Project Information

Project ID: 1001723 DEA: 050N7064 EFIS: 0524000077 QA Service Level: 1
DIST-CO-RTE-PM: 05-SB-101-10.9/12.3
Work Description: SB 101 - Segment 4E North - Cabrillo
Location Description:
Contractor Name: Granite Construction
Contractor Address: P.O. Box. 6744, Santa Barbara, CA
Resident Engineer: Tristan Gebhart Structure Rep.: Josh Madrigal

Sample Information

DIME Sample ID: 2026-07-17-30
TL Number from the TL Form:
Sample Submitted By Organization: CT D05 - Carpinteria Field Laboratory
Sample Organization Contact: (805) 621-3616
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 07/17/2026
Date that the sample was received by the laboratory/organization performing the testing: 07/17/2026
The quantity of what the sample constitutes: 54 CY
A brief description of the sample: CIDH 5000 3/8" .40wc cor
From where was the sample collected: Supplier
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: CEMEX Santa Barbara

Material Information

The concrete mix design number: 1627310
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: 32068059
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Dischard fron concrete truck into wheelbarrow.
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:

Test Results

Test

DIME Test ID: 2026-07-17-30-1
Test Method: ASTM C1064-17: Standard Test Method for Temperature of Freshly Mixed Hydraulic-Cement Concrete
Verified Date: 07/21/2026
Date Tested: 07/17/2026
Submitted By Organization: CT D05 - Carpinteria Field Laboratory
Organization Address: 21 Griffin Road North,
Organization City: Windsor
Organization State: CT
Organization Zipcode: 06095-1590
Organization Email: dlachaine@trccompanies.com
Organization Phone: (805) 621-3616
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Temperature 87 F

Test

DIME Test ID: 2026-07-17-30-2
Test Method: ASTM C143-20: Standard Test Method for Slump of Hydraulic-Cement Concrete
Verified Date: 07/21/2026
Date Tested: 07/17/2026
Submitted By Organization: CT D05 - Carpinteria Field Laboratory
Organization Address: 21 Griffin Road North,
Organization City: Windsor
Organization State: CT
Organization Zipcode: 06095-1590
Organization Email: dlachaine@trccompanies.com
Organization Phone: (805) 621-3616
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Slump 9 inch

Test

DIME Test ID: 2026-07-17-30-3
Test Method: ASTM C39-18: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 08/20/2026
Date Tested: 08/14/2026
Submitted By Organization: CT D05 - Carpinteria Field Laboratory
Organization Address: 21 Griffin Road North,
Organization City: Windsor
Organization State: CT
Organization Zipcode: 06095-1590
Organization Email: dlachaine@trccompanies.com
Organization Phone: (805) 621-3616
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 3
Test performed With no density determined
Average diameter of cylinder 1 4.01 in
Average diameter of cylinder 2 4.01 in
Capped in accordance with? ASTM C1231 - Unbonded Elastomeric Pad Cap
Average diameter of cylinder 3 4.01 in
Cross sectional area of cylinder 1 12.63 in^2
Cross sectional area of cylinder 2 12.63 in^2
Cross sectional area of cylinder 3 12.63 in^2
Compressive strength (to nearest 10 psi) 8780 psi
Maximum load on cylinder 1 111040 lb
Maximum load on cylinder 2 106720 lb
Maximum load on cylinder 3 114900 lb
Compressive strength of cylinder 1 8791.8 psi
Type of fracture pattern of cylinder 1 5
Compressive strength of cylinder 2 8449.7 psi
Compressive strength of cylinder 3 9097.4 psi
Type of fracture pattern of cylinder 2 3
Type of fracture pattern of cylinder 3 3
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Correction factor for cylinder 3 1
Age of specimen 28 days
Age of specimen in hours no data0 hours