Sample Record for 2026-01-09-32

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 1000731 DEA: 042Q4404 EFIS: 0419000013 QA Service Level: 1
DIST-CO-RTE-PM: 04-SON-121-6.5,8.4
Work Description: REMOVE BR AND AC SURF, CONSTRUCT BR DECK, RAILING AND POLYESTER CONC.
Location Description: SONOMA COUNTY NEAR SONOMA AT YELLOW CREEK BRIDGE AND AT ARROYO SECO BRIDGE
Contractor Name: GORDON N. BALL, INC.
Contractor Address: Unknown
Resident Engineer: Fabio La Serna Structure Rep.: Jeremy Light

Sample Information

DIME Sample ID: 2026-01-09-32
TL Number from the TL Form:
Sample Submitted By Organization: CT SC - 3672 - Petaluma
Sample Organization Contact: (510) 3939273
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 01/09/2026
Date that the sample was received by the laboratory/organization performing the testing: 01/09/2025
The quantity of what the sample constitutes: 18 CY
A brief description of the sample: 3 4x8 Cylinders
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier: 20-0023
Structure name: Yellow creek Br NB App Slabs & Barrier Footings
The fabricator/manufacturer/facility name: Shamrock Materials Inc

Material Information

The concrete mix design number: H7511503
The truck number from where the sample was collected: 2465
The batch plant ticket number from where the sample was collected: 434322
Concrete batch plant: 138
The fabricator/manufacturer designation for the sample: Shamrock Materials
A detailed description of where the material sample was collected: Back of Truck
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:

Test Results

Test 1 of 5

DIME Test ID: 2026-01-09-32-1
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 02/10/2026
Date Tested: 02/06/2026
Submitted By Organization: Quality Assurance Engineering, Inc dba Consolidated Engineering Laboratories
Organization Address: 690 Walnut,
Organization City: vallejo
Organization State: CA
Organization Zipcode: 94592
Organization Email: yannick.aranas@dot.ca.gov
Organization Phone: (916) 639-4315
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 3
Test performed With no density determined
Capped in accordance with? ASTM C1231 - Unbonded Elastomeric Pad Cap
Average diameter of cylinder 1 4.00 in
Average diameter of cylinder 2 4.00 in
Average diameter of cylinder 3 4.00 in
Cross sectional area of cylinder 1 12.57 in^2
Cross sectional area of cylinder 2 12.57 in^2
Cross sectional area of cylinder 3 12.57 in^2
Compressive strength (to nearest 10 psi) 11160 psi
Maximum load on cylinder 1 139630 lb
Maximum load on cylinder 2 140940 lb
Maximum load on cylinder 3 140270 lb
Compressive strength of cylinder 1 11108.2 psi
Type of fracture pattern of cylinder 1 3
Compressive strength of cylinder 2 11212.4 psi
Compressive strength of cylinder 3 11159.1 psi
Type of fracture pattern of cylinder 2 3
Type of fracture pattern of cylinder 3 3
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Correction factor for cylinder 3 1
Age of specimen 28 days
Age of specimen in hours no data

Test 2 of 5

DIME Test ID: 2026-01-09-32-4
Test Method: ASTM C1064-17: Standard Test Method for Temperature of Freshly Mixed Hydraulic-Cement Concrete
Verified Date: 01/12/2026
Date Tested: 01/09/2026
Submitted By Organization: CT SC - 3672 - Petaluma
Organization Address: 756 Francisco Boulevard West,
Organization City: San Rafael
Organization State: CA
Organization Zipcode: 94901
Organization Email: jeremy.light@dot.ca.gov
Organization Phone: (510) 393-9273
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Temperature 56 F

Test 3 of 5

DIME Test ID: 2026-01-09-32-5
Test Method: ASTM C143-15a: Standard Test Method for Slump of Hydraulic-Cement Concrete
Verified Date: 01/12/2026
Date Tested: 01/09/2026
Submitted By Organization: CT SC - 3672 - Petaluma
Organization Address: 756 Francisco Boulevard West,
Organization City: San Rafael
Organization State: CA
Organization Zipcode: 94901
Organization Email: jeremy.light@dot.ca.gov
Organization Phone: (510) 393-9273
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Slump 8.5 inch

Test 4 of 5

DIME Test ID: 2026-01-09-32-6
Test Method: ASTM C1064-17: Standard Test Method for Temperature of Freshly Mixed Hydraulic-Cement Concrete
Verified Date: 01/12/2026
Date Tested: 01/09/2026
Submitted By Organization: CT SC - 3672 - Petaluma
Organization Address: 756 Francisco Boulevard West,
Organization City: San Rafael
Organization State: CA
Organization Zipcode: 94901
Organization Email: jeremy.light@dot.ca.gov
Organization Phone: (510) 393-9273
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Temperature 56 F

Test 5 of 5

DIME Test ID: 2026-01-09-32-7
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 01/12/2026
Date Tested: 01/12/2026
Submitted By Organization: CT HQ - Vallejo Field Laboratory
Organization Address: 690 Walnut,
Organization City: vallejo
Organization State: CA
Organization Zipcode: 94592
Organization Email: yannick.aranas@dot.ca.gov
Organization Phone: (916) 639-4315
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 3
Test performed With no density determined
Capped in accordance with? ASTM C1231 - Unbonded Elastomeric Pad Cap
Apparent mass of submerged cylinder 1 1 lb
Average diameter of cylinder 1 4.00 in
Average diameter of cylinder 2 4.00 in
Average diameter of cylinder 3 4.00 in
Cross sectional area of cylinder 1 12.57 in^2
Cross sectional area of cylinder 2 12.57 in^2
Cross sectional area of cylinder 3 12.57 in^2
Compressive strength (to nearest 10 psi) 6300 psi
Maximum load on cylinder 1 78562 lb
Maximum load on cylinder 2 78500 lb
Maximum load on cylinder 3 80635 lb
Compressive strength of cylinder 1 6250.0 psi
Type of fracture pattern of cylinder 1 3
Compressive strength of cylinder 2 6250.0 psi
Compressive strength of cylinder 3 6410 psi
Type of fracture pattern of cylinder 2 2
Type of fracture pattern of cylinder 3 3
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Correction factor for cylinder 3 1
Age of specimen 3 days
Age of specimen in hours no data0 hours
Serial number of delivery ticket, if available no data

Tests Assigned to this Sample

DIME Test IDTest MethodAssigned DateTest DateAssigned ByAssigned LabTest CommentsAssigned To
2026-01-09-32-3ASTM C143-15a: Standard Test Method for Slump of Hydraulic-Cement Concrete01/12/2026Not scheduledDhiren RajmohanCT SC - 3672 - Novato Field Office