Sample Record for 2025-09-30-35
Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project Information
Project ID: 993446 DEA: 120J34U4 EFIS: 1218000034
QA Service Level: 1
DIST-CO-RTE-PM: 12-ORA-55,55-29.6,R6.4/10.3
Work Description: CONSTR BRIDGES, RW, SW, JPCP, HMA PVMT, DRAINAGE AND ELECT SYSTEMS.
Location Description: ORANGE COUNTY IN IRVINE, SANTA ANA, AND TUSTIN ON ROUTE 5 AT NEWPORT AVENUE UNDERCROSSING AND ON ROUTE 55 FROM 0.4 MILE NORTH OF ROUTE 55/405 SEPARATION TO 0.1 MILE SOUTH OF ROUTE 5/55 SEPARATION
Contractor Name: SECURITY PAVING COMPANY, INC.
Contractor Address: 3075 Townsgate Road, Suite 200, Westlake Village, CA 91361
Resident Engineer: Adrian Wu Structure Rep.: Yong Gyun Park
Sample Information
DIME Sample ID: 2025-09-30-35
TL Number from the TL Form:
Sample Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Sample Organization Contact: (530) 329-6527
Type of Sample: Quality Assurance
Type of Material: SMTL TM5 - Couplers
Sample Taken Date: 09/30/2025
Date that the sample was received by the laboratory/organization performing the testing: 10/02/2025
The quantity of what the sample constitutes: 150
A brief description of the sample: Bar Splice Grip Twist Coupler
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Field
Material Information
Production or Authorization Testing: Production Testing
Service or Ultimate: Service
Material Standard Code: ASTM A706
Material Grade: 60
Rebar Manufacturer: Cascade
Coupler Manufacturer: BarSplice
Intermediate Assembler or Fabricator:
Rebar Size: #6
Coupler Model: Grip Twist Bar Splice
Coating Standards: Uncoated
Shape of Rebar: Straight
Rebar Hoop Diameter:
Rebar Hoop Fabricator:
Coupler Component Heat/Lot Number(s): C242326, A241127
Rebar Heat Number(s): 425722
Rebar Size 2 :
Coupler Unique ID: SS-17-05
Test Results
Test 1 of 1
DIME Test ID: 2025-09-30-35-1
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile Slip)
Verified Date: 10/15/2025
Date Tested: 10/14/2025
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
|
Number of Samples
|
4
|
| Sample | Mfg. Lot Number(s) | Size | Area (sqin) | Slip (inch) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | | 1A | 425722 | #6 | 0.44 | 0.003 | 39720 | 90500 | NA | M Lee | | 1B | 425722 | #6 | 0.44 | 0 | 39710 | 90500 | NA | M Lee | | 1C | 425722 | #6 | 0.44 | 0 | 39840 | 90500 | NA | M Lee | | 1D | 425722 | #6 | 0.44 | 0 | 39990 | 91000 | NA | M Lee |
| |
|
Temperature
|
0 f
|
|
UTM
|
NA
|
|
Halo ID
|
NA
|