Sample Record for 2025-11-08-12
Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project Information
Project ID: 994415 DEA: 120R3114 EFIS: 1220000021
QA Service Level: 1
DIST-CO-RTE-PM: 12-LA,ORA-91-R20.6/R20.7,R0.0/4.8
Work Description: PLACE JPCP (RSC) AND RHMA, AND MODIFY ELECTRICAL SYSTEMS.
Location Description: LOS ANGELES AND ORANGE COUNTIES FROM 0.1 MILE WEST OF THE LOS ANGLES COUNTY LINE IN CERRITOS TO 0.1 MILE EAST OF ACACIA STREET UNDERCROSSING IN ANAHEIM
Contractor Name: BEADOR CONSTRUCTION COMPANY, INC.
Contractor Address: 2900 Bristol Street, Suite D204, Costa Mesa, CA 92626
Resident Engineer: Bill Gilchrist Structure Rep.: Matthew Chang
Sample Information
DIME Sample ID: 2025-11-08-12
TL Number from the TL Form:
Sample Submitted By Organization: CT D12 - Huntington Beach Field Laboratory
Sample Organization Contact: 9492798846
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 11/08/2025
Date that the sample was received by the laboratory/organization performing the testing: 11/08/2025
The quantity of what the sample constitutes: 6
A brief description of the sample: 6x12 concrete cylinders
From where was the sample collected: Job Site
Laboratory sample identification: 25-0385
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Unknown
Material Information
The concrete mix design number: RSC CTS-72-EHI
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: Unknown
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Discharge from concrete truck into wheelbarrow.
Where the material sample would have been placed if not sampled: WB 91 Western Ave. Departure Bridge No 55-0299, PM R2.35
From Lot No.:
Bag Lot No.:
Test Results
Test 1 of 1
DIME Test ID: 2025-11-08-12-1
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 11/12/2025
Date Tested: 11/11/2025
Submitted By Organization: CT D12 - Huntington Beach Field Laboratory
Organization Address: 19601 Beach Boulevard,
Organization City: Huntington Beach
Organization State: CA
Organization Zipcode: 92648
Organization Email: frank.mai@dot.ca.gov
Organization Phone: (949) 279-8846
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
2
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
|
Average diameter of cylinder 1
|
6.02 in
|
|
Average diameter of cylinder 2
|
6.02 in
|
|
Cross sectional area of cylinder 1
|
28.46 in^2
|
|
Cross sectional area of cylinder 2
|
28.46 in^2
|
|
Compressive strength (to nearest 10 psi)
|
6010 psi
|
|
Maximum load on cylinder 1
|
170570 lb
|
|
Maximum load on cylinder 2
|
171350 lb
|
|
Compressive strength of cylinder 1
|
5993.3 psi
|
|
Type of fracture pattern of cylinder 1
|
3
|
|
Compressive strength of cylinder 2
|
6020.7 psi
|
|
Type of fracture pattern of cylinder 2
|
3
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Age of specimen
|
3 days
|
|
Age of specimen in hours
|
no data0 hours
|