Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project ID: 1000731 DEA: 042Q4404 EFIS: 0419000013
QA Service Level: 1
DIST-CO-RTE-PM: 04-SON-121-6.5,8.4
Work Description: REMOVE BR AND AC SURF, CONSTRUCT BR DECK, RAILING AND POLYESTER CONC.
Location Description: SONOMA COUNTY NEAR SONOMA AT YELLOW CREEK BRIDGE AND AT ARROYO SECO BRIDGE
Contractor Name: GORDON N. BALL, INC.
Contractor Address: Unknown
Resident Engineer: Fabio La Serna Structure Rep.: Jeremy Light
DIME Sample ID: 2026-01-09-32
TL Number from the TL Form:
Sample Submitted By Organization: CT SC - 3672 - Petaluma
Sample Organization Contact: (510) 3939273
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 01/09/2026
Date that the sample was received by the laboratory/organization performing the testing: 01/09/2025
The quantity of what the sample constitutes: 18 CY
A brief description of the sample: 3 4x8 Cylinders
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier: 20-0023
Structure name: Yellow creek Br NB App Slabs & Barrier Footings
The fabricator/manufacturer/facility name: Shamrock Materials Inc
The concrete mix design number: H7511503
The truck number from where the sample was collected: 2465
The batch plant ticket number from where the sample was collected: 434322
Concrete batch plant: 138
The fabricator/manufacturer designation for the sample: Shamrock Materials
A detailed description of where the material sample was collected: Back of Truck
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
DIME Test ID: 2026-01-09-32-1
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 02/10/2026
Date Tested: 02/06/2026
Submitted By Organization: Quality Assurance Engineering, Inc dba Consolidated Engineering Laboratories
Organization Address: 690 Walnut,
Organization City: vallejo
Organization State: CA
Organization Zipcode: 94592
Organization Email: yannick.aranas@dot.ca.gov
Organization Phone: (916) 639-4315
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C1231 - Unbonded Elastomeric Pad Cap
|
|
Average diameter of cylinder 1
|
4.00 in
|
|
Average diameter of cylinder 2
|
4.00 in
|
|
Average diameter of cylinder 3
|
4.00 in
|
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
|
Compressive strength (to nearest 10 psi)
|
11160 psi
|
|
Maximum load on cylinder 1
|
139630 lb
|
|
Maximum load on cylinder 2
|
140940 lb
|
|
Maximum load on cylinder 3
|
140270 lb
|
|
Compressive strength of cylinder 1
|
11108.2 psi
|
|
Type of fracture pattern of cylinder 1
|
3
|
|
Compressive strength of cylinder 2
|
11212.4 psi
|
|
Compressive strength of cylinder 3
|
11159.1 psi
|
|
Type of fracture pattern of cylinder 2
|
3
|
|
Type of fracture pattern of cylinder 3
|
3
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
28 days
|
|
Age of specimen in hours
|
no data
|
DIME Test ID: 2026-01-09-32-4
Test Method: ASTM C1064-17: Standard Test Method for Temperature of Freshly Mixed Hydraulic-Cement Concrete
Verified Date: 01/12/2026
Date Tested: 01/09/2026
Submitted By Organization: CT SC - 3672 - Petaluma
Organization Address: 756 Francisco Boulevard West,
Organization City: San Rafael
Organization State: CA
Organization Zipcode: 94901
Organization Email: jeremy.light@dot.ca.gov
Organization Phone: (510) 393-9273
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
DIME Test ID: 2026-01-09-32-5
Test Method: ASTM C143-15a: Standard Test Method for Slump of Hydraulic-Cement Concrete
Verified Date: 01/12/2026
Date Tested: 01/09/2026
Submitted By Organization: CT SC - 3672 - Petaluma
Organization Address: 756 Francisco Boulevard West,
Organization City: San Rafael
Organization State: CA
Organization Zipcode: 94901
Organization Email: jeremy.light@dot.ca.gov
Organization Phone: (510) 393-9273
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
DIME Test ID: 2026-01-09-32-6
Test Method: ASTM C1064-17: Standard Test Method for Temperature of Freshly Mixed Hydraulic-Cement Concrete
Verified Date: 01/12/2026
Date Tested: 01/09/2026
Submitted By Organization: CT SC - 3672 - Petaluma
Organization Address: 756 Francisco Boulevard West,
Organization City: San Rafael
Organization State: CA
Organization Zipcode: 94901
Organization Email: jeremy.light@dot.ca.gov
Organization Phone: (510) 393-9273
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
DIME Test ID: 2026-01-09-32-7
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 01/12/2026
Date Tested: 01/12/2026
Submitted By Organization: CT HQ - Vallejo Field Laboratory
Organization Address: 690 Walnut,
Organization City: vallejo
Organization State: CA
Organization Zipcode: 94592
Organization Email: yannick.aranas@dot.ca.gov
Organization Phone: (916) 639-4315
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C1231 - Unbonded Elastomeric Pad Cap
|
|
Apparent mass of submerged cylinder 1
|
1 lb
|
|
Average diameter of cylinder 1
|
4.00 in
|
|
Average diameter of cylinder 2
|
4.00 in
|
|
Average diameter of cylinder 3
|
4.00 in
|
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
|
Compressive strength (to nearest 10 psi)
|
6300 psi
|
|
Maximum load on cylinder 1
|
78562 lb
|
|
Maximum load on cylinder 2
|
78500 lb
|
|
Maximum load on cylinder 3
|
80635 lb
|
|
Compressive strength of cylinder 1
|
6250.0 psi
|
|
Type of fracture pattern of cylinder 1
|
3
|
|
Compressive strength of cylinder 2
|
6250.0 psi
|
|
Compressive strength of cylinder 3
|
6410 psi
|
|
Type of fracture pattern of cylinder 2
|
2
|
|
Type of fracture pattern of cylinder 3
|
3
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
3 days
|
|
Age of specimen in hours
|
no data0 hours
|
|
Serial number of delivery ticket, if available
|
no data
|