Print Report | Back to Sample Detail

Sample Record for 2025-11-03-69

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 1000563 DEA: 021H7104 EFIS: 0217000013 QA Service Level: 1
DIST-CO-RTE-PM: 02-SIS-3,5-L47.4,R45.5/R46.0
Work Description: NEW MECHANIC SHOP AT YREKA MAINTENANCE STATION.
Location Description: SISKIYOU COUNTY IN YREKA ON ROUTE 3 AT YREKA MAINTENANCE STATION AND ON ROUTE 5 FROM 0.2 MILE SOUTH TO 0.4 MILE NORTH OF SOUTH YREKA UNDERCROSSING #02-0159
Contractor Name: MCCUEN CONSTRUCTION, INC.
Contractor Address: 3269 Swetzer Road, Loomis, CA 95650
Resident Engineer: Henry Austin Structure Rep.: Carlos Paz

Sample Information

DIME Sample ID: 2025-11-03-69
TL Number from the TL Form: 877606
Sample Submitted By Organization: CT D02 - Redding Northern Regional Laboratory
Sample Organization Contact: (530) 225-3194
Type of Sample: Production Start-Up
Type of Material: Hot Mix Asphalt
Sample Taken Date: 11/03/2025
Date that the sample was received by the laboratory/organization performing the testing: 11/04/2025
The quantity of what the sample constitutes: Production Start Up Evaluation
A brief description of the sample: 16 boxes of Lime Treated 3/4-inch Type A HMA (eq. PG 64-28M) with 23.6% RAP and virgin PG 58-34M binder from Valero - Benicia
From where was the sample collected: Manufacturer
Laboratory sample identification: D80116
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: JF Shea Construction - Fawndale Rock and Asphalt - Redding CA

Material Information

HMA Type: Type A HMA
HMA Grading: 3/4 inch
Lot number:
Sublot number:
HMA Mix Number:
Binder content (%): 4.5
Virgin binder PG: PG 58-34M
Design binder PG: PG 64-28M
Binder Supplier: Valero (Benicia, CA)
RAP content (%): 24
WMA Additives: No
Antistrip type: 1% Lime

Test Results

Test

DIME Test ID: 2025-11-03-69-1
Test Method: AASHTO T209-22: Standard Method of Test for Theoretical Maximum Specific Gravity (Gmm) and Density of Asphalt Mixtures (Maximum Specific Gravity)
Verified Date: 11/24/2025
Date Tested: 11/05/2025
Submitted By Organization: CT D02 - Redding Northern Regional Laboratory
Organization Address: 1657 Riverside Drive,
Organization City: Redding
Organization State: CA
Organization Zipcode: 96001
Organization Email: ward.jenkins@dot.ca.gov
Organization Phone: 530-225-3194
General Comments for this Test: Gmm=2.584
Test Result Compliance: not applicable
Additional Comments When Verified:
Number of Samples 1
What is the unit of measurement for theoretical density? SI Units
Mass Determination Air
Method Performed no data
Mass of container filled with water 1 7331 grams
Mass of oven-dry sample in air for Sample 1 2666.8 grams
Mass of container filled with the sample and water for Sample 1 8965.8 grams
Temperature of Water 77.4 °F
Specific Gravity for Sample 1 2.584
Theoretical maximum density at 25°C (77°F) 2577 kg/m^3

Test

DIME Test ID: 2025-11-03-69-2
Test Method: AASHTO T308-10: Standard Method of Test for Determining the Asphalt Binder Content of Hot Mix Asphalt (HMA) by the Ignition Method (Method A) (Asphalt Binder Content)
Verified Date: 11/24/2025
Date Tested: 11/18/2025
Submitted By Organization: CT D02 - Redding Northern Regional Laboratory
Organization Address: 1657 Riverside Drive,
Organization City: Redding
Organization State: CA
Organization Zipcode: 96001
Organization Email: ward.jenkins@dot.ca.gov
Organization Phone: 530-225-3194
General Comments for this Test: Pb=4.62%, TV=4.50
Test Result Compliance: complies
Additional Comments When Verified:
What temperature unit is used? Celsius
Test procedure used? Method A
Mass of the specimen basket assembly 3041.9 g
Mass of the specimen and specimen basket assembly prior to ignition 5144.1 g
Mass of HMA Sample prior to ignition 2102.2 g
Corrected Asphalt Binder Content 4.62 %
Mass Loss 107.4 g
Mass of aggregate remaining after ignition 1994.8 g
Correction Factor (Percent by mass of HMA Specimen) 0.35 %
Moisture Content no data0 %
Temperature Compensation Factor 0.14 %
Test Temperature 538 C

Test

DIME Test ID: 2025-11-03-69-3
Test Method: AASHTO T275-07r12: Standard Method of Test for Bulk Specific Gravity (Gmb) of Compacted Asphalt Mixtures Using Paraffin-Coated Specimens (Bulk Specific Gravity)
Verified Date: 11/24/2025
Date Tested: 11/06/2025
Submitted By Organization: CT D02 - Redding Northern Regional Laboratory
Organization Address: 1657 Riverside Drive,
Organization City: Redding
Organization State: CA
Organization Zipcode: 96001
Organization Email: ward.jenkins@dot.ca.gov
Organization Phone: 530-225-3194
General Comments for this Test: Gmb=2.454
Test Result Compliance: not applicable
Additional Comments When Verified:
Bulk Specific Gravity 2.452
Bulk Specific Gravity 2 2.447
Bulk Specific Gravity 3 2.463
Average Bulk Specific Gravity 2.454

Test

DIME Test ID: 2025-11-03-69-4
Test Method: AASHTO T269-14: Standard Method of Test for Percent Air Voids in Compacted Dense and Open Asphalt Mixtures (Air Void)
Verified Date: 11/24/2025
Date Tested: 11/06/2025
Submitted By Organization: CT D02 - Redding Northern Regional Laboratory
Organization Address: 1657 Riverside Drive,
Organization City: Redding
Organization State: CA
Organization Zipcode: 96001
Organization Email: ward.jenkins@dot.ca.gov
Organization Phone: 530-225-3194
General Comments for this Test: Pa=5.0%
Test Result Compliance: complies
Additional Comments When Verified:
Percent Air Voids 5.1 %
Percent Air Voids 2 5.3 %
Percent Air Voids 3 4.7 %
Average Percent Air Voids 5 %

Test

DIME Test ID: 2025-11-03-69-5
Test Method: AASHTO T283-14: Standard Method of Test for Resistance of Compacted Asphalt Mixtures to Moisture-Induced Damage (Moisture Content)
Verified Date: 11/24/2025
Date Tested: 11/19/2025
Submitted By Organization: CT D02 - Redding Northern Regional Laboratory
Organization Address: 1657 Riverside Drive,
Organization City: Redding
Organization State: CA
Organization Zipcode: 96001
Organization Email: ward.jenkins@dot.ca.gov
Organization Phone: 530-225-3194
General Comments for this Test: S1=121 psi, S2=114 psi, TSR=94%
Test Result Compliance: complies
Additional Comments When Verified:
Unit system used? SI Units
Average Dry Tensile Strength 121 psi
Average Wet Tensile Strength 114 psi
Tensile Strength Ratio 0.94