Project Information

Project ID: 1001375 DEA: 040A53T4 EFIS: 0421000155 COOP: 040A53TCM QA Service Level: 1
DIST-CO-RTE-PM: 04-SOL-80-L1.8/L3.2
Work Description: Construct I-80 WB Truck Scales
Location Description: CONSTRUCTION ON STATE HIGHWAY IN SOLANO COUNTY IN AND NEAR FAIRFIELD ON ROUTE 12 FROM THE 80/12 EAST JUNCTION TO 0.9 MILE EAST OF CHADBOURNE ROAD UNDERCROSSING AND ON ROUTE 80 FROM 0.5 MILE WEST OF DAN WILSON CREEK BRIDGE TO WEST TEXAS STREET UNDERCROSSI
Contractor Name: Kiewit Infrastructure West Co.
Contractor Address: 4650 Business Center Drive, Fairfield, CA 94534
Resident Engineer: Darren Isada Structure Rep.: Nana Budu

Sample Information

DIME Sample ID: 2026-03-16-12
TL Number from the TL Form:
Sample Submitted By Organization: CT HQ - QASI Los Angeles Field Office
Sample Organization Contact: (858) 285-5797
Type of Sample: Quality Assurance
Type of Material: SMTL TM5 - Headed Bars
Sample Taken Date: 03/16/2026
Date that the sample was received by the laboratory/organization performing the testing: 03/19/2026
The quantity of what the sample constitutes: 4
A brief description of the sample: #9 HRC 150 T Heads
From where was the sample collected: Fabricator
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: HRC

Material Information

Production or Authorization Testing: Authorization Testing
Rebar Heat Number(s): 4153326
Head Manufacturer Lot Number(s): C258174
Rebar Size: #9
Headed Bar Model Name: HRC Type 150
Size of Head: Reduced Size - 4x
Head Connection Type:
Head Shape: Circular
Rebar Manufacturer: CMC Steel Arizona
Head Manufacturer: HRC Fountain Valley
Head Fabricator: Nucor Utah
Material Standard Code: ASTM A706
Headed Bar Unique ID: 9FW-17-04

Test Results

Test 1 of 1

DIME Test ID: 2026-03-16-12-1
Test Method: ASTM A970-18: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 03/25/2026
Date Tested: 03/25/2026
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: brian.ellis@dot.ca.gov
Organization Phone: (916) 380-8623
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples 4
Lot #Area (sqin)Peak Load (lbf)Tensile Strength (psi)CommentsTested By
119039090500Ok NeckingKleinfelder
118886089000Ok NeckingKleinfelder
118962089500Ok NeckingKleinfelder
118964089500Ok NeckingKleinfelder
Temperature 0 f
UTM NA