Specific Gravity
|
2.348
|
|
Bulk Specific Gravity 2
|
2.34
|
|
Bulk Specific Gravity 3
|
2.357
|
|
Average Bulk Specific Gravity
|
2.348
|
DIME Test ID: 2026-08-19-64-5
Test Method: AASHTO T269-24E25: Standard Method of Test for Percent Air Voids in Compacted Dense and Open Asphalt Mixtures (Air Void)
Verified Date: 09/11/2026
Date Tested: 09/10/2026
Submitted By Organization: CT D11 - District 11 Materials Laboratory
Organization Address: 4050 Taylor Street,
Organization City: San Diego
Organization State: CA
Organization Zipcode: 92110
Organization Email: benjamin.haney@dot.ca.gov
Organization Phone: (858) 688-1595
General Comments for this Test: Complies Target 4.0% ( +/- 1.5% ) Tested an Avg of 3.4%
Test Result Compliance: complies
Additional Comments When Verified:
|
Percent Air Voids
|
3.4 %
|
|
Percent Air Voids 2
|
3.7 %
|
|
Percent Air Voids 3
|
3 %
|
|
Average Percent Air Voids
|
3.4 %
|
DIME Test ID: 2026-08-19-64-6
Test Method: CTM 389-19: Method of Test for Hamburg Wheel-Track Testing of Compacted Hot Mix Asphalt
Verified Date: 09/17/2026
Date Tested: 09/16/2026
Submitted By Organization: CT D11 - District 11 Materials Laboratory
Organization Address: 4050 Taylor Street,
Organization City: San Diego
Organization State: CA
Organization Zipcode: 92110
Organization Email: benjamin.haney@dot.ca.gov
Organization Phone: (858) 688-1595
General Comments for this Test: Complies Target < 12.7 mm - Tested an Avg of 2.19 mm
Test Result Compliance: complies
Additional Comments When Verified:
|
Specimen Preparation Method
|
PMLC
|
|
Test Temperature
|
122 F
|
|
Air Void Content for specimen A-1
|
6 %
|
|
Air Void Content for specimen A-2
|
6 %
|
|
Air Void Content for specimen B-1
|
6.2 %
|
|
Air Void Content for specimen B-2
|
6.3 %
|
|
Stripping Inflection Point (Wheel A)
|
>20000
|
|
Stripping Inflection Point (Wheel B)
|
>20000
|
|
Maximum impression at 5000 passes (left wheel)
|
1.56 mm
|
|
Maximum impression at 5000 passes (right wheel)
|
1.14 mm
|
|
Average impression at 5000 passes (left/right avg)
|
1.35 mm
|
|
Maximum impression at 10000 passes (left wheel)
|
2.12 mm
|
|
Maximum impression at 10000 passes (right wheel)
|
1.35 mm
|
|
Average impression at 10000 passes (left/right avg)
|
1.74 mm
|
|
Maximum impression at 15000 passes (left wheel)
|
2.38 mm
|
|
Maximum impression at 15000 passes (right wheel)
|
1.53 mm
|
|
Average impression at 15000 passes (left/right avg)
|
1.96 mm
|
|
Maximum impression at 20000 passes (left wheel)
|
2.65 mm
|
|
Maximum impression at 20000 passes (right wheel)
|
1.72 mm
|
|
Average impression at 20000 passes (left/right avg)
|
2.19 mm
|
|
Average impression at 25000 passes (left/right avg)
|
no data
|
DIME Test ID: 2026-08-19-64-8
Test Method: AASHTO T30-19: Standard Method of Test for Mechanical Analysis of Extracted Aggregate (Mechanical Analysis)
Verified Date: 09/15/2026
Date Tested: 09/15/2026
Submitted By Organization: CT D11 - District 11 Materials Laboratory
Organization Address: 4050 Taylor Street,
Organization City: San Diego
Organization State: CA
Organization Zipcode: 92110
Organization Email: benjamin.haney@dot.ca.gov
Organization Phone: (858) 688-1595
General Comments for this Test: Complies per Mix Design 35-11
Page 4
Test Result Compliance: complies
Additional Comments When Verified:
|
Is an aggregate correction factor used?
|
Yes
|
|
Aggregate correction factor for the 2 in. sieve (% passing)
|
no data0 %
|
|
Aggregate correction factor for the 1 1/2 in. sieve (% passing)
|
no data0 %
|
|
Aggregate correction factor for the 1 in. sieve (% passing)
|
no data0 %
|
|
Aggregate correction factor for the 3/4 in. sieve (% passing)
|
-0.7 %
|
|
Aggregate correction factor for the 1/2 in. sieve (% passing)
|
-0.2 %
|
|
Aggregate correction factor for the 3/8 in. sieve (% passing)
|
-0.5 %
|
|
Aggregate correction factor for the #4 sieve (% passing)
|
0.2 %
|
|
Aggregate correction factor for the #8 sieve (% passing)
|
-1.1 %
|
|
Aggregate correction factor for the #16 sieve (% passing)
|
-0.1 %
|
|
Aggregate correction factor for the #30 sieve (% passing)
|
0.1 %
|
|
Aggregate correction factor for the #50 sieve (% passing)
|
0.4 %
|
|
Aggregate correction factor for the #100 sieve (% passing)
|
0.8 %
|
|
Aggregate correction factor for the #200 sieve (% passing)
|
0.9 %
|
|
Cumulative percent passing the 2 in. sieve
|
100 %
|
|
Cumulative percent passing the 1 1/2 in. sieve
|
100 %
|
|
Cumulative percent passing the 1 in. sieve
|
100 %
|
|
Cumulative percent passing the 3/4 in. sieve
|
99 %
|
|
Cumulative percent passing the 1/2 in. sieve
|
85 %
|
|
Cumulative percent passing the 3/8 in. sieve
|
65 %
|
|
Cumulative percent passing the #4 sieve
|
30 %
|
|
Cumulative percent passing the #8 sieve
|
21 %
|
|
Cumulative percent passing the #16 sieve
|
15 %
|
|
Cumulative percent passing the #30 sieve
|
11 %
|
|
Cumulative percent passing the #50 sieve
|
8 %
|
|
Cumulative percent passing the #100 sieve
|
6 %
|
|
Cumulative percent passing the #200 sieve
|
4.4 %
|