Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project ID: 1002087 DEA: 043AA904 EFIS: 0420000066
QA Service Level: 1
DIST-CO-RTE-PM: 04-MRN-131-1.95
Work Description: 3AA90 INSTALL SOLDIER PILE AND LAGGING WALL, AND RECONSTRUCT - Hwy 131 PM 1.95
Location Description:
Contractor Name: Julio Gallardo
Contractor Address: Unknown
Resident Engineer: Andrew Wong Structure Rep.: Unknown
DIME Sample ID: 2026-06-04-146
TL Number from the TL Form:
Sample Submitted By Organization: CT SC - 3672 - Petaluma
Sample Organization Contact: (510) 3939273
Type of Sample: Quality Control
Type of Material: Concrete
Sample Taken Date: 06/04/2026
Date that the sample was received by the laboratory/organization performing the testing: 06/24/2026
The quantity of what the sample constitutes: 9 CY
A brief description of the sample: cement
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Shamrock Materials
The concrete mix design number: D67112E1
The truck number from where the sample was collected: 2464
The batch plant ticket number from where the sample was collected: 1086862
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Back of truck chute
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
DIME Test ID: 2026-06-04-146-1
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C39 - Ground End Cured in accordance with ASTM C511
Verified Date: 07/02/2026
Date Tested: 07/02/2026
Submitted By Organization: CT HQ - Vallejo Field Laboratory
Organization Address: 690 Walnut,
Organization City: vallejo
Organization State: CA
Organization Zipcode: 94592
Organization Email: yannick.aranas@dot.ca.gov
Organization Phone: (916) 639-4315
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
|
Capped in accordance with?
|
ASTM C39 - Ground End
|
|
Compressive strength (to nearest 10 psi)
|
6610 psi
|
|
Average diameter of cylinder 1
|
4.00 in
|
|
Average diameter of cylinder 2
|
4.00 in
|
|
Compressive strength of cylinder 1
|
5929.6 psi
|
|
Compressive strength of cylinder 2
|
5943.9 psi
|
|
Average diameter of cylinder 3
|
4.00 in
|
|
Compressive strength of cylinder 3
|
7943.5 psi
|
|
Maximum load on cylinder 1
|
74535 lb
|
|
Maximum load on cylinder 2
|
74715 lb
|
|
Maximum load on cylinder 3
|
99850 lb
|
|
Type of fracture pattern of cylinder 1
|
3
|
|
Type of fracture pattern of cylinder 2
|
3
|
|
Type of fracture pattern of cylinder 3
|
3
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
28 days
|