Print Report | Back to Sample Detail

Sample Record for 2026-04-20-32

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 994574 DEA: 050C7334 EFIS: 0518000116 QA Service Level: 1
DIST-CO-RTE-PM: 05-SCR-1-10.5/13.4
Work Description: CONSTRUCT OVERCROSSING AND AUXILIARY LANE/ Replace Capitola Ave OC + RWs and SWs
Location Description: SANTA CRUZ COUNTY IN AND NEAR CITY OF CAPITOLA FROM STATE PARK DRIVE OVERCROSSING TO 0.2 MILE NORTH OF BAY AVENUE UNDERCROSSING
Contractor Name: GRANITE CONSTRUCTION COMPANY
Contractor Address: 580 West Beach Street, Watsonville, CA 95076
Resident Engineer: Fernando Dos Santos Structure Rep.: Jarred Burrows

Sample Information

DIME Sample ID: 2026-04-20-32
TL Number from the TL Form:
Sample Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Sample Organization Contact: (213) 505-4213
Type of Sample: Quality Assurance
Type of Material: SMTL TM5 - Couplers
Sample Taken Date: 04/20/2026
Date that the sample was received by the laboratory/organization performing the testing: 04/29/2026
The quantity of what the sample constitutes: 8
A brief description of the sample: HRC 500/510 Coupler
From where was the sample collected: Manufacturer
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: HRC

Material Information

Production or Authorization Testing: Production Testing
Service or Ultimate: Ultimate
Material Standard Code: ASTM A706
Material Grade: 60
Rebar Manufacturer: Nucor
Coupler Manufacturer: HRC
Intermediate Assembler or Fabricator:
Rebar Size: #11
Coupler Model: HRC 500/510
Coating Standards: Uncoated
Shape of Rebar: Straight
Rebar Hoop Diameter:
Rebar Hoop Fabricator:
Coupler Component Heat/Lot Number(s): 73140308, 74141308
Rebar Heat Number(s): 1202070637
Rebar Size 2 :
Coupler Unique ID: TP-17-03

Test Results

Test

DIME Test ID: 2026-04-20-32-1
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile Slip)
Verified Date: 05/05/2026
Date Tested: 05/05/2026
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: brian.ellis@dot.ca.gov
Organization Phone: (916) 380-8623
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Number of Samples 8
SampleMfg. Lot Number(s)SizeArea (sqin)Slip (inch)Peak Load (lbf)Peak Stress (psi)CommentsTested By
11111.560.00914197091000ok neckingKleinfelder
21111.56000014227091000ok neckingKleinfelder
31111.56000014161091000ok neckingKleinfelder
41111.56000014092090500ok neckingKleinfelder
12111.560.01714137090500ok neckingKleinfelder
22111.56000014256091500ok neckingKleinfelder
32111.56000014121090500ok neckingKleinfelder
42111.56000014181091000ok neckingKleinfelder
Temperature 0 f
UTM NA
Halo ID na