Sample Record for 2026-03-06-1
Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project Information
Project ID: 994901 DEA: 112T3434 EFIS: 1120000081
QA Service Level: 1
DIST-CO-RTE-PM: 11-SD-805-5.1/8.3
Work Description: SOUNDWALLS, WIDEN FREEWAY, STRUCTURES, LANDSCAPE AND ELECTRICAL.
Location Description: SAN DIEGO COUNTY IN CHULA VISTA FROM PALOMAR STREET OVERCROSSING TO 0.5 MILE NORTH OF BONITA ROAD UNDERCROSSING
Contractor Name: WALSH CONSTRUCTION COMPANY II, LLC
Contractor Address: 1260 Corona Pointe Court #201
Resident Engineer: Tan Cao Structure Rep.: Daniela Lopez
Sample Information
DIME Sample ID: 2026-03-06-1
TL Number from the TL Form:
Sample Submitted By Organization: CT D11 - District 11 Materials Laboratory
Sample Organization Contact: (858) 518-8709
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 03/06/2026
Date that the sample was received by the laboratory/organization performing the testing: 03/06/2026
The quantity of what the sample constitutes: Field Sample
A brief description of the sample: Field Sample
From where was the sample collected: Source
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Associated Otay
Material Information
The concrete mix design number: RRM 23117
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: 1
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Field Sample
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
Test Results
Test
DIME Test ID: 2026-03-06-1-5
Test Method: CTM 557-June 2020: Method of Test for Temperature of Freshly Mixed Hydraulic Cement Concrete
Verified Date: 03/09/2026
Date Tested: 03/06/2026
Submitted By Organization: CT D11 - District 11 Materials Laboratory
Organization Address: 4050 Taylor Street,
Organization City: San Diego
Organization State: CA
Organization Zipcode: 92110
Organization Email: benjamin.haney@dot.ca.gov
Organization Phone: (858) 688-1595
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Test
DIME Test ID: 2026-03-06-1-8
Test Method: CTM 556-January 2018: Method of Test for Slump of Fresh Portland Cement Concrete
Verified Date: 03/09/2026
Date Tested: 03/06/2026
Submitted By Organization: CT D11 - District 11 Materials Laboratory
Organization Address: 4050 Taylor Street,
Organization City: San Diego
Organization State: CA
Organization Zipcode: 92110
Organization Email: benjamin.haney@dot.ca.gov
Organization Phone: (858) 688-1595
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Test
DIME Test ID: 2026-03-06-1-7
Test Method: CTM 518-June 2010: Method of Test for Unit Weight of Fresh Concrete
Verified Date: 03/09/2026
Date Tested: 03/06/2026
Submitted By Organization: CT D11 - District 11 Materials Laboratory
Organization Address: 4050 Taylor Street,
Organization City: San Diego
Organization State: CA
Organization Zipcode: 92110
Organization Email: benjamin.haney@dot.ca.gov
Organization Phone: (858) 688-1595
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
|
Unit weight of the concrete
|
149.44 lb/ft^3
|
|
Cement content
|
586 lb/yd^3
|
Test
DIME Test ID: 2026-03-06-1-6
Test Method: CTM 504-June 2010: Method of Test for Determining Air Content of Freshly Mixed Concrete by the Pressure Method
Verified Date: 03/09/2026
Date Tested: 03/06/2026
Submitted By Organization: CT D11 - District 11 Materials Laboratory
Organization Address: 4050 Taylor Street,
Organization City: San Diego
Organization State: CA
Organization Zipcode: 92110
Organization Email: benjamin.haney@dot.ca.gov
Organization Phone: (858) 688-1595
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Test
DIME Test ID: 2026-03-06-1-1
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 03/13/2026
Date Tested: 03/13/2026
Submitted By Organization: CT D11 - District 11 Materials Laboratory
Organization Address: 4050 Taylor Street,
Organization City: San Diego
Organization State: CA
Organization Zipcode: 92110
Organization Email: benjamin.haney@dot.ca.gov
Organization Phone: (858) 688-1595
General Comments for this Test: 7 Day
Test Result Compliance: does not comply
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
2
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
|
Average diameter of cylinder 1
|
5.97 in
|
|
Average diameter of cylinder 2
|
5.98 in
|
|
Cross sectional area of cylinder 1
|
27.99 in^2
|
|
Cross sectional area of cylinder 2
|
28.09 in^2
|
|
Compressive strength (to nearest 10 psi)
|
3460 psi
|
|
Maximum load on cylinder 1
|
94720 lb
|
|
Maximum load on cylinder 2
|
99105 lb
|
|
Compressive strength of cylinder 1
|
3384.1 psi
