Sample Record for 2026-03-30-33

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 1000759 DEA: 074X9704 EFIS: 0716000335 QA Service Level: 1
DIST-CO-RTE-PM: 07-LA,-1-42.4
Work Description: CONSTRUCT DRILLED HOLE AND DRILLED HOLE (ROCK SOCKET).
Location Description: LOS ANGELES COUNTY IN MALIBU AT 0.1 MILE SOUTH OF BIG ROCK DRIVE
Contractor Name: BEADOR CONSTRUCTION COMPANY, INC.
Contractor Address: 2900 Bristol Street, Suite D204, Costa Mesa, CA 92626
Resident Engineer: Elizabeth Martinez Structure Rep.: Frank Lotfi

Sample Information

DIME Sample ID: 2026-03-30-33
TL Number from the TL Form: 033026
Sample Submitted By Organization: CT D07 - Materials Field Laboratory, Unit 1953
Sample Organization Contact: (213) 817-0387
Type of Sample: Acceptance
Type of Material: Concrete
Sample Taken Date: 03/30/2026
Date that the sample was received by the laboratory/organization performing the testing: 04/01/2026
The quantity of what the sample constitutes: 130 CY
A brief description of the sample: 4X8 PCC cylinders
From where was the sample collected: Job Site
Laboratory sample identification: 26-073
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Associate Ready Mix

Material Information

The concrete mix design number: SL4KCNIMK
The truck number from where the sample was collected: 1
The batch plant ticket number from where the sample was collected: 67118218
Concrete batch plant: Associated Ready Mix Concrete
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: truck chute
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:

Test Results

Test

DIME Test ID: 2026-03-30-33-1
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 04/06/2026
Date Tested: 04/06/2026
Submitted By Organization: CT D07 - Materials Field Laboratory, Unit 1953
Organization Address: 1940 South Workman Mill Road,
Organization City: Whittier
Organization State: CA
Organization Zipcode: 90601
Organization Email: chad.chotibhongs@dot.ca.gov
Organization Phone: (213) 407-6963
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 3
Test performed With no density determined
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Average diameter of cylinder 1 4.01 in
Average diameter of cylinder 2 4.01 in
Average diameter of cylinder 3 4.01 in
Cross sectional area of cylinder 1 12.63 in^2
Cross sectional area of cylinder 2 12.63 in^2
Cross sectional area of cylinder 3 12.63 in^2
Compressive strength (to nearest 10 psi) 5600 psi
Maximum load on cylinder 1 70667 lb
Maximum load on cylinder 2 72645 lb
Maximum load on cylinder 3 69011 lb
Compressive strength of cylinder 1 5595.2 psi
Type of fracture pattern of cylinder 1 2
Compressive strength of cylinder 2 5751.8 psi
Compressive strength of cylinder 3 5464.1 psi
Type of fracture pattern of cylinder 2 2
Type of fracture pattern of cylinder 3 2
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Correction factor for cylinder 3 1
Age of specimen 7 days
Age of specimen in hours no data0 hours

Test

DIME Test ID: 2026-03-30-33-2
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 04/27/2026
Date Tested: 04/27/2026
Submitted By Organization: CT D07 - Materials Field Laboratory, Unit 1953
Organization Address: 1940 South Workman Mill Road,
Organization City: Whittier
Organization State: CA
Organization Zipcode: 90601
Organization Email: chad.chotibhongs@dot.ca.gov
Organization Phone: (213) 407-6963
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 3
Test performed With no density determined
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Average diameter of cylinder 1 4.01 in
Average diameter of cylinder 2 4.01 in
Average diameter of cylinder 3 4.01 in
Cross sectional area of cylinder 1 12.63 in^2
Cross sectional area of cylinder 2 12.63 in^2
Cross sectional area of cylinder 3 12.63 in^2
Compressive strength (to nearest 10 psi) 8060 psi
Maximum load on cylinder 1 100388 lb
Maximum load on cylinder 2 103902 lb
Maximum load on cylinder 3 101246 lb
Compressive strength of cylinder 1 7948.4 psi
Type of fracture pattern of cylinder 1 2
Compressive strength of cylinder 2 8226.6 psi
Compressive strength of cylinder 3 8016.3 psi
Type of fracture pattern of cylinder 2 2
Type of fracture pattern of cylinder 3 2
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Correction factor for cylinder 3 1
Age of specimen 28 days
Age of specimen in hours no data0 hours