Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project ID: 212470 DEA: 044A1304 EFIS: 0400001106 COOP: 042718
QA Service Level: 1
DIST-CO-RTE-PM: 04-SON-101-18.5/18.5
Work Description: CONSISTS OF MODIFICATION AND RECONSTRUCTION OF THE EXISTING US 101/HEARN AVENUE INTERCHANGE IN SONOMA COUNTY, INCLUDING REPLACING THE EXISTING TWO-LANE HEARN AVENUE OVERCROSSING WITH A NEW OVERCROSSING, AND MODIFYING THE SOUTHBOUND OFF-RAMP IN CITY
Location Description: IN SONOMA COUNTY.
Contractor Name: Ghilotti Construction Company, Inc. (Chase McPhaul)
Contractor Address: 246 Ghilotti Avenue, Santa Rosa, CA 95407
Resident Engineer: Seyed "Syd" Valeh Structure Rep.: Anthony "Tony" Tierra; Sardar Chalabe
DIME Sample ID: 2025-04-23-85
TL Number from the TL Form:
Sample Submitted By Organization: Pavement Engineers
Sample Organization Contact: (530) 913-3751
Type of Sample: Quality Control
Type of Material: Concrete
Sample Taken Date: 04/23/2025
Date that the sample was received by the laboratory/organization performing the testing: 04/24/2025
The quantity of what the sample constitutes: 10CY
A brief description of the sample: concrete
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier:
Structure name: Hearn Ave. East and West
The fabricator/manufacturer/facility name: Superior Supplies Ready Mix
The concrete mix design number: 675cr1
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: 309601
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Back of Truck
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
DIME Test ID: 2025-04-23-85-1
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 09/10/2025
Date Tested: 04/30/2025
Submitted By Organization: Pavement Engineers
Organization Address: 3650 Industrial Boulevard,
Organization City: West Sacramento
Organization State: CA
Organization Zipcode: 95691
Organization Email: michelleh@pavementengineering.com
Organization Phone: (530) 913-3751
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
2
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C1231 - Unbonded Elastomeric Pad Cap
|
|
Apparent mass of submerged cylinder 1
|
no data0 lb
|
|
Average diameter of cylinder 1
|
4.00 in
|
|
Average diameter of cylinder 2
|
4.00 in
|
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
|
Compressive strength (to nearest 10 psi)
|
6220 psi
|
|
Maximum load on cylinder 1
|
76685 lb
|
|
Maximum load on cylinder 2
|
79710 lb
|
|
Type of fracture pattern of cylinder 1
|
4
|
|
Type of fracture pattern of cylinder 2
|
2
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Age of specimen
|
7 days
|
|
Age of specimen in hours
|
no data0 hours
|
|
Serial number of delivery ticket, if available
|
309601
|
DIME Test ID: 2025-04-23-85-2
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 09/10/2025
Date Tested: 05/21/2025
Submitted By Organization: Pavement Engineers
Organization Address: 3650 Industrial Boulevard,
Organization City: West Sacramento
Organization State: CA
Organization Zipcode: 95691
Organization Email: michelleh@pavementengineering.com
Organization Phone: (530) 913-3751
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
|
Unit system used?
|
US Units
|
|
Number of specimens
|
3
|
|
Test performed
|
With no density determined
|
|
Capped in accordance with?
|
ASTM C1231 - Unbonded Elastomeric Pad Cap
|
|
Apparent mass of submerged cylinder 1
|
no data0 lb
|
|
Average diameter of cylinder 1
|
4.00 in
|
|
Average diameter of cylinder 2
|
4.00 in
|
|
Average diameter of cylinder 3
|
4.00 in
|
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
|
Compressive strength (to nearest 10 psi)
|
8280 psi
|
|
Maximum load on cylinder 1
|
103845 lb
|
|
Maximum load on cylinder 2
|
107760 lb
|
|
Maximum load on cylinder 3
|
100715 lb
|
|
Type of fracture pattern of cylinder 1
|
2
|
|
Type of fracture pattern of cylinder 2
|
4
|
|
Type of fracture pattern of cylinder 3
|
4
|
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
|
Correction factor for cylinder 1
|
1
|
|
Correction factor for cylinder 2
|
1
|
|
Correction factor for cylinder 3
|
1
|
|
Age of specimen
|
28 days
|
|
Age of specimen in hours
|
no data0 hours
|
|
Serial number of delivery ticket, if available
|
309601
|