Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project ID: 1001575 DEA: 061H9604 EFIS: 0625000104
QA Service Level: 1
DIST-CO-RTE-PM: 06-KER-46,119-VAR
Work Description: COLD PLANE AC PAVEMENT AND PLACING RHMA TYPE G.
Location Description: KERN COUNTY AT VARIOUS LOCATIONS
Contractor Name: Griffith Company (Edward Torres)
Contractor Address: 1128 Carrier Parkway Avenue, Bakersfield, CA 93308
Resident Engineer: Alejandro Ruezga Structure Rep.: Unknown
DIME Sample ID: 2025-12-08-37
TL Number from the TL Form:
Sample Submitted By Organization: WSP USA - Phoenix
Sample Organization Contact: 480-519-9086
Type of Sample: Quality Assurance
Type of Material: Asphalt Binder
Sample Taken Date: 12/08/2025
Date that the sample was received by the laboratory/organization performing the testing: 12/15/2025
The quantity of what the sample constitutes: 1 can of binder
A brief description of the sample: 70-10
From where was the sample collected: Source
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Griffith Edmonston
Performance Grade: PG 70-10
Modified: No
Lot number:
Sublot number:
Tank number:
Time of sample:
HMA Supplier:
Certified Asphalt Supplier: San Joaquin Refinery - Bakersfield CA
Multigrade: No
Multigrade Type:
Asphalt Binder Mix Number:
DIME Test ID: 2025-12-08-37-1
Test Method: AASHTO T315-24: Standard Method of Test for Determining the Rheological Properties of Asphalt Binder Using a Dynamic Shear Rheometer (DSR) (Dynamic Shear)
Verified Date: 12/30/2025
Date Tested: 12/24/2025
Submitted By Organization: Atlas - Denver
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ian.broddrick@dot.ca.gov
Organization Phone: (916) 741-2680
General Comments for this Test: OG
Test Result Compliance: complies
Additional Comments When Verified:
|
Phase
|
Original binder
|
|
Test Gap
|
1 mm
|
|
Test Frequency
|
10.0 rad/s
|
|
Strain Amplitude
|
12.00 %
|
|
Stress Amplitude
|
0.174 kPa
|
|
Phase Angle (δ) (for the 10 cycles)
|
89.4 degree
|
|
Complex Modulus (G*) (for the 10 measurements)
|
1.449 kPa
|
|
Test Temperature (Specimen 1)
|
70.0 C
|
|
Dynamic Shear, G*/sin(δ)
|
1.45 kPa
|
DIME Test ID: 2025-12-08-37-2
Test Method: AASHTO T315-24: Standard Method of Test for Determining the Rheological Properties of Asphalt Binder Using a Dynamic Shear Rheometer (DSR) (Dynamic Shear)
Verified Date: 12/30/2025
Date Tested: 12/30/2025
Submitted By Organization: Atlas - Denver
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ian.broddrick@dot.ca.gov
Organization Phone: (916) 741-2680
General Comments for this Test: RTFO
Test Result Compliance: complies
Additional Comments When Verified:
|
Phase
|
RTFO residue
|
|
Test Gap
|
1 mm
|
|
Test Frequency
|
10.0 rad/s
|
|
Strain Amplitude
|
10.00 %
|
|
Stress Amplitude
|
0.267 kPa
|
|
Phase Angle (δ) (for the 10 cycles)
|
88.7 degree
|
|
Complex Modulus (G*) (for the 10 measurements)
|
2.669 kPa
|
|
Test Temperature (Specimen 1)
|
70.0 C
|
|
Dynamic Shear, G*/sin(δ)
|
2.67 kPa
|
DIME Test ID: 2025-12-08-37-3
Test Method: AASHTO T315-24: Standard Method of Test for Determining the Rheological Properties of Asphalt Binder Using a Dynamic Shear Rheometer (DSR) (Dynamic Shear)
Verified Date: 12/30/2025
Date Tested: 12/30/2025
Submitted By Organization: WSP USA - Phoenix
Organization Address: 690 Walnut Avenue,
Organization City: Vallejo
Organization State: CA
Organization Zipcode: 94592
Organization Email: aaron.franklin@dot.ca.gov
Organization Phone: (858) 699-0513
General Comments for this Test: PAV
Test Result Compliance: does not comply
Additional Comments When Verified:
|
Phase
|
RTFO residue
|
|
Test Gap
|
1 mm
|
|
Test Frequency
|
10.0 rad/s
|
|
Strain Amplitude
|
1.00 %
|
|
Stress Amplitude
|
81.514 kPa
|
|
Phase Angle (δ) (for the 10 cycles)
|
58.6 degree
|
|
Complex Modulus (G*) (for the 10 measurements)
|
8150.539 kPa
|
|
Test Temperature (Specimen 1)
|
34.0 C
|
|
Dynamic Shear, G*/sin(δ)
|
9548.98 kPa
|
DIME Test ID: 2025-12-08-37-4
Test Method: AASHTO T240-23: Standard Method of Test for Effect of Heat and Air on a Moving Film of Asphalt Binder (Rolling Thin-Film Oven Test)
Verified Date: 12/30/2025
Date Tested: 12/24/2025
Submitted By Organization: WSP USA - Phoenix
Organization Address: 690 Walnut Avenue,
Organization City: Vallejo
Organization State: CA
Organization Zipcode: 94592
Organization Email: aaron.franklin@dot.ca.gov
Organization Phone: (858) 699-0513
General Comments for this Test: MASS CHANGE
Test Result Compliance: complies
Additional Comments When Verified:
|
Is mass change based on one or two containers?
|
Two
|
|
Is mass change correction factor needed?
