Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project ID: 993678 DEA: 042Q8004 EFIS: 0419000050 COOP: 042836,042944
QA Service Level: 1
DIST-CO-RTE-PM: 04-SM-101,92-US 101 & SR 92-10.9/12.1 & 11.8/13.4
Work Description: US 101/SR 92 INTERCHANGE AREA IMPROVEMENT :PROJECT WILL CONSTRUCT CONGESTION RELIEF IMPROVEMENTS AT THE US 101/SR 92 INTERCHANGE AREA.
Location Description:
Contractor Name: GORDON N. BALL, INC.
Contractor Address: 333 CAMILLE AVENUE, ALAMO, CA 94507
Resident Engineer: Mohamed Fouad Structure Rep.: Bryan Nagid
DIME Sample ID: 2025-10-04-12
TL Number from the TL Form:
Sample Submitted By Organization: CT SC - 3674 - Pacifica 2
Sample Organization Contact: (510) 714-7639
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 10/04/2025
Date that the sample was received by the laboratory/organization performing the testing: 10/20/2025
The quantity of what the sample constitutes: 189 CY
A brief description of the sample: Bent 16 CIDH Concrete
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier: 35-0252L
Structure name:
The fabricator/manufacturer/facility name: Central Concrete
The concrete mix design number: DDGPV2Q3
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: -
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Concrete sample from wheel barrow
Where the material sample would have been placed if not sampled: CIDH Pile
From Lot No.:
Bag Lot No.:
DIME Test ID: 2025-10-04-12-1
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 11/03/2025
Date Tested: 11/01/2025
Submitted By Organization: Kleinfelder - Hayward
Organization Address: 690 Walnut,
Organization City: vallejo
Organization State: CA
Organization Zipcode: 94592
Organization Email: yannick.aranas@dot.ca.gov
Organization Phone: (916) 639-4315
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C1231 - Unbonded Elastomeric Pad Cap
|
|
Average diameter of cylinder 1
|
4.00 in
|
|
Average diameter of cylinder 2
|
4.00 in
|
|
Average diameter of cylinder 3
|
4.00 in
|
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
|
Compressive strength (to nearest 10 psi)
|
7560 psi
|
|
Maximum load on cylinder 1
|
95213 lb
|
|
Maximum load on cylinder 2
|
93932 lb
|
|
Maximum load on cylinder 3
|
96058 lb
|
|
Compressive strength of cylinder 1
|
7574.6 psi
|
|
Type of fracture pattern of cylinder 1
|
5
|
|
Compressive strength of cylinder 2
|
7472.7 psi
|
|
Compressive strength of cylinder 3
|
7641.8 psi
|
|
Type of fracture pattern of cylinder 2
|
3
|
|
Type of fracture pattern of cylinder 3
|
5
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
28 days
|
|
Age of specimen in hours
|
no data0 hours
|