Sample Record for 2026-03-13-31

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 1002051 DEA: 120T4604 EFIS: 1222000053 QA Service Level: 1
DIST-CO-RTE-PM: 12---unknown
Work Description:
Location Description:
Contractor Name: Unknown
Contractor Address: Unknown
Resident Engineer: Unknown Structure Rep.: Unknown

Sample Information

DIME Sample ID: 2026-03-13-31
TL Number from the TL Form:
Sample Submitted By Organization: CT D12 - Huntington Beach Field Laboratory
Sample Organization Contact: 9492798846
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 03/13/2026
Date that the sample was received by the laboratory/organization performing the testing: 03/14/2026
The quantity of what the sample constitutes: 6
A brief description of the sample: 4x8 concrete cylinders
From where was the sample collected: Job Site
Laboratory sample identification: 26-0039
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Unknown

Material Information

The concrete mix design number: 5264125A
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: Unknown
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Discharge from concrete truck into wheelbarrow.
Where the material sample would have been placed if not sampled: SB 55 Edinger Off Ramp
From Lot No.:
Bag Lot No.:

Test Results

Test 1 of 2

DIME Test ID: 2026-03-13-31-1
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 03/30/2026
Date Tested: 03/27/2026
Submitted By Organization: CT D12 - Huntington Beach Field Laboratory
Organization Address: 19601 Beach Boulevard,
Organization City: Huntington Beach
Organization State: CA
Organization Zipcode: 92648
Organization Email: frank.mai@dot.ca.gov
Organization Phone: (949) 279-8846
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 3
Test performed With no density determined
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Average diameter of cylinder 1 4.00 in
Average diameter of cylinder 2 4.00 in
Average diameter of cylinder 3 4.00 in
Cross sectional area of cylinder 1 12.57 in^2
Cross sectional area of cylinder 2 12.57 in^2
Cross sectional area of cylinder 3 12.57 in^2
Compressive strength (to nearest 10 psi) 3930 psi
Maximum load on cylinder 1 50310 lb
Maximum load on cylinder 2 47390 lb
Maximum load on cylinder 3 50380 lb
Compressive strength of cylinder 1 4002.4 psi
Type of fracture pattern of cylinder 1 5
Compressive strength of cylinder 2 3770.1 psi
Compressive strength of cylinder 3 4008 psi
Type of fracture pattern of cylinder 2 5
Type of fracture pattern of cylinder 3 5
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Correction factor for cylinder 3 1
Age of specimen 14 days
Age of specimen in hours no data