Project ID: 1000731 DEA: 042Q4404 EFIS: 0419000013
QA Service Level: 1
DIST-CO-RTE-PM: 04-SON-121-6.5,8.4
Work Description: REMOVE BR AND AC SURF, CONSTRUCT BR DECK, RAILING AND POLYESTER CONC.
Location Description: SONOMA COUNTY NEAR SONOMA AT YELLOW CREEK BRIDGE AND AT ARROYO SECO BRIDGE
Contractor Name: GORDON N. BALL, INC.
Contractor Address: Unknown
Resident Engineer: Fabio La Serna Structure Rep.: Jeremy Light
DIME Sample ID: 2025-09-26-17
TL Number from the TL Form:
Sample Submitted By Organization: CT SC - 3672 - Novato Field Office
Sample Organization Contact: (916) 621-8033
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 09/26/2025
Date that the sample was received by the laboratory/organization performing the testing: 09/26/2025
The quantity of what the sample constitutes: 3 CY
A brief description of the sample: Rapid Strength Concrete
From where was the sample collected: Manufacturer
Laboratory sample identification:
Structure unique identifier: 20-0023
Structure name: Arroyo Seco bridge
The fabricator/manufacturer/facility name: Shamrock Materials Inc
The concrete mix design number: H7511503
The truck number from where the sample was collected: 2456
The batch plant ticket number from where the sample was collected: 409037
Concrete batch plant: 138 Petaluma
The fabricator/manufacturer designation for the sample: Shamrock Materials
A detailed description of where the material sample was collected: back of truck
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
DIME Test ID: 2025-09-26-17-1
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 09/29/2025
Date Tested: 09/29/2025
Submitted By Organization: CT HQ - Vallejo Field Laboratory
Organization Address: 690 Walnut,
Organization City: vallejo
Organization State: CA
Organization Zipcode: 94592
Organization Email: yannick.aranas@dot.ca.gov
Organization Phone: (916) 639-4315
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C1231 - Unbonded Elastomeric Pad Cap
|
|
Average diameter of cylinder 1
|
4.00 in
|
|
Average diameter of cylinder 2
|
4.01 in
|
|
Average diameter of cylinder 3
|
4.01 in
|
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
|
Cross sectional area of cylinder 2
|
12.63 in^2
|
|
Cross sectional area of cylinder 3
|
12.63 in^2
|
|
Compressive strength (to nearest 10 psi)
|
5690 psi
|
|
Maximum load on cylinder 1
|
70580 lb
|
|
Maximum load on cylinder 2
|
73094 lb
|
|
Maximum load on cylinder 3
|
71586 lb
|
|
Compressive strength of cylinder 1
|
5615.0 psi
|
|
Type of fracture pattern of cylinder 1
|
5
|
|
Compressive strength of cylinder 2
|
5787.3 psi
|
|
Compressive strength of cylinder 3
|
5667.9 psi
|
|
Type of fracture pattern of cylinder 2
|
5
|
|
Type of fracture pattern of cylinder 3
|
5
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
3 days
|
|
Age of specimen in hours
|
no data
|
DIME Test ID: 2025-09-26-17-2
Test Method: ASTM C1064-17: Standard Test Method for Temperature of Freshly Mixed Hydraulic-Cement Concrete
Submitted By Organization: CT SC - 3672 - Novato Field Office
Organization Address: 384 Bel Marin Keys Boulevard, Suite 200,
Organization City: Novato
Organization State: CA
Organization Zipcode: 94949
Organization Email: josh.velono@dot.ca.gov
Organization Phone: (916) 621-8033
Data has not been verified.
DIME Test ID: 2025-09-26-17-3
Test Method: ASTM C143-15a: Standard Test Method for Slump of Hydraulic-Cement Concrete
Submitted By Organization: CT SC - 3672 - Novato Field Office
Organization Address: 384 Bel Marin Keys Boulevard, Suite 200,
Organization City: Novato
Organization State: CA
Organization Zipcode: 94949
Organization Email: josh.velono@dot.ca.gov
Organization Phone: (916) 621-8033
Data has not been verified.
