Project ID: 1000300 DEA: 060S0504 EFIS: 0615000047
QA Service Level: 1
DIST-CO-RTE-PM: 06-KER-166-17.5
Work Description: MICROPILING, STRUCTURAL CONCRETE, AND HOT MIX ASPHALT (TYPE A).
Location Description: KERN COUNTY NEAR METTLER AT CALIFORNIA AQUEDUCT BRIDGE
Contractor Name: GRANITE CONSTRUCTION COMPANY
Contractor Address: 3005 James Road, Bakersfield, CA 93308
Resident Engineer: James Burford Structure Rep.: Albert Heredia
DIME Sample ID: 2025-10-30-41
TL Number from the TL Form:
Sample Submitted By Organization: CT D06 - Bakersfield Field Laboratory
Sample Organization Contact: 661-549-8281
Type of Sample: Acceptance
Type of Material: Concrete
Sample Taken Date: 10/30/2025
Date that the sample was received by the laboratory/organization performing the testing: 10/30/2025
The quantity of what the sample constitutes: 12 concrete cylinders 4X8
A brief description of the sample: 4x8 cylinders
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Granite
The concrete mix design number: ND19551
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: 1
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Back of Truck
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
DIME Test ID: 2025-10-30-41-1
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 11/06/2025
Date Tested: 11/06/2025
Submitted By Organization: CT D06 - Bakersfield Field Laboratory
Organization Address: 1824 Norris Road,
Organization City: Bakersfield
Organization State: CA
Organization Zipcode: 93308
Organization Email: kulwinder.rai@dot.ca.gov
Organization Phone: (661) 549-8281
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
|
Average diameter of cylinder 1
|
4.00 in
|
|
Average diameter of cylinder 2
|
4.00 in
|
|
Average diameter of cylinder 3
|
4.00 in
|
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
|
Compressive strength (to nearest 10 psi)
|
3940 psi
|
|
Maximum load on cylinder 1
|
45410 lb
|
|
Maximum load on cylinder 2
|
52570 lb
|
|
Maximum load on cylinder 3
|
50600 lb
|
|
Compressive strength of cylinder 1
|
3612.6 psi
|
|
Type of fracture pattern of cylinder 1
|
5
|
|
Compressive strength of cylinder 2
|
4182.2 psi
|
|
Compressive strength of cylinder 3
|
4025.5 psi
|
|
Type of fracture pattern of cylinder 2
|
2
|
|
Type of fracture pattern of cylinder 3
|
5
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
7 days
|
|
Age of specimen in hours
|
no data0 hours
|
DIME Test ID: 2025-10-30-41-2
Test Method: ASTM C39-18: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 11/13/2025
Date Tested: 11/13/2025
Submitted By Organization: CT D06 - Bakersfield Field Laboratory
Organization Address: 1824 Norris Road,
Organization City: Bakersfield
Organization State: CA
Organization Zipcode: 93308
Organization Email: kulwinder.rai@dot.ca.gov
Organization Phone: (661) 549-8281
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Average diameter of cylinder 1
|
4.00 in
|
|
Average diameter of cylinder 2
|
4.00 in
|
|
Capped in accordance with?
|
ASTM C1231 - Unbonded Elastomeric Pad Cap
|
|
Average diameter of cylinder 3
|
4.00 in
|
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
|
Compressive strength (to nearest 10 psi)
|
4610 psi
|
|
Maximum load on cylinder 1
|
57450 lb
|
|
Maximum load on cylinder 2
|
60130 lb
|
|
Maximum load on cylinder 3
|
56450 lb
|
|
Compressive strength of cylinder 1
|
4570.4 psi
|
|
Type of fracture pattern of cylinder 1
|
4
|
|
Compressive strength of cylinder 2
|
4783.6 psi
|
|
Compressive strength of cylinder 3
|
4490.9 psi
|
|
Type of fracture pattern of cylinder 2
|
4
|
|
Type of fracture pattern of cylinder 3
|
1
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
14 days
|
|
Age of specimen in hours
|
no data0 hours
|
DIME Test ID: 2025-10-30-41-3
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 11/26/2025
Date Tested: 11/26/2025
Submitted By Organization: CT D06 - Bakersfield Field Laboratory
Organization Address: 1824 Norris Road,
Organization City: Bakersfield
Organization State: CA
Organization Zipcode: 93308
Organization Email: kulwinder.rai@dot.ca.gov
Organization Phone: (661) 549-8281
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C1231 - Unbonded Elastomeric Pad Cap
|
|
Average diameter of cylinder 1
|
4.00 in
|
|
Average diameter of cylinder 2
|
4.00 in
|
|
Average diameter of cylinder 3
|
4.00 in
|
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
|
Compressive strength (to nearest 10 psi)
|
5770 psi
|
|
Maximum load on cylinder 1
|
81690 lb
|
|
Maximum load on cylinder 2
|
66810 lb
|
|
Maximum load on cylinder 3
|
69020 lb
|
|
Compressive strength of cylinder 1
|
6498.8 psi
|
|
Type of fracture pattern of cylinder 1
|
2
|
|
Compressive strength of cylinder 2
|
5315.0 psi
|
|
Compressive strength of cylinder 3
|
5490.9 psi
|
|
Type of fracture pattern of cylinder 2
|
2
|
|
Type of fracture pattern of cylinder 3
|
1
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
27 days
|
|
Age of specimen in hours
|
no data0 hours
|