Project Information

Project ID: 995493 DEA: 081G6704 EFIS: 0816000049 QA Service Level: 1
DIST-CO-RTE-PM: 08-RIV-79-5.4/11.4
Work Description: HOT MIX ASPHALT, SOIL NAIL, STRUCTURAL CONCRETE AND ROADWAY EXC.
Location Description: RIVERSIDE COUNTY NEAR TEMECULA FROM 0.4 MILE SOUTH OF SAGE ROAD TO 1.1 MILES SOUTH OF PAUBA ROAD
Contractor Name: ORTIZ ENTERPRISES, INC.
Contractor Address: 6 CUSHING STE 200, IRVINE, CA 92618
Resident Engineer: Osama Abdalla Structure Rep.: Arnel Vega

Sample Information

DIME Sample ID: 2026-01-22-36
TL Number from the TL Form: 178708
Sample Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Sample Organization Contact: 213-792-4794
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 01/22/2026
Date that the sample was received by the laboratory/organization performing the testing: 01/26/2026
The quantity of what the sample constitutes: 8
A brief description of the sample: 4x8
From where was the sample collected: Job Site
Laboratory sample identification: 1085-08
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: np

Material Information

The concrete mix design number: 5236125A
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: na
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: na
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:

Test Results

Test

DIME Test ID: 2026-01-22-36-1
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C1231 - Unbonded Elastomeric Pad Cap
Cured in accordance with ASTM C511
Verified Date: 04/08/2026
Date Tested: 01/29/2026
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Cross sectional area of cylinder 1 12.57 in^2
Cross sectional area of cylinder 2 12.57 in^2
Capped in accordance with? ASTM C1231 - Unbonded Elastomeric Pad Cap
Compressive strength (to nearest 10 psi) 3660 psi
Average diameter of cylinder 1 4.00 in
Average diameter of cylinder 2 4.00 in
Compressive strength of cylinder 1 3606.2 psi
Compressive strength of cylinder 2 3704.9 psi
Maximum load on cylinder 1 45330 lb
Maximum load on cylinder 2 46570 lb
Type of fracture pattern of cylinder 1 1
Type of fracture pattern of cylinder 2 2
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Age of specimen 7 days

Test

DIME Test ID: 2026-01-22-36-2
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C1231 - Unbonded Elastomeric Pad Cap
Cured in accordance with ASTM C511
Verified Date: 04/08/2026
Date Tested: 02/05/2026
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Cross sectional area of cylinder 1 12.57 in^2
Cross sectional area of cylinder 2 12.57 in^2
Capped in accordance with? ASTM C1231 - Unbonded Elastomeric Pad Cap
Compressive strength (to nearest 10 psi) 4440 psi
Average diameter of cylinder 1 4.00 in
Average diameter of cylinder 2 4.00 in
Compressive strength of cylinder 1 4366.0 psi
Compressive strength of cylinder 2 4515.5 psi
Maximum load on cylinder 1 54880 lb
Maximum load on cylinder 2 56760 lb
Type of fracture pattern of cylinder 1 2
Type of fracture pattern of cylinder 2 2
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Age of specimen 14 days

Test

DIME Test ID: 2026-01-22-36-3
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C1231 - Unbonded Elastomeric Pad Cap
Cured in accordance with ASTM C511
Verified Date: 04/08/2026
Date Tested: 02/19/2026
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Cross sectional area of cylinder 1 12.57 in^2
Cross sectional area of cylinder 2 12.57 in^2
Capped in accordance with? ASTM C1231 - Unbonded Elastomeric Pad Cap
Compressive strength (to nearest 10 psi) 5300 psi
Average diameter of cylinder 1 4.00 in
Average diameter of cylinder 2 4.00 in
Compressive strength of cylinder 1 5230.7 psi
Compressive strength of cylinder 2 5368.3 psi
Maximum load on cylinder 1 65750 lb
Maximum load on cylinder 2 67480 lb
Type of fracture pattern of cylinder 1 3
Type of fracture pattern of cylinder 2 3
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Age of specimen 28 days

Test

DIME Test ID: 2026-01-22-36-4
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C1231 - Unbonded Elastomeric Pad Cap
Cured in accordance with ASTM C511
Verified Date: 04/08/2026
Date Tested: 03/05/2026
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Cross sectional area of cylinder 1 12.57 in^2
Cross sectional area of cylinder 2 12.57 in^2
Capped in accordance with? ASTM C1231 - Unbonded Elastomeric Pad Cap
Compressive strength (to nearest 10 psi) 5800 psi
Average diameter of cylinder 1 4.00 in
Average diameter of cylinder 2 4.00 in
Compressive strength of cylinder 1 5713.6 psi
Compressive strength of cylinder 2 5878.3 psi
Maximum load on cylinder 1 71820 lb
Maximum load on cylinder 2 73890 lb
Type of fracture pattern of cylinder 1 3
Type of fracture pattern of cylinder 2 3
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Age of specimen 42 days