|
|
Type of fracture pattern of cylinder 1
|
2
|
|
Compressive strength of cylinder 2
|
3528.1 psi
|
|
Type of fracture pattern of cylinder 2
|
2
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Age of specimen
|
7 days
|
|
Age of specimen in hours
|
no data0 hours
|
Test
DIME Test ID: 2026-03-06-1-2
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 03/20/2026
Date Tested: 03/20/2026
Submitted By Organization: CT D11 - District 11 Materials Laboratory
Organization Address: 4050 Taylor Street,
Organization City: San Diego
Organization State: CA
Organization Zipcode: 92110
Organization Email: benjamin.haney@dot.ca.gov
Organization Phone: (858) 688-1595
General Comments for this Test: 14 Day, Complies
3625 @ 42 days
Test Result Compliance: complies
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
2
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
|
Average diameter of cylinder 1
|
5.97 in
|
|
Average diameter of cylinder 2
|
5.97 in
|
|
Cross sectional area of cylinder 1
|
27.99 in^2
|
|
Cross sectional area of cylinder 2
|
27.99 in^2
|
|
Compressive strength (to nearest 10 psi)
|
4340 psi
|
|
Maximum load on cylinder 1
|
119215 lb
|
|
Maximum load on cylinder 2
|
123485 lb
|
|
Compressive strength of cylinder 1
|
4259.2 psi
|
|
Type of fracture pattern of cylinder 1
|
2
|
|
Compressive strength of cylinder 2
|
4411.8 psi
|
|
Type of fracture pattern of cylinder 2
|
2
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Age of specimen
|
7 days
|
|
Age of specimen in hours
|
no data0 hours
|
Test
DIME Test ID: 2026-03-06-1-3
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 04/06/2026
Date Tested: 04/03/2026
Submitted By Organization: CT D11 - District 11 Materials Laboratory
Organization Address: 4050 Taylor Street,
Organization City: San Diego
Organization State: CA
Organization Zipcode: 92110
Organization Email: benjamin.haney@dot.ca.gov
Organization Phone: (858) 688-1595
General Comments for this Test: 28 Day, complies
Test Result Compliance: complies
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
2
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C1231 - Unbonded Elastomeric Pad Cap
|
|
Average diameter of cylinder 1
|
5.99 in
|
|
Average diameter of cylinder 2
|
5.99 in
|
|
Cross sectional area of cylinder 1
|
28.18 in^2
|
|
Cross sectional area of cylinder 2
|
28.18 in^2
|
|
Compressive strength (to nearest 10 psi)
|
5150 psi
|
|
Maximum load on cylinder 1
|
145675 lb
|
|
Maximum load on cylinder 2
|
144615 lb
|
|
Compressive strength of cylinder 1
|
5169.4 psi
|
|
Type of fracture pattern of cylinder 1
|
1
|
|
Compressive strength of cylinder 2
|
5131.8 psi
|
|
Type of fracture pattern of cylinder 2
|
1
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Age of specimen
|
28 days
|
|
Age of specimen in hours
|
no data0 hours
|
Test
DIME Test ID: 2026-03-06-1-4
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Submitted By Organization: CT D11 - District 11 Materials Laboratory
Organization Address: 7177 Opportunity Road,
Organization City: San Diego
Organization State: CA
Organization Zipcode: 92111
Organization Email: D11PlantServices@dot.ca.gov
Organization Phone: (858) 518-8709
This test has been superseded on 04/21/2026.
Reason: corrected
Test
DIME Test ID: 2026-03-06-1-9
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 04/21/2026
Date Tested: 04/21/2026
Submitted By Organization: CT D11 - District 11 Materials Laboratory
Organization Address: 4050 Taylor Street,
Organization City: San Diego
Organization State: CA
Organization Zipcode: 92110
Organization Email: benjamin.haney@dot.ca.gov
Organization Phone: (858) 688-1595
General Comments for this Test: Retest 46 Day Break,
Complies
Test Result Compliance: complies
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
2
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
|
Average diameter of cylinder 1
|
5.99 in
|
|
Average diameter of cylinder 2
|
5.99 in
|
|
Cross sectional area of cylinder 1
|
28.18 in^2
|
|
Cross sectional area of cylinder 2
|
28.18 in^2
|
|
Compressive strength (to nearest 10 psi)
|
6100 psi
|
|
Maximum load on cylinder 1
|
169005 lb
|
|
Maximum load on cylinder 2
|
174785 lb
|
|
Compressive strength of cylinder 1
|
5997.3 psi
|
|
Type of fracture pattern of cylinder 1
|
1
|
|
Compressive strength of cylinder 2
|
6202.4 psi
|
|
Type of fracture pattern of cylinder 2
|
1
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Age of specimen
|
42 days
|
|
Age of specimen in hours
|
no data0 hours
|