Print Report | Back to Sample Detail

Sample Record for 2026-02-06-11

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 995125 DEA: 101E3004 EFIS: 1018000273 QA Service Level: 1
DIST-CO-RTE-PM: 10-SJ-5-32.5/49.8
Work Description: REMOVE EXISTING PAVEMENT AND REPLACE WITH CONCRETE PAVEMENT.
Location Description: SAN JOAQUIN COUNTY IN AND NEAR STOCKTON FROM 0.2 MILE SOUTH OF HAMMER LANE UNDERCROSSING TO SACRAMENTO COUNTY LINE
Contractor Name: BAY CITIES PAVING & GRADING, INC.
Contractor Address: 1450 Civic Court, Building B #400, Concord, CA 95351
Resident Engineer: Ariel Mendoza Structure Rep.: Unknown

Sample Information

DIME Sample ID: 2026-02-06-11
TL Number from the TL Form:
Sample Submitted By Organization: Atlas - Denver
Sample Organization Contact: 303-975-9959
Type of Sample: Verification
Type of Material: Asphalt Binder
Sample Taken Date: 02/06/2026
Date that the sample was received by the laboratory/organization performing the testing: 02/09/2026
The quantity of what the sample constitutes: 1 Quart Can
A brief description of the sample: PG 64-10 Tank 19
From where was the sample collected: Source
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Pacific Northwest Oil - Stockton, CA

Material Information

Performance Grade: PG 64-10
Modified:
Lot number:
Sublot number:
Tank number: 19
Time of sample:
HMA Supplier:
Certified Asphalt Supplier: Pacific Northwest Oil - Stockton CA
Multigrade: Yes
Multigrade Type:
Asphalt Binder Mix Number:

Test Results

Test 1 of 7

DIME Test ID: 2026-02-06-11-1
Test Method: AASHTO T315-24: Standard Method of Test for Determining the Rheological Properties of Asphalt Binder Using a Dynamic Shear Rheometer (DSR) (Dynamic Shear)
Verified Date: 02/19/2026
Date Tested: 02/19/2026
Submitted By Organization: Atlas - Denver
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ian.broddrick@dot.ca.gov
Organization Phone: (916) 741-2680
General Comments for this Test: OG
Test Result Compliance: complies
Additional Comments When Verified:
Phase Original binder
Test Gap 1 mm
Test Frequency 10.0 rad/s
Strain Amplitude 12.06 %
Stress Amplitude 0.175 kPa
Phase Angle (δ) (for the 10 cycles) 86.8 degree
Complex Modulus (G*) (for the 10 measurements) 1.452 kPa
Test Temperature (Specimen 1) 64.0 C
Dynamic Shear, G*/sin(δ) 1.45 kPa

Test 2 of 7

DIME Test ID: 2026-02-06-11-2
Test Method: AASHTO T315-24: Standard Method of Test for Determining the Rheological Properties of Asphalt Binder Using a Dynamic Shear Rheometer (DSR) (Dynamic Shear)
Verified Date: 02/19/2026
Date Tested: 02/19/2026
Submitted By Organization: Atlas - Denver
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ian.broddrick@dot.ca.gov
Organization Phone: (916) 741-2680
General Comments for this Test: RTFO
Test Result Compliance: complies
Additional Comments When Verified:
Phase RTFO residue
Test Gap 1 mm
Test Frequency 10.0 rad/s
Strain Amplitude 10.05 %
Stress Amplitude 0.360 kPa
Phase Angle (δ) (for the 10 cycles) 83.5 degree
Complex Modulus (G*) (for the 10 measurements) 3.585 kPa
Test Temperature (Specimen 1) 64.0 C
Dynamic Shear, G*/sin(δ) 3.61 kPa

Test 3 of 7

DIME Test ID: 2026-02-06-11-3
Test Method: AASHTO T315-24: Standard Method of Test for Determining the Rheological Properties of Asphalt Binder Using a Dynamic Shear Rheometer (DSR) (Dynamic Shear)
Verified Date: 02/19/2026
Date Tested: 02/19/2026
Submitted By Organization: Atlas - Denver
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ian.broddrick@dot.ca.gov
Organization Phone: (916) 741-2680
General Comments for this Test: PAV
Test Result Compliance: complies
Additional Comments When Verified:
Phase PAV residue
Test Plate Diameter 8 mm
Test Gap 2 mm
Test Frequency 10.0 rad/s
Strain Amplitude 1.01 %
Stress Amplitude 23.428 kPa
Phase Angle (δ) (for the 10 cycles) 51.5 degree
Complex Modulus (G*) (for the 10 measurements) 2331.045 kPa
Test Temperature (Specimen 1) 31.0 C
(G*) x sin(δ)= 1824 kPa

