Project Information

Project ID: 1002020 DEA: 113B0514 EFIS: 1126000157 QA Service Level: 1
DIST-CO-RTE-PM: 11---unknown
Work Description: EMERGENCY - Repair Damaged Bridge Rail
Location Description:
Contractor Name: Unknown
Contractor Address: Unknown
Resident Engineer: Unknown Structure Rep.: Unknown

Sample Information

DIME Sample ID: 2026-03-19-37
TL Number from the TL Form:
Sample Submitted By Organization: CT D11 - District 11 Materials Laboratory
Sample Organization Contact: (858) 518-8709
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 03/19/2026
Date that the sample was received by the laboratory/organization performing the testing: 03/19/2026
The quantity of what the sample constitutes: Field Sample
A brief description of the sample: Field Sample
From where was the sample collected: Source
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Robertson's

Material Information

The concrete mix design number: RRM 20036
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: 1
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Field Sample
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:

Test Results

Test 1 of 6

DIME Test ID: 2026-03-19-37-1
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 03/26/2026
Date Tested: 03/26/2026
Submitted By Organization: CT D11 - District 11 Materials Laboratory
Organization Address: 4050 Taylor Street,
Organization City: San Diego
Organization State: CA
Organization Zipcode: 92110
Organization Email: benjamin.haney@dot.ca.gov
Organization Phone: (858) 688-1595
General Comments for this Test: 7 Day, complies
Test Result Compliance: complies
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Average diameter of cylinder 1 5.98 in
Average diameter of cylinder 2 5.96 in
Cross sectional area of cylinder 1 28.09 in^2
Cross sectional area of cylinder 2 27.9 in^2
Compressive strength (to nearest 10 psi) 4410 psi
Maximum load on cylinder 1 123645 lb
Maximum load on cylinder 2 123260 lb
Compressive strength of cylinder 1 4401.7 psi
Type of fracture pattern of cylinder 1 1
Compressive strength of cylinder 2 4417.9 psi
Type of fracture pattern of cylinder 2 1
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Age of specimen 7 days
Age of specimen in hours no data0 hours

Test 2 of 6

DIME Test ID: 2026-03-19-37-2
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 04/03/2026
Date Tested: 04/02/2026
Submitted By Organization: CT D11 - District 11 Materials Laboratory
Organization Address: 4050 Taylor Street,
Organization City: San Diego
Organization State: CA
Organization Zipcode: 92110
Organization Email: benjamin.haney@dot.ca.gov
Organization Phone: (858) 688-1595
General Comments for this Test: 14 Day, complies
Test Result Compliance: complies
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Capped in accordance with? ASTM C1231 - Unbonded Elastomeric Pad Cap
Average diameter of cylinder 1 5.98 in
Average diameter of cylinder 2 5.97 in
Cross sectional area of cylinder 1 28.09 in^2
Cross sectional area of cylinder 2 27.99 in^2
Compressive strength (to nearest 10 psi) 4200 psi
Maximum load on cylinder 1 116750 lb
Maximum load on cylinder 2 118505 lb
Compressive strength of cylinder 1 4156.3 psi
Type of fracture pattern of cylinder 1 1
Compressive strength of cylinder 2 4233.8 psi
Type of fracture pattern of cylinder 2 1
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Age of specimen 14 days
Age of specimen in hours no data0 hours

Test 3 of 6

DIME Test ID: 2026-03-19-37-5
Test Method: CTM 557-June 2020: Method of Test for Temperature of Freshly Mixed Hydraulic Cement Concrete
Verified Date: 03/26/2026
Date Tested: 03/19/2026
Submitted By Organization: CT D11 - District 11 Materials Laboratory
Organization Address: 4050 Taylor Street,
Organization City: San Diego
Organization State: CA
Organization Zipcode: 92110
Organization Email: benjamin.haney@dot.ca.gov
Organization Phone: (858) 688-1595
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Temperature 75 F

Test 4 of 6

DIME Test ID: 2026-03-19-37-6
Test Method: CTM 504-June 2010: Method of Test for Determining Air Content of Freshly Mixed Concrete by the Pressure Method
Verified Date: 03/26/2026
Date Tested: 03/19/2026
Submitted By Organization: CT D11 - District 11 Materials Laboratory
Organization Address: 4050 Taylor Street,
Organization City: San Diego
Organization State: CA
Organization Zipcode: 92110
Organization Email: benjamin.haney@dot.ca.gov
Organization Phone: (858) 688-1595
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Air Content 1 %

Test 5 of 6

DIME Test ID: 2026-03-19-37-7
Test Method: CTM 518-June 2010: Method of Test for Unit Weight of Fresh Concrete
Verified Date: 03/26/2026
Date Tested: 03/19/2026
Submitted By Organization: CT D11 - District 11 Materials Laboratory
Organization Address: 4050 Taylor Street,
Organization City: San Diego
Organization State: CA
Organization Zipcode: 92110
Organization Email: benjamin.haney@dot.ca.gov
Organization Phone: (858) 688-1595
General Comments for this Test:
Test Result Compliance: not applicable
Additional Comments When Verified:
Unit weight of the concrete 149.96 lb/ft^3
Cement content 597.5 lb/yd^3

Test 6 of 6

DIME Test ID: 2026-03-19-37-8
Test Method: CTM 556-January 2018: Method of Test for Slump of Fresh Portland Cement Concrete
Verified Date: 03/26/2026
Date Tested: 03/19/2026
Submitted By Organization: CT D11 - District 11 Materials Laboratory
Organization Address: 4050 Taylor Street,
Organization City: San Diego
Organization State: CA
Organization Zipcode: 92110
Organization Email: benjamin.haney@dot.ca.gov
Organization Phone: (858) 688-1595
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Slump 3.75 inch