DIME Test ID: 2025-09-26-17-4
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 10/06/2025
Date Tested: 10/01/2025
Submitted By Organization: Quality Assurance Engineering, Inc dba Consolidated Engineering Laboratories
Organization Address: 690 Walnut,
Organization City: vallejo
Organization State: CA
Organization Zipcode: 94592
Organization Email: yannick.aranas@dot.ca.gov
Organization Phone: (916) 639-4315
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
5
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
|
Average diameter of cylinder 1
|
4.00 in
|
|
Average diameter of cylinder 2
|
4.00 in
|
|
Average diameter of cylinder 3
|
4.00 in
|
|
Average diameter of cylinder 4
|
4.00 in
|
|
Average diameter of cylinder 5
|
4.00 in
|
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
|
Cross sectional area of cylinder 4
|
12.57 in^2
|
|
Cross sectional area of cylinder 5
|
12.57 in^2
|
|
Compressive strength (to nearest 10 psi)
|
6830 psi
|
|
Maximum load on cylinder 1
|
85970 lb
|
|
Maximum load on cylinder 2
|
85030 lb
|
|
Maximum load on cylinder 3
|
86830 lb
|
|
Maximum load on cylinder 4
|
85270 lb
|
|
Maximum load on cylinder 5
|
86270 lb
|
|
Compressive strength of cylinder 1
|
6839.3 psi
|
|
Type of fracture pattern of cylinder 1
|
2
|
|
Compressive strength of cylinder 2
|
6764.5 psi
|
|
Compressive strength of cylinder 3
|
6907.7 psi
|
|
Compressive strength of cylinder 4
|
6783.6 psi
|
|
Compressive strength of cylinder 5
|
6863.2 psi
|
|
Type of fracture pattern of cylinder 2
|
2
|
|
Type of fracture pattern of cylinder 3
|
2
|
|
Type of fracture pattern of cylinder 4
|
2
|
|
Type of fracture pattern of cylinder 5
|
2
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Correction factor for cylinder 4
|
1
|
|
Correction factor for cylinder 5
|
1
|
|
Age of specimen
|
5 days
|
|
Age of specimen in hours
|
no data
|
DIME Test ID: 2025-09-26-17-5
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 10/06/2025
Date Tested: 10/03/2025
Submitted By Organization: Quality Assurance Engineering, Inc dba Consolidated Engineering Laboratories
Organization Address: 690 Walnut,
Organization City: vallejo
Organization State: CA
Organization Zipcode: 94592
Organization Email: yannick.aranas@dot.ca.gov
Organization Phone: (916) 639-4315
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
5
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
|
Average diameter of cylinder 1
|
4.00 in
|
|
Average diameter of cylinder 2
|
4.00 in
|
|
Average diameter of cylinder 3
|
4.00 in
|
|
Average diameter of cylinder 4
|
4.00 in
|
|
Average diameter of cylinder 5
|
4.00 in
|
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
|
Cross sectional area of cylinder 4
|
12.57 in^2
|
|
Cross sectional area of cylinder 5
|
12.57 in^2
|
|
Compressive strength (to nearest 10 psi)
|
6960 psi
|
|
Maximum load on cylinder 1
|
86150 lb
|
|
Maximum load on cylinder 2
|
89300 lb
|
|
Maximum load on cylinder 3
|
86700 lb
|
|
Maximum load on cylinder 4
|
86420 lb
|
|
Maximum load on cylinder 5
|
89130 lb
|
|
Compressive strength of cylinder 1
|
6853.6 psi
|
|
Type of fracture pattern of cylinder 1
|
3
|
|
Compressive strength of cylinder 2
|
7104.2 psi
|
|
Compressive strength of cylinder 3
|
6897.4 psi
|
|
Compressive strength of cylinder 4
|
6875.1 psi
|
|
Compressive strength of cylinder 5
|
7090.7 psi
|
|
Type of fracture pattern of cylinder 2
|
5
|
|
Type of fracture pattern of cylinder 3
|
3
|
|
Type of fracture pattern of cylinder 4
|
2
|
|
Type of fracture pattern of cylinder 5
|
2
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Correction factor for cylinder 4
|
1
|
|
Correction factor for cylinder 5
|
1
|
|
Age of specimen
|
7 days
|
|
Age of specimen in hours
|
no data
|
DIME Test ID: 2025-09-26-17-7
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 09/30/2025
Date Tested: 09/30/2025
Submitted By Organization: Kleinfelder - Hayward
Organization Address: 690 Walnut,
Organization City: vallejo
Organization State: CA
Organization Zipcode: 94592
Organization Email: yannick.aranas@dot.ca.gov
Organization Phone: (916) 639-4315
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
2
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C1231 - Unbonded Elastomeric Pad Cap
|
|
Average diameter of cylinder 1
|
4.00 in
|
|
Average diameter of cylinder 2
|
4.00 in
|
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
|
Compressive strength (to nearest 10 psi)
|
6130 psi
|
|
Maximum load on cylinder 1
|
79076 lb
|
|
Maximum load on cylinder 2
|
75085 lb
|
|
Compressive strength of cylinder 1
|
6290.9 psi
|
|
Type of fracture pattern of cylinder 1
|
5
|
|
Compressive strength of cylinder 2
|
5973.3 psi
|
|
Type of fracture pattern of cylinder 2
|
5
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Age of specimen
|
4 days
|
|
Age of specimen in hours
|
no data
|