Test 4 of 7

DIME Test ID: 2026-02-06-11-4
Test Method: AASHTO T313-22: Standard Method of Test for Determining the Flexural Creep Stiffness of Asphalt Binder Using the Bending Beam Rheometer (BBR)
Verified Date: 02/19/2026
Date Tested: 02/19/2026
Submitted By Organization: Atlas - Denver
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ian.broddrick@dot.ca.gov
Organization Phone: (916) 741-2680
General Comments for this Test: BBR
Test Result Compliance: complies
Additional Comments When Verified:
Time test started no data HH:MM:SS
Flags issued by software during test no data
Correlation coefficient (R²) no data0
Regression coefficient a no data
Regression coefficient b no data
Regression coefficient c no data
Load at time 0.0 no data0 mN
Deflection at time 0.0 s no data0 µm
Load at time 0.5 s no data0 mN
Deflection at time 0.5 s no data0 µm
Load at 60.0 s no data0 mN
Beam deflection 60.0 s no data0 µm
Measured Stiffness Modulus 60.0 s no data
Estimated Stiffness Modulus 60.0 s 30.945 MPa
Difference between stiffness moduli 60.0 s no data
Estimated m-value 60.0 s 0.471

Test 5 of 7

DIME Test ID: 2026-02-06-11-5
Test Method: AASHTO T316-22: Standard Method of Test for Viscosity Determination of Asphalt Binder Using Rotational Viscometer
Verified Date: 02/19/2026
Date Tested: 02/17/2026
Submitted By Organization: Atlas - Denver
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ian.broddrick@dot.ca.gov
Organization Phone: (916) 741-2680
General Comments for this Test: VISCOCITY @ 135C
Test Result Compliance: complies
Additional Comments When Verified:
Is viscosity reading in cP/Pa-s? cP
Time of test 00:00 HH:MM
Test Temperature 135 C
Speed 20 rpm
Spindle size .463 in
Torque 9.6 %
Viscosity reading #1 (A) 239 cP
Viscosity reading #2 (B) 239 cP
Viscosity reading #3 (C) 239 cP
Average viscosity 0.239 Pa-s

Test 6 of 7

DIME Test ID: 2026-02-06-11-6
Test Method: AASHTO T240-23: Standard Method of Test for Effect of Heat and Air on a Moving Film of Asphalt Binder (Rolling Thin-Film Oven Test)
Verified Date: 02/19/2026
Date Tested: 02/18/2026
Submitted By Organization: Atlas - Denver
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ian.broddrick@dot.ca.gov
Organization Phone: (916) 741-2680
General Comments for this Test: MASS CHANGE
Test Result Compliance: complies
Additional Comments When Verified:
Is mass change based on one or two containers? Two
Is mass change correction factor needed? Yes
Any material loss from containers during heating process/testing? no data
Mass of container #1 before test (m1i) 209.641 grams
Mass of container #2 before test (m2i) 210.053 grams
Mass of container #1 after test (m1f) 209.55 grams
Mass of container #2 after test (m2f) 209.958 grams
Average mass change -0.238 percent
Mass of empty container #1 175.057 grams
Mass of empty container #2 175.277 grams
Mass correction factor 0.03

Test 7 of 7

DIME Test ID: 2026-02-06-11-7
Test Method: AASHTO T51-22: Standard Method of Test for Ductility of Asphalt Materials (Asphalt Binder)
Verified Date: 02/19/2026
Date Tested: 02/18/2026
Submitted By Organization: Atlas - Denver
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ian.broddrick@dot.ca.gov
Organization Phone: (916) 741-2680
General Comments for this Test: DUCTILITY
Test Result Compliance: complies
Additional Comments When Verified:
Is a normal test obtainable? Yes
Number of replicates tested Three
Ductility of test #1 (D1) 150 cm
Ductility of test #2 (D2) 150 cm
Ductility of test #3 (D3) 150 cm
Ductility of sample 150 cm