Project ID: 1001573 DEA: 060X2904 EFIS: 0618000050
QA Service Level: 1
DIST-CO-RTE-PM: 06-FRE-33-13.9/16.7
Work Description: HMA (TYPE A), RDWY EXC, CL 2 AB, CURB RAMPS AND MOBILIZATION.
Location Description: FRESNO COUNTY IN AND NEAR COALINGA FROM ENTERPRISE PARKWAY TO LOS GATOS CREEK SOUTH CHANNEL BRIDGE
Contractor Name: Cal Valley Construction, Inc. (Chris Grimm)
Contractor Address: Unknown
Resident Engineer: Din Dadawalla Structure Rep.: Unknown
DIME Sample ID: 2026-04-22-34
TL Number from the TL Form:
Sample Submitted By Organization: CT D06 - Millbrook Field Laboratory
Sample Organization Contact: (559) 341-3953
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 04/22/2026
Date that the sample was received by the laboratory/organization performing the testing: 04/23/2026
The quantity of what the sample constitutes: 9 4x8 Compression Strength Cylinders
A brief description of the sample: Concrete Placed During Shift
From where was the sample collected: Job Site
Laboratory sample identification: 5
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: JJJ Redi-Mix Coalinga
The concrete mix design number: 631000
The truck number from where the sample was collected: J81
The batch plant ticket number from where the sample was collected: 42691
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Location C-42
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
DIME Test ID: 2026-04-22-34-1
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 04/27/2026
Date Tested: 04/27/2026
Submitted By Organization: CT D06 - Millbrook Field Laboratory
Organization Address: 1352 W. Olive Ave,
Organization City: Fresno
Organization State: CA
Organization Zipcode: 93728
Organization Email: tomas.silva@dot.ca.gov
Organization Phone: (559) 341-3953
General Comments for this Test:
Test Result Compliance: does not comply
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
|
Average diameter of cylinder 1
|
3.99 in
|
|
Average diameter of cylinder 2
|
4.00 in
|
|
Average diameter of cylinder 3
|
4.00 in
|
|
Cross sectional area of cylinder 1
|
12.5 in^2
|
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
|
Compressive strength (to nearest 10 psi)
|
3080 psi
|
|
Maximum load on cylinder 1
|
39263 lb
|
|
Maximum load on cylinder 2
|
37947 lb
|
|
Maximum load on cylinder 3
|
38610 lb
|
|
Compressive strength of cylinder 1
|
3141.0 psi
|
|
Type of fracture pattern of cylinder 1
|
3
|
|
Compressive strength of cylinder 2
|
3018.9 psi
|
|
Compressive strength of cylinder 3
|
3071.6 psi
|
|
Type of fracture pattern of cylinder 2
|
6
|
|
Type of fracture pattern of cylinder 3
|
6
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
5 days
|
|
Age of specimen in hours
|
no data0 hours
|
DIME Test ID: 2026-04-22-34-2
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 04/29/2026
Date Tested: 04/29/2026
Submitted By Organization: CT D06 - Millbrook Field Laboratory
Organization Address: 1352 W. Olive Ave,
Organization City: Fresno
Organization State: CA
Organization Zipcode: 93728
Organization Email: tomas.silva@dot.ca.gov
Organization Phone: (559) 341-3953
General Comments for this Test:
Test Result Compliance: does not comply
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C1231 - Unbonded Elastomeric Pad Cap
|
|
Average diameter of cylinder 1
|
4.01 in
|
|
Average diameter of cylinder 2
|
4.00 in
|
|
Average diameter of cylinder 3
|
4.00 in
|
|
Cross sectional area of cylinder 1
|
12.63 in^2
|
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
|
Compressive strength (to nearest 10 psi)
|
3300 psi
|
|
Maximum load on cylinder 1
|
42396 lb
|
|
Maximum load on cylinder 2
|
41302 lb
|
|
Maximum load on cylinder 3
|
40997 lb
|
|
Compressive strength of cylinder 1
|
3356.8 psi
|
|
Type of fracture pattern of cylinder 1
|
2
|
|
Compressive strength of cylinder 2
|
3285.8 psi
|
|
Compressive strength of cylinder 3
|
3261.5 psi
|
|
Type of fracture pattern of cylinder 2
|
6
|
|
Type of fracture pattern of cylinder 3
|
3
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
7 days
|
|
Age of specimen in hours
|
no data0 hours
|
DIME Test ID: 2026-04-22-34-3
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 05/21/2026
Date Tested: 05/20/2026
Submitted By Organization: CT D06 - Millbrook Field Laboratory
Organization Address: 1352 W. Olive Ave,
Organization City: Fresno
Organization State: CA
Organization Zipcode: 93728
Organization Email: tomas.silva@dot.ca.gov
Organization Phone: (559) 341-3953
General Comments for this Test: Required strenght 3600 psi @ 28 days
Test Result Compliance: complies
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C1231 - Unbonded Elastomeric Pad Cap
|
|
Average diameter of cylinder 1
|
4.01 in
|
|
Average diameter of cylinder 2
|
4.01 in
|
|
Average diameter of cylinder 3
|
4.01 in
|
|
Cross sectional area of cylinder 1
|
12.63 in^2
|
|
Cross sectional area of cylinder 2
|
12.63 in^2
|
|
Cross sectional area of cylinder 3
|
12.63 in^2
|
|
Compressive strength (to nearest 10 psi)
|
4640 psi
|
|
Maximum load on cylinder 1
|
57859 lb
|
|
Maximum load on cylinder 2
|
58007 lb
|
|
Maximum load on cylinder 3
|
59844 lb
|
|
Compressive strength of cylinder 1
|
4581.1 psi
|
|
Type of fracture pattern of cylinder 1
|
3
|
|
Compressive strength of cylinder 2
|
4592.8 psi
|
|
Compressive strength of cylinder 3
|
4738.2 psi
|
|
Type of fracture pattern of cylinder 2
|
2
|
|
Type of fracture pattern of cylinder 3
|
3
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
28 days
|
|
Age of specimen in hours
|
no data0 hours
|