Project ID: 1001959 DEA: 040V1604 EFIS: 0426000196
QA Service Level: 1
DIST-CO-RTE-PM: 04-ALA-680-20.42/20.45
Work Description: 680/580 Flyover Emergency Joint Replacement
Location Description:
Contractor Name: Golden State Bridge
Contractor Address: 3701 Mallard Drive, Benicia, CA 94510
Resident Engineer: Reza Kamkar Structure Rep.: Unknown
DIME Sample ID: 2026-05-29-30
TL Number from the TL Form:
Sample Submitted By Organization: CT SC - 3674 - Livermore
Sample Organization Contact: (510) 393-1493
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 05/29/2026
Date that the sample was received by the laboratory/organization performing the testing: 06/03/2026
The quantity of what the sample constitutes: 6.76 CY
A brief description of the sample: RSC Bridge Deck Cylinders
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Precision Concrete
The concrete mix design number: 8537-1 TP
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: 1399
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Back of truck chute
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
DIME Test ID: 2026-05-29-30-1
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 06/08/2026
Date Tested: 06/08/2026
Submitted By Organization: CT HQ - Vallejo Field Laboratory
Organization Address: 690 Walnut,
Organization City: vallejo
Organization State: CA
Organization Zipcode: 94592
Organization Email: yannick.aranas@dot.ca.gov
Organization Phone: (916) 639-4315
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C1231 - Unbonded Elastomeric Pad Cap
|
|
Average diameter of cylinder 1
|
4.00 in
|
|
Average diameter of cylinder 2
|
4.00 in
|
|
Average diameter of cylinder 3
|
4.00 in
|
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
|
Compressive strength (to nearest 10 psi)
|
7770 psi
|
|
Maximum load on cylinder 1
|
95715 lb
|
|
Maximum load on cylinder 2
|
100375 lb
|
|
Maximum load on cylinder 3
|
96880 lb
|
|
Compressive strength of cylinder 1
|
7614.6 psi
|
|
Type of fracture pattern of cylinder 1
|
6
|
|
Compressive strength of cylinder 2
|
7985.3 psi
|
|
Compressive strength of cylinder 3
|
7707.2 psi
|
|
Type of fracture pattern of cylinder 2
|
3
|
|
Type of fracture pattern of cylinder 3
|
6
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
10 days
|
|
Age of specimen in hours
|
no data
|