Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project Information
Project ID: 1000665 DEA: 081K4004 EFIS: 0819000031
QA Service Level: 1
DIST-CO-RTE-PM: 08-RIV-15-3.5/6.8
Work Description: HMA (TYPE A), RDWY EXC, STR CONC RET WALL, RUBBERIZED HMA (OGFC).
Location Description: TEMECULA FROM 0.1 MI NORTH OF TEMECULA PARKWAY TO 0.2 MI NORTH OF WINCHESTER ROAD
Contractor Name: BEADOR CONSTRUCTION COMPANY, INC.
Contractor Address: 2900 Bristol Street, Suite D204, Costa Mesa, CA 92626
Resident Engineer: Denise Sostrom Structure Rep.: Gizachew Abayneh
Sample Information
DIME Sample ID: 2025-10-02-44
TL Number from the TL Form:
Sample Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Sample Organization Contact: 213-792-4794
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 10/02/2025
Date that the sample was received by the laboratory/organization performing the testing: 10/10/2025
The quantity of what the sample constitutes: 2
A brief description of the sample: 6X12
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: *
Material Information
The concrete mix design number: 000
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: np
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: column wrap
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
Test Results
Test 1 of 2
DIME Test ID: 2025-10-02-44-1
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 11/17/2025
Date Tested: 10/16/2025
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
1
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C1231 - Unbonded Elastomeric Pad Cap
|
|
Apparent mass of submerged cylinder 1
|
no data0 lb
|
|
Average diameter of cylinder 1
|
6.01 in
|
|
Cross sectional area of cylinder 1
|
28.37 in^2
|
|
Compressive strength of cylinder (to nearest 10 psi)
|
6040 psi
|
|
Maximum load on cylinder 1
|
171485 lb
|
|
Type of fracture pattern of cylinder 1
|
1
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Age of specimen
|
14 days
|
|
Age of specimen in hours
|
no data0 hours
|
|
Serial number of delivery ticket, if available
|
no data
|
Test 2 of 2
DIME Test ID: 2025-10-02-44-2
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
Data has not been verified.