QA Service Level: 2
DIST-CO-RTE-PM: 07-VEN-34-6.3
Work Description: Construct grade separation structure and connector ramps
Location Description: SR34 and Rice Avenue, Oxnard
Contractor Name: Unknown
Contractor Address: Unknown
Resident Engineer: Unknown Structure Rep.: Azizollah Maghsoudloo
DIME Sample ID: 2026-01-27-34
TL Number from the TL Form:
Sample Submitted By Organization: Surecast West
Sample Organization Contact: (951) 491-9506
Type of Sample: Quality Control
Type of Material: Concrete
Sample Taken Date: 01/27/2026
Date that the sample was received by the laboratory/organization performing the testing: 01/28/2026
The quantity of what the sample constitutes: 10.75 CY
A brief description of the sample: TYPE I /II
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: CEMEX REDLANDS
The concrete mix design number: 1610974
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: 31876615
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: CONCRETE SAMPLE FROM WHEELBARROW
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
DIME Test ID: 2026-01-27-34-1
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 02/12/2026
Date Tested: 02/10/2026
Submitted By Organization: Surecast West
Organization Address: 8203 Alabama Street,
Organization City: Redlands
Organization State: CA
Organization Zipcode: 92373
Organization Email: cody@surecastwest.com
Organization Phone: (951) 491-9506
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
|
Average diameter of cylinder 1
|
4.00 in
|
|
Average diameter of cylinder 2
|
4.00 in
|
|
Average diameter of cylinder 3
|
4.00 in
|
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
|
Compressive strength (to nearest 10 psi)
|
5610 psi
|
|
Maximum load on cylinder 1
|
70340 lb
|
|
Maximum load on cylinder 2
|
71440 lb
|
|
Maximum load on cylinder 3
|
69690 lb
|
|
Type of fracture pattern of cylinder 1
|
1
|
|
Type of fracture pattern of cylinder 2
|
1
|
|
Type of fracture pattern of cylinder 3
|
1
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
9 days
|
|
Age of specimen in hours
|
no data0 hours
|