Sample Record for 2026-03-27-43

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 1000483 DEA: 120S1404 EFIS: 1219000098 QA Service Level: 1
DIST-CO-RTE-PM: 12-ORA-1-21.5/31.1,32.7
Work Description: INSTALL CONC BARRIER, CURB, HMA PVMT, TRAFFIC STRIPE AND MARKINGS.
Location Description: ORANGE COUNTY IN AND NEAR HUNTINGTON BEACH AND SEAL BEACH FROM SANTA ANA RIVER BRIDGE TO ANDERSON STREET AND AT SEAL BEACH BOULEVARD
Contractor Name: CHUMO CONSTRUCTION, INC.
Contractor Address: Unknown
Resident Engineer: Imad Karam Structure Rep.: Unknown

Sample Information

DIME Sample ID: 2026-03-27-43
TL Number from the TL Form:
Sample Submitted By Organization: CT D12 - Huntington Beach Field Laboratory
Sample Organization Contact: 9492798846
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 03/27/2026
Date that the sample was received by the laboratory/organization performing the testing: 03/30/2026
The quantity of what the sample constitutes: 9
A brief description of the sample: 4x8 concrete cylinders
From where was the sample collected: Job Site
Laboratory sample identification: 26-0047
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Cemex / Irvine

Material Information

The concrete mix design number: 1627309
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: Unknown
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Discharge from concrete truck into wheelbarrow.
Where the material sample would have been placed if not sampled: NOT PROVIDED
From Lot No.:
Bag Lot No.:

Test Results

Test

DIME Test ID: 2026-03-27-43-1
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 04/10/2026
Date Tested: 04/03/2026
Submitted By Organization: CT D12 - Huntington Beach Field Laboratory
Organization Address: 19601 Beach Boulevard,
Organization City: Huntington Beach
Organization State: CA
Organization Zipcode: 92648
Organization Email: frank.mai@dot.ca.gov
Organization Phone: (949) 279-8846
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 3
Test performed With no density determined
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Average diameter of cylinder 1 4.00 in
Average diameter of cylinder 2 4.00 in
Average diameter of cylinder 3 3.99 in
Cross sectional area of cylinder 1 12.57 in^2
Cross sectional area of cylinder 2 12.57 in^2
Cross sectional area of cylinder 3 12.5 in^2
Compressive strength (to nearest 10 psi) 4920 psi
Maximum load on cylinder 1 61830 lb
Maximum load on cylinder 2 63490 lb
Maximum load on cylinder 3 59730 lb
Compressive strength of cylinder 1 4918.9 psi
Type of fracture pattern of cylinder 1 3
Compressive strength of cylinder 2 5050.9 psi
Compressive strength of cylinder 3 4778.4 psi
Type of fracture pattern of cylinder 2 3
Type of fracture pattern of cylinder 3 3
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Correction factor for cylinder 3 1
Age of specimen 7 days
Age of specimen in hours no data0 hours

Test

DIME Test ID: 2026-03-27-43-2
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 04/10/2026
Date Tested: 04/10/2026
Submitted By Organization: CT D12 - Huntington Beach Field Laboratory
Organization Address: 19601 Beach Boulevard,
Organization City: Huntington Beach
Organization State: CA
Organization Zipcode: 92648
Organization Email: frank.mai@dot.ca.gov
Organization Phone: (949) 279-8846
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 3
Test performed With no density determined
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Average diameter of cylinder 1 4.00 in
Average diameter of cylinder 2 4.01 in
Average diameter of cylinder 3 4.00 in
Cross sectional area of cylinder 1 12.57 in^2
Cross sectional area of cylinder 2 12.63 in^2
Cross sectional area of cylinder 3 12.57 in^2
Compressive strength (to nearest 10 psi) 6780 psi
Maximum load on cylinder 1 84340 lb
Maximum load on cylinder 2 84390 lb
Maximum load on cylinder 3 87340 lb
Compressive strength of cylinder 1 6709.6 psi
Type of fracture pattern of cylinder 1 3
Compressive strength of cylinder 2 6681.7 psi
Compressive strength of cylinder 3 6948.3 psi
Type of fracture pattern of cylinder 2 3
Type of fracture pattern of cylinder 3 3
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Correction factor for cylinder 3 1
Age of specimen 14 days
Age of specimen in hours no data0 hours