Sample Record for 2026-04-28-73

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 1001645 DEA: 051R1004 EFIS: 0523000125 QA Service Level: 1
DIST-CO-RTE-PM: 05-SLO, -1-32.6
Work Description: BRIDGE REPLACEMENT, HMA, AND RSP PROTECTION.
Location Description: SAN LUIS OBISPO COUNTY NEAR MORRO BAY AT TORO CREEK BRIDGE
Contractor Name: SOUZA CONSTRUCTION
Contractor Address: 4027 Santa Fe Road, San Luis Obispo, CA 93403
Resident Engineer: Dean Russu Structure Rep.: Dave Lewis

Sample Information

DIME Sample ID: 2026-04-28-73
TL Number from the TL Form:
Sample Submitted By Organization: CT D05 - Whitley Gardens Field Laboratory
Sample Organization Contact: 805-540-9933
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 04/28/2026
Date that the sample was received by the laboratory/organization performing the testing: 04/29/2026
The quantity of what the sample constitutes: 770RMR3810 Trial Batch
A brief description of the sample: 28 and 42 Day Cylinder Samples
From where was the sample collected: Manufacturer
Laboratory sample identification: 770RMR3810 Trial Batch
Structure unique identifier:
Structure name: Trial Batch
The fabricator/manufacturer/facility name: CalPortland San Luis Obispo

Material Information

The concrete mix design number: 770RMR3810
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: 1
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Mix Truck
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:

Test Results

Test

DIME Test ID: 2026-04-28-73-1
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 06/24/2026
Date Tested: 05/26/2026
Submitted By Organization: CT D05 - Whitley Gardens Field Laboratory
Organization Address: 102 South Whitley Gardens Drive,
Organization City: Paso Robles
Organization State: CA
Organization Zipcode: 93346
Organization Email: kyle.engen@dot.ca.gov
Organization Phone: (805) 540-9933
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 3
Test performed With no density determined
Capped in accordance with? ASTM C1231 - Unbonded Elastomeric Pad Cap
Average diameter of cylinder 1 4.00 in
Average diameter of cylinder 2 4.00 in
Average diameter of cylinder 3 4.00 in
Cross sectional area of cylinder 1 12.57 in^2
Cross sectional area of cylinder 2 12.57 in^2
Cross sectional area of cylinder 3 12.57 in^2
Compressive strength (to nearest 10 psi) 7340 psi
Maximum load on cylinder 1 92024 lb
Maximum load on cylinder 2 93632 lb
Maximum load on cylinder 3 91040 lb
Compressive strength of cylinder 1 7320.9 psi
Type of fracture pattern of cylinder 1 4
Compressive strength of cylinder 2 7448.8 psi
Compressive strength of cylinder 3 7242.6 psi
Type of fracture pattern of cylinder 2 4
Type of fracture pattern of cylinder 3 4
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Correction factor for cylinder 3 1
Age of specimen 28 days
Age of specimen in hours no data0 hours

Test

DIME Test ID: 2026-04-28-73-2
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 06/24/2026
Date Tested: 06/09/2026
Submitted By Organization: CT D05 - Whitley Gardens Field Laboratory
Organization Address: 102 South Whitley Gardens Drive,
Organization City: Paso Robles
Organization State: CA
Organization Zipcode: 93346
Organization Email: kyle.engen@dot.ca.gov
Organization Phone: (805) 540-9933
General Comments for this Test: 42 Day
Test Result Compliance: complies
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 3
Test performed With no density determined
Capped in accordance with? ASTM C1231 - Unbonded Elastomeric Pad Cap
Average diameter of cylinder 1 4.00 in
Average diameter of cylinder 2 4.00 in
Average diameter of cylinder 3 4.00 in
Cross sectional area of cylinder 1 12.57 in^2
Cross sectional area of cylinder 2 12.57 in^2
Cross sectional area of cylinder 3 12.57 in^2
Compressive strength (to nearest 10 psi) 6830 psi
Maximum load on cylinder 1 81252 lb
Maximum load on cylinder 2 79869 lb
Maximum load on cylinder 3 96392 lb
Compressive strength of cylinder 1 6464.0 psi
Type of fracture pattern of cylinder 1 4
Compressive strength of cylinder 2 6353.9 psi
Compressive strength of cylinder 3 7668.4 psi
Type of fracture pattern of cylinder 2 5
Type of fracture pattern of cylinder 3 5
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Correction factor for cylinder 3 1
Age of specimen 42 days
Age of specimen in hours no data0 hours