Project Information

Project ID: 211924 DEA: 040G6424 EFIS: 0413000350 QA Service Level: 1
DIST-CO-RTE-PM: 04-MRN-1-001-28.51
Work Description:
Location Description:
Contractor Name: MYERS-DISNEY JV
Contractor Address: 9033 Washington BLVD, Pico Rivera, CA 90660
Resident Engineer: Unknown Structure Rep.: Anthony Tierra

Sample Information

DIME Sample ID: 2026-09-04-5
TL Number from the TL Form:
Sample Submitted By Organization: CT D04 - Petaluma Field Laboratory
Sample Organization Contact: 510-385-7413
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 09/04/2026
Date that the sample was received by the laboratory/organization performing the testing: 09/08/2026
The quantity of what the sample constitutes: 15 CY
A brief description of the sample: 9 4x8 concrete cylinders
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier:
Structure name: Lagunitas Creek Overflow Bridge
The fabricator/manufacturer/facility name: Bauman Landscape Construction Redi-Mix Concrete

Material Information

The concrete mix design number: 85350SCC
The truck number from where the sample was collected: BAUMAN_M23
The batch plant ticket number from where the sample was collected: NA
Concrete batch plant:
The fabricator/manufacturer designation for the sample: Bauman Landscape Construction Redi-Mix Concrete
A detailed description of where the material sample was collected: Back of Truck
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:

Test Results

Test

DIME Test ID: 2026-09-04-5-1
Test Method: ASTM C1064-17: Standard Test Method for Temperature of Freshly Mixed Hydraulic-Cement Concrete
Submitted By Organization: CT D04 - Petaluma Field Laboratory
Organization Address: 3401 Regatta Blvd.,
Organization City: Richmond
Organization State: CA
Organization Zipcode: 94804
Organization Email: ignacio.arechiga@dot.ca.gov
Organization Phone: (510) 385-7413
Data has not been verified.

Test

DIME Test ID: 2026-09-04-5-2
Test Method: ASTM C143-15a: Standard Test Method for Slump of Hydraulic-Cement Concrete
Submitted By Organization: CT D04 - Petaluma Field Laboratory
Organization Address: 3401 Regatta Blvd.,
Organization City: Richmond
Organization State: CA
Organization Zipcode: 94804
Organization Email: ignacio.arechiga@dot.ca.gov
Organization Phone: (510) 385-7413
Data has not been verified.

Test

DIME Test ID: 2026-09-04-5-3
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 10/02/2026
Date Tested: 10/02/2026
Submitted By Organization: CT HQ - Vallejo Field Laboratory
Organization Address: 690 Walnut,
Organization City: vallejo
Organization State: CA
Organization Zipcode: 94592
Organization Email: yannick.aranas@dot.ca.gov
Organization Phone: (916) 639-4315
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 3
Test performed With no density determined
Capped in accordance with? ASTM C1231 - Unbonded Elastomeric Pad Cap
Average diameter of cylinder 1 4.00 in
Average diameter of cylinder 2 4.00 in
Average diameter of cylinder 3 4.00 in
Cross sectional area of cylinder 1 12.57 in^2
Cross sectional area of cylinder 2 12.57 in^2
Cross sectional area of cylinder 3 12.57 in^2
Compressive strength (to nearest 10 psi) 5880 psi
Maximum load on cylinder 1 73590 lb
Maximum load on cylinder 2 73220 lb
Maximum load on cylinder 3 74790 lb
Compressive strength of cylinder 1 5854.4 psi
Type of fracture pattern of cylinder 1 3
Compressive strength of cylinder 2 5825.0 psi
Compressive strength of cylinder 3 5949.9 psi
Type of fracture pattern of cylinder 2 2
Type of fracture pattern of cylinder 3 3
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Correction factor for cylinder 3 1
Age of specimen 28 days
Age of specimen in hours no data0 hours

Test

DIME Test ID: 2026-09-04-5-4
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 09/09/2026
Date Tested: 09/09/2026
Submitted By Organization: CT HQ - Vallejo Field Laboratory
Organization Address: 690 Walnut,
Organization City: vallejo
Organization State: CA
Organization Zipcode: 94592
Organization Email: yannick.aranas@dot.ca.gov
Organization Phone: (916) 639-4315
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 3
Test performed With no density determined
Capped in accordance with? ASTM C1231 - Unbonded Elastomeric Pad Cap
Average diameter of cylinder 1 4.00 in
Average diameter of cylinder 2 4.00 in
Average diameter of cylinder 3 4.00 in
Cross sectional area of cylinder 1 12.57 in^2
Cross sectional area of cylinder 2 12.57 in^2
Cross sectional area of cylinder 3 12.57 in^2
Compressive strength (to nearest 10 psi) 3990 psi
Maximum load on cylinder 1 49950 lb
Maximum load on cylinder 2 52160 lb
Maximum load on cylinder 3 48400 lb
Compressive strength of cylinder 1 3973.7 psi
Type of fracture pattern of cylinder 1 3
Compressive strength of cylinder 2 4149.6 psi
Compressive strength of cylinder 3 3850.4 psi
Type of fracture pattern of cylinder 2 2
Type of fracture pattern of cylinder 3 3
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Correction factor for cylinder 3 1
Age of specimen 5 days
Age of specimen in hours no data0 hours

Test

DIME Test ID: 2026-09-04-5-5
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 09/11/2026
Date Tested: 09/11/2026
Submitted By Organization: CT HQ - Vallejo Field Laboratory
Organization Address: 690 Walnut,
Organization City: vallejo
Organization State: CA
Organization Zipcode: 94592
Organization Email: yannick.aranas@dot.ca.gov
Organization Phone: (916) 639-4315
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 3
Test performed With no density determined
Capped in accordance with? ASTM C1231 - Unbonded Elastomeric Pad Cap
Average diameter of cylinder 1 4.00 in
Average diameter of cylinder 2 4.00 in
Average diameter of cylinder 3 4.00 in
Cross sectional area of cylinder 1 12.57 in^2
Cross sectional area of cylinder 2 12.57 in^2
Cross sectional area of cylinder 3 12.57 in^2
Compressive strength (to nearest 10 psi) 4480 psi
Maximum load on cylinder 1 58850 lb
Maximum load on cylinder 2 53740 lb
Maximum load on cylinder 3 56345 lb
Compressive strength of cylinder 1 4681.8 psi
Type of fracture pattern of cylinder 1 2
Compressive strength of cylinder 2 4275.3 psi
Compressive strength of cylinder 3 4482.5 psi
Type of fracture pattern of cylinder 2 5
Type of fracture pattern of cylinder 3 3
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Correction factor for cylinder 3 1
Age of specimen 7 days
Age of specimen in hours no data