Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project ID: 1001616 DEA: 061C0604 EFIS: 0621000014
QA Service Level: 1
DIST-CO-RTE-PM: 06-KER-223-1.8/10.4
Work Description: FULL DEPTH RECYCLE AND V-DITCHES.
Location Description: KERN COUNTY NEAR BAKERSFIELD FROM ROUTE 223/5 SEPARATION TO 0.1 MILE WEST OF ROUTE 223/99 SEPARATION
Contractor Name: Granite Construction Co. (Miguel Duran)
Contractor Address: 3005 JAMES ROAD, BAKERSFIELD CA 93308
Resident Engineer: Samuel Garcia Structure Rep.: None None
DIME Sample ID: 2026-08-13-58
TL Number from the TL Form:
Sample Submitted By Organization: CT D06 - Bakersfield Field Laboratory
Sample Organization Contact: 661-549-8281
Type of Sample: Acceptance
Type of Material: Concrete
Sample Taken Date: 08/13/2026
Date that the sample was received by the laboratory/organization performing the testing: 08/13/2026
The quantity of what the sample constitutes: JPCP-RSC
A brief description of the sample: 6 Beams
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: CTS SHORT LOAD RAPID SET
The concrete mix design number: CTS-65-EHI-JCPC
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: 1
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Back of Truck
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
DIME Test ID: 2026-08-13-58-1
Test Method: ASTM C78-18: Standard Test Method for Flexural Strength of Concrete (Using Simple Beam with Third-Point Loading)
Verified Date: 08/24/2026
Date Tested: 08/24/2026
Submitted By Organization: CT D06 - Bakersfield Field Laboratory
Organization Address: 1824 Norris Road,
Organization City: Bakersfield
Organization State: CA
Organization Zipcode: 93308
Organization Email: kulwinder.rai@dot.ca.gov
Organization Phone: (661) 549-8281
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
|
Number of specimens
|
3
|
|
Unit system used?
|
US Units
|
|
Does the testing machine measure load or stress on the beam specimen?
|
Load
|
|
Fracture initiates in the tension surface
|
Within the Middle Third of the Span Length
|
|
Is a beam dimensional correction factor used?
|
No
|
|
Modulus of rupture
|
655 psi
|
|
Modulus of rupture 2
|
695 psi
|
|
Modulus of rupture 3
|
610 psi
|
|
Modulus of rupture average
|
655 psi
|