|
No
|
|
Any material loss from containers during heating process/testing?
|
no data
|
|
Mass of container #1 before test (m1i)
|
187.231 grams
|
|
Mass of container #2 before test (m2i)
|
201.683 grams
|
|
Mass of container #1 after test (m1f)
|
187.141 grams
|
|
Mass of container #2 after test (m2f)
|
201.665 grams
|
|
Average mass change
|
-0.155 percent
|
|
Mass of empty container #1
|
152.414 grams
|
|
Mass of empty container #2
|
166.675 grams
|
DIME Test ID: 2025-12-08-37-6
Test Method: AASHTO T316-22: Standard Method of Test for Viscosity Determination of Asphalt Binder Using Rotational Viscometer
Verified Date: 12/30/2025
Date Tested: 12/24/2025
Submitted By Organization: WSP USA - Phoenix
Organization Address: 690 Walnut Avenue,
Organization City: Vallejo
Organization State: CA
Organization Zipcode: 94592
Organization Email: aaron.franklin@dot.ca.gov
Organization Phone: (858) 699-0513
General Comments for this Test: VISCOCITY AT 135C
Test Result Compliance: complies
Additional Comments When Verified:
|
Is viscosity reading in cP/Pa-s?
|
cP
|
|
Time of test
|
00:00 HH:MM
|
|
Test Temperature
|
135 C
|
|
Speed
|
200 rpm
|
|
Spindle size
|
.463 in
|
|
Torque
|
32.2 %
|
|
Viscosity reading #1 (A)
|
402.5 cP
|
|
Viscosity reading #2 (B)
|
402.5 cP
|
|
Viscosity reading #3 (C)
|
403.75 cP
|
|
Average viscosity
|
0.403 Pa-s
|
DIME Test ID: 2025-12-08-37-7
Test Method: AASHTO T51-22: Standard Method of Test for Ductility of Asphalt Materials (Asphalt Binder)
Verified Date: 12/30/2025
Date Tested: 12/30/2025
Submitted By Organization: WSP USA - Phoenix
Organization Address: 690 Walnut Avenue,
Organization City: Vallejo
Organization State: CA
Organization Zipcode: 94592
Organization Email: aaron.franklin@dot.ca.gov
Organization Phone: (858) 699-0513
General Comments for this Test: DUCTILITY
Test Result Compliance: complies
Additional Comments When Verified:
|
Is a normal test obtainable?
|
Yes
|
|
Number of replicates tested
|
Three
|
|
Ductility of test #1 (D1)
|
150 cm
|
|
Ductility of test #2 (D2)
|
150 cm
|
|
Ductility of test #3 (D3)
|
150 cm
|
|
Ductility of sample
|
150 cm
|
DIME Test ID: 2025-12-08-37-8
Test Method: AASHTO T315-24: Standard Method of Test for Determining the Rheological Properties of Asphalt Binder Using a Dynamic Shear Rheometer (DSR) (Dynamic Shear)
Verified Date: 12/30/2025
Date Tested: 12/30/2025
Submitted By Organization: WSP USA - Phoenix
Organization Address: 690 Walnut Avenue,
Organization City: Vallejo
Organization State: CA
Organization Zipcode: 94592
Organization Email: aaron.franklin@dot.ca.gov
Organization Phone: (858) 699-0513
General Comments for this Test: PAV + 3C
Test Result Compliance: complies
Additional Comments When Verified:
|
Phase
|
PAV residue
|
|
Test Plate Diameter
|
8 mm
|
|
Test Gap
|
2 mm
|
|
Test Frequency
|
10.0 rad/s
|
|
Strain Amplitude
|
1.00 %
|
|
Stress Amplitude
|
48.732 kPa
|
|
Phase Angle (δ) (for the 10 cycles)
|
62.1 degree
|
|
Complex Modulus (G*) (for the 10 measurements)
|
4872.889 kPa
|
|
Test Temperature (Specimen 1)
|
37.0 C
|
|
(G*) x sin(δ)=
|
4306 kPa
|
DIME Test ID: 2025-12-08-37-9
Test Method: AASHTO T313-22: Standard Method of Test for Determining the Flexural Creep Stiffness of Asphalt Binder Using the Bending Beam Rheometer (BBR)
Verified Date: 12/30/2025
Date Tested: 12/30/2025
Submitted By Organization: WSP USA - Phoenix
Organization Address: 690 Walnut Avenue,
Organization City: Vallejo
Organization State: CA
Organization Zipcode: 94592
Organization Email: aaron.franklin@dot.ca.gov
Organization Phone: (858) 699-0513
General Comments for this Test: BBR
Test Result Compliance: complies
Additional Comments When Verified:
|
Time test started
|
no data HH:MM:SS
|
|
Flags issued by software during test
|
no data
|
|
Correlation coefficient (R²)
|
no data0
|
|
Regression coefficient a
|
no data
|
|
Regression coefficient b
|
no data
|
|
Regression coefficient c
|
no data
|
|
Load at time 0.0
|
no data0 mN
|
|
Deflection at time 0.0 s
|
no data0 µm
|
|
Load at time 0.5 s
|
no data0 mN
|
|
Deflection at time 0.5 s
|
no data0 µm
|
|
Load at 60.0 s
|
no data0 mN
|
|
Beam deflection 60.0 s
|
no data0 µm
|
|
Measured Stiffness Modulus 60.0 s
|
no data
|
|
Estimated Stiffness Modulus 60.0 s
|
266.5 MPa
|
|
Difference between stiffness moduli 60.0 s
|
no data
|
|
Estimated m-value 60.0 s
|
0.372
|