Project ID: 1000199 DEA: 050N7054 EFIS: 0518000111
QA Service Level: 1
DIST-CO-RTE-PM: 05-SB-101-10.4/11.1
Work Description: South Coast 101 HOV Lanes Project 4E South- Santa Barbara
Location Description:
Contractor Name: Granite Construction Company
Contractor Address: PO Box 6744, Santa Barbara, CA 93160
Resident Engineer: Tristan Gebhart Structure Rep.: Gary Cavafian
DIME Sample ID: 2025-09-30-6
TL Number from the TL Form:
Sample Submitted By Organization: CT D05 - Carpinteria Field Laboratory
Sample Organization Contact: (805) 621-3616
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 09/30/2025
Date that the sample was received by the laboratory/organization performing the testing: 09/30/2025
The quantity of what the sample constitutes: 110 CY
A brief description of the sample: 1 x 4 PCC Aggregates
From where was the sample collected: Supplier
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: CEMEX Santa Barbara
The concrete mix design number: 1629003
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: 31760814
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Discharge from concrete truck into wheelbarrow.
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
DIME Test ID: 2025-09-30-6-1
Test Method: ASTM C1064-17: Standard Test Method for Temperature of Freshly Mixed Hydraulic-Cement Concrete
Verified Date: 09/30/2025
Date Tested: 09/30/2025
Submitted By Organization: CT D05 - Carpinteria Field Laboratory
Organization Address: 21 Griffin Road North,
Organization City: Windsor
Organization State: CT
Organization Zipcode: 06095-1590
Organization Email: dlachaine@trccompanies.com
Organization Phone: (805) 621-3616
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
DIME Test ID: 2025-09-30-6-2
Test Method: ASTM C143-20: Standard Test Method for Slump of Hydraulic-Cement Concrete
Verified Date: 09/30/2025
Date Tested: 09/30/2025
Submitted By Organization: CT D05 - Carpinteria Field Laboratory
Organization Address: 21 Griffin Road North,
Organization City: Windsor
Organization State: CT
Organization Zipcode: 06095-1590
Organization Email: dlachaine@trccompanies.com
Organization Phone: (805) 621-3616
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
DIME Test ID: 2025-09-30-6-3
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 11/24/2025
Date Tested: 11/12/2025
Submitted By Organization: CT D05 - Carpinteria Field Laboratory
Organization Address: 21 Griffin Road North,
Organization City: Windsor
Organization State: CT
Organization Zipcode: 06095-1590
Organization Email: dlachaine@trccompanies.com
Organization Phone: (805) 621-3616
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
|
Average diameter of cylinder 1
|
4.00 in
|
|
Average diameter of cylinder 2
|
4.00 in
|
|
Average diameter of cylinder 3
|
4.00 in
|
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
|
Compressive strength (to nearest 10 psi)
|
6080 psi
|
|
Maximum load on cylinder 1
|
76230 lb
|
|
Maximum load on cylinder 2
|
67140 lb
|
|
Maximum load on cylinder 3
|
85760 lb
|
|
Compressive strength of cylinder 1
|
6064.4 psi
|
|
Type of fracture pattern of cylinder 1
|
5
|
|
Compressive strength of cylinder 2
|
5341.3 psi
|
|
Compressive strength of cylinder 3
|
6822.6 psi
|
|
Type of fracture pattern of cylinder 2
|
5
|
|
Type of fracture pattern of cylinder 3
|
2
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
43 days
|
|
Age of specimen in hours
|
no data0 hours
|
DIME Test ID: 2025-09-30-6-4
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 11/24/2025
Date Tested: 10/28/2025
Submitted By Organization: CT D05 - Carpinteria Field Laboratory
Organization Address: 21 Griffin Road North,
Organization City: Windsor
Organization State: CT
Organization Zipcode: 06095-1590
Organization Email: dlachaine@trccompanies.com
Organization Phone: (805) 621-3616
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C1231 - Unbonded Elastomeric Pad Cap
|
|
Average diameter of cylinder 1
|
4.01 in
|
|
Average diameter of cylinder 2
|
4.01 in
|
|
Average diameter of cylinder 3
|
4.00 in
|
|
Cross sectional area of cylinder 1
|
12.63 in^2
|
|
Cross sectional area of cylinder 2
|
12.63 in^2
|
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
|
Compressive strength (to nearest 10 psi)
|
5660 psi
|
|
Maximum load on cylinder 1
|
66830 lb
|
|
Maximum load on cylinder 2
|
75300 lb
|
|
Maximum load on cylinder 3
|
71810 lb
|
|
Compressive strength of cylinder 1
|
5291.4 psi
|
|
Type of fracture pattern of cylinder 1
|
5
|
|
Compressive strength of cylinder 2
|
5962.0 psi
|
|
Compressive strength of cylinder 3
|
5712.8 psi
|
|
Type of fracture pattern of cylinder 2
|
2
|
|
Type of fracture pattern of cylinder 3
|
2
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
28 days
|
|
Age of specimen in hours
|
no data0 